The server, its policies and counters, and the BACnet/SC hub. The Python reference lists every group. Each page opens with its main classes, then the other classes, the dictionaries (TypedDict) and the type aliases, in stub order.
BACnetServer
Section titled “BACnetServer”BACnet server that hosts objects and responds to client requests.
For SC, sc_ca_cert, sc_client_cert, and sc_client_key must be nonempty paths; omission, None, or empty strings raise ValueError at construction. Their None defaults preserve non-SC use and positional layout only. start() loads the explicit site CA and operational cert/key before dialing or draining registrations. Local TLS configuration errors raise RuntimeError; repair the files and retry on the same server. Later startup failures do not have a general registration rollback guarantee.
SC also requires keyword-only sc_device_uuid: exactly 16 bytes, not all zero, copied at construction. Missing, None, wrong length, or all-zero values raise ValueError after credential-presence validation, before file/network I/O. Provision before deployment and durably reuse the same UUID for the device’s lifetime. No generation, persistence, change detection, or version/variant enforcement is provided. Non-SC transports ignore this option.
Segmentation defaults to NONE. When enabled, apdu_segment_timeout_ms must be positive; it supplies Device APDU_SEGMENT_TIMEOUT, response SegmentACK waits, and the 4*Tseg receive inactivity timer. A separate 16-second no-progress resource limit aborts abandoned request transfers with OTHER.
Usage:
server = BACnetServer(device_instance=1234, device_name="My Device")server.add_analog_input(1, "Temperature", units=62)await server.start()BACnetServer.init
Section titled “BACnetServer.init”def __init__( self, device_instance: int, device_name: str = "BACnet Device", interface: str = "0.0.0.0", port: int = 0xBAC0, broadcast_address: str = "255.255.255.255", transport: str = "bip", sc_hub: Optional[str] = None, sc_vmac: Optional[bytes] = None, sc_ca_cert: Optional[str] = None, sc_client_cert: Optional[str] = None, sc_client_key: Optional[str] = None, sc_heartbeat_interval_ms: Optional[int] = None, sc_heartbeat_timeout_ms: Optional[int] = None, ipv6_interface: Optional[str] = None, dcc_password: Optional[str] = None, reinit_password: Optional[str] = None, *, mutation_policy: Literal["permissive", "deny_all"] | MutationHandler = "permissive", dcc_policy: str = "deny_all", dcc_source_restriction: list[tuple[int | None, bytes]] | None = None, dcc_disable_rate_limit: tuple[int, int] | None = None, serial_port: Optional[str] = None, mstp_baud: int = 38400, mstp_mac: int = 1, mstp_max_master: int = 127, mstp_max_info_frames: int = 1, mstp_extended_frames: bool = False, mstp_echo: bool = False, mstp_echo_grace_ms: Optional[int] = None, mstp_transmit_latency_pad_ms: Optional[int] = None, mstp_usage_timeout_ms: Optional[int] = None, mstp_reply_timeout_ms: Optional[int] = None, max_confirmed_in_flight: int = 64, max_unconfirmed_in_flight: int = 32, max_confirmed_in_flight_per_peer: int = 16, max_unconfirmed_in_flight_per_peer: int = 8, confirmed_recovery_reserve: int = 4, max_recovery_in_flight_per_peer: int = 1, rpm_max_result_elements: int = 256, rpm_max_service_ack_bytes: int = 16384, alarm_summary_max_objects: int = 4096, alarm_summary_max_service_ack_bytes: int = 16384, enrollment_summary_max_objects: int = 4096, enrollment_summary_max_service_ack_bytes: int = 16384, atomic_read_file_max_requested_stream_octets: int = 16384, atomic_read_file_max_requested_records: int = 256, atomic_read_file_max_service_ack_bytes: int = 16384, atomic_write_file_max_stream_payload_octets: int = 16384, atomic_write_file_max_records: int = 256, atomic_write_file_max_record_payload_bytes: int = 16384, read_range_max_returned_items: int = 256, read_range_max_service_ack_bytes: int = 16384, event_information_max_objects: int = 4096, event_information_max_returned_summaries: int = 256, event_information_max_service_ack_bytes: int = 16384, sc_device_uuid: Optional[bytes | bytearray] = None, registered_network_port: Optional[int] = None, cov_policy: CovPolicy | None = None, time_sync_policy: TimeSyncPolicy | None = None, share_port_by_address: bool = False, segmentation_supported: Segmentation = Segmentation.NONE, apdu_segment_timeout_ms: int = 5000, bbmd: Optional[Bbmd] = None, foreign_device: Optional[ForeignDevice] = None, multicast: Optional[Multicast] = None, sc_npdu_per_origin_limit: int | None = None, sc_control_rate_limit: tuple[int, int] | None = None, on_reinitialize: Optional[ReinitializeHandler] = None, after_reinitialize: Optional[AfterReinitialize] = None, router: Optional[BACnetRouter] = None,) -> Nonedcc_password and reinit_password hold 1 to 20
characters; a longer one (#2060) or an empty one (#2094) raises
ValueError here. None configures no password.
transport="router" with router (a BACnetRouter built
with application="client_and_server"): host the device on the
router’s own application entity (#2071), answering at the router’s
address on each of its networks, beside a BACnetClient on the
same router. start() takes the server’s share from the running
router, once per router start; before the router starts, or when a
server already took it, it raises RuntimeError. Confirmed requests
to the router reach this server, except confirmed COV notifications,
which go to the client, and confirmed event notifications, which
reach both with only this server’s answer sent; confirmed audit
notifications reach this server alone. Unconfirmed requests reach
both. A start refused before the server runs, such as for a
duplicate object name, leaves the share for the next start.
apdu_segment_timeout_ms must be under 60000. router without
transport="router", or the reverse, raises ValueError.
on_reinitialize (default None): carry out ReinitializeDevice
(#1566). It is called with a ReinitializeRequest once a request
has passed its password and state checks, while the server holds its
object database, so it must return at once: no awaiting, no blocking,
and no other rusty_bacnet call (one would raise RuntimeError).
That check sees only its own thread: never wait on the event loop or
another thread from it (run_coroutine_threadsafe(...).result(),
Thread.join, any future’s .result()), which deadlocks the
server. An async def handler is answered SERVICES / OTHER.
Return None or True to accept, False to refuse with SERVICES /
SERVICE_REQUEST_DENIED, or an (ErrorClass, ErrorCode) tuple to
refuse with those. An exception, or any other return value, answers
SERVICES / OTHER and goes to sys.unraisablehook. Without it every
request is refused. With it, a registered BBMD port’s BDT and
foreign-device rows take writes, which ACTIVATE_CHANGES or WARMSTART
puts into effect.
after_reinitialize (default None; needs on_reinitialize):
called with the ReinitializeRequest on the event loop that
started the server, once the accepted request’s SimpleACK has been
handed to the transport. Restart, back up or restore here. It never
runs for a refused request, nor after a stop() that began before
the hand-off. A coroutine it returns runs as a task. On MS/TP, handed
off means queued: the frame still waits for the token, so stopping
at once can drop the reply; wait a short while first.
share_port_by_address (B/IP only, default False): bind the
interface address itself, so devices on other addresses of this host
can share the port. Needs an explicit interface and a nonzero port;
broadcasts and unicast are still handled in the order they arrived.
bbmd / foreign_device (at most one, else ValueError): run
the device as a BBMD (B/IP only), or register it with a BBMD on
another subnet as a foreign device (#938). foreign_device also
applies to transport="ipv6" with a B/IPv6 BBMD (#1941). See
Bbmd and ForeignDevice. A registered Network Port reports
the mode in BACnet_IP_Mode (normal 0, foreign 1, BBMD 2), or on
B/IPv6 in BACnet_IPv6_Mode (normal 0, foreign 1).
registered_network_port (B/IP or B/IPv6, 1 to 255): the Network
Port object, added with add_bip_network_port (transport="bip")
or add_bip6_network_port (transport="ipv6"), that represents
the server’s link. Start checks the object’s address and UDP port
against the transport’s, then publishes the bound port. A B/IPv6
port also publishes its VMAC and multicast group, and reports
BACnet_IPv6_Mode NORMAL (0), or FOREIGN (1) with foreign_device=
and its FD_BBMD_Address and FD_Subscription_Lifetime rows. With
on_reinitialize, a client may write those two rows; a
ReinitializeDevice ACTIVATE_CHANGES then registers with the new
values at once.
sc_npdu_per_origin_limit (SC only, default None): maximum
queued, unconsumed NPDUs per ingress path and source. None keeps 32;
explicit values must be 1 through 256. Invalid values or a non-SC
transport raise ValueError before file or network I/O. Negative or
unrepresentably large values raise OverflowError. The aggregate
receive queue remains 256; see sc_npdu_drop_counts.
sc_control_rate_limit (SC only, default None): (burst, per_second), the network-layer messages one source may send back to
back and then each second (#1969). None keeps 256 then 32 a second.
The burst must be 1 through 4096 and the rate at least 1; invalid
values or a non-SC transport raise ValueError before file or network
I/O, and negative values raise OverflowError. A message over its
source’s budget is dropped and counted in control_rate_drops.
mstp_extended_frames (MS/TP only, default False): take and send
extended frames (Types 32 and 33), which carry NPDUs of up to 1497
octets, so the device accepts APDUs of up to 1476 instead of 480.
mstp_echo and mstp_echo_grace_ms (MS/TP only) declare an
adapter that returns every octet this station sends, as for
BACnetClient; a negative grace, or one above 4294967295, raises
OverflowError when the server is built.
mstp_transmit_latency_pad_ms, mstp_usage_timeout_ms and
mstp_reply_timeout_ms (MS/TP only) set the transmit-latency pad
and the two timeouts, in milliseconds, as for BACnetClient.
BACnetServer.add_analog_input
Section titled “BACnetServer.add_analog_input”def add_analog_input( self, instance: int, name: str, units: EngineeringUnits | int = 62, present_value: float = 0.0, *, tags: Optional[list[NameValue]] = None, profile_location: Optional[str] = None, profile_name: Optional[str] = None,) -> Nonetags, profile_location and profile_name provision the
optional Tags, Profile_Location and Profile_Name rows; each is served
only when given. Tags takes writes over the network, the other two
are read-only. A tag name with a semicolon, a tag value that isn’t
primitive, a location whose URI scheme isn’t http, https or bacnet,
or a profile name without its vendor-number prefix ("555-room")
raises BacnetProtocolError, and wrong shapes TypeError or
ValueError.
BACnetServer.add_analog_output
Section titled “BACnetServer.add_analog_output”def add_analog_output( self, instance: int, name: str, units: EngineeringUnits | int = 62, *, tags: Optional[list[NameValue]] = None, profile_location: Optional[str] = None, profile_name: Optional[str] = None,) -> NoneProfile keywords as on add_analog_input.
BACnetServer.add_analog_value
Section titled “BACnetServer.add_analog_value”def add_analog_value( self, instance: int, name: str, units: EngineeringUnits | int = 62, *, present_value_access: Literal["commandable", "writable", "read_only"] = "commandable", value_source_tracking: bool = False, audit_level: Literal["default", "none", "audit_config", "audit_all"] | None = None, auditable_operations: int | None = None, audit_priority_filter: int | Literal["inherit"] | None = None, tags: Optional[list[NameValue]] = None, profile_location: Optional[str] = None, profile_name: Optional[str] = None,) -> NoneOptional AV Audit rows: None is absent; priority ‘inherit’ is present NULL.
present_value_access is "commandable" (writes go through
Priority_Array), "writable" (a write replaces Present_Value) or
"read_only" (peers write it only while out of service).
value_source_tracking serves Value_Source on a noncommandable
object: the writer of the last Present_Value write, who alone may
then correct it. A commandable object tracks its sources through
Priority_Array already, so asking it to track raises ValueError.
Profile keywords as on add_analog_input.
BACnetServer.add_binary_input
Section titled “BACnetServer.add_binary_input”def add_binary_input( self, instance: int, name: str, *, tags: Optional[list[NameValue]] = None, profile_location: Optional[str] = None, profile_name: Optional[str] = None,) -> NoneProfile keywords as on add_analog_input.
BACnetServer.add_binary_output
Section titled “BACnetServer.add_binary_output”def add_binary_output( self, instance: int, name: str, *, tags: Optional[list[NameValue]] = None, profile_location: Optional[str] = None, profile_name: Optional[str] = None,) -> NoneProfile keywords as on add_analog_input.
BACnetServer.add_binary_value
Section titled “BACnetServer.add_binary_value”def add_binary_value( self, instance: int, name: str, *, present_value_access: Literal["commandable", "writable", "read_only"] = "commandable", value_source_tracking: bool = False, audit_level: Literal["default", "none", "audit_config", "audit_all"] | None = None, auditable_operations: int | None = None, audit_priority_filter: int | Literal["inherit"] | None = None, tags: Optional[list[NameValue]] = None, profile_location: Optional[str] = None, profile_name: Optional[str] = None,) -> NoneOptional BV Audit rows: None is absent; priority ‘inherit’ is present NULL.
Access, Value_Source and profile keywords as on add_analog_value.
BACnetServer.add_multistate_input
Section titled “BACnetServer.add_multistate_input”def add_multistate_input( self, instance: int, name: str, number_of_states: int, *, tags: Optional[list[NameValue]] = None, profile_location: Optional[str] = None, profile_name: Optional[str] = None,) -> NoneProfile keywords as on add_analog_input.
BACnetServer.add_multistate_output
Section titled “BACnetServer.add_multistate_output”def add_multistate_output( self, instance: int, name: str, number_of_states: int, *, tags: Optional[list[NameValue]] = None, profile_location: Optional[str] = None, profile_name: Optional[str] = None,) -> NoneProfile keywords as on add_analog_input.
BACnetServer.add_multistate_value
Section titled “BACnetServer.add_multistate_value”def add_multistate_value( self, instance: int, name: str, number_of_states: int, *, present_value_access: Literal["commandable", "writable", "read_only"] = "commandable", value_source_tracking: bool = False, tags: Optional[list[NameValue]] = None, profile_location: Optional[str] = None, profile_name: Optional[str] = None,) -> NoneAccess, Value_Source and profile keywords as on add_analog_value.
BACnetServer.add_calendar
Section titled “BACnetServer.add_calendar”def add_calendar( self, instance: int, name: str, *, date_list: Optional[list[CalendarEntry]] = None,) -> Nonedate_list seeds Date_List with calendar entries, the form a typed
read of it gives. An entry the Calendar refuses, such as a month
outside 1 to 14 or 255, raises BacnetProtocolError (VALUE_OUT_OF_RANGE)
and nothing is registered; wrong shapes raise TypeError or
ValueError.
BACnetServer.add_schedule
Section titled “BACnetServer.add_schedule”def add_schedule( self, instance: int, name: str, *, weekly_schedule: Optional[list[list[TimeValue]]] = None, exception_schedule: Optional[list[SpecialEvent]] = None, effective_period: Optional[tuple[BACnetDate, BACnetDate]] = None,) -> NoneAdd a Schedule object; Schedule_Default is NULL.
The keywords take the forms typed reads of the properties give, so a
read’s .value builds the same Schedule: weekly_schedule seven
days, Monday first, each a list of (time, value) pairs;
exception_schedule a list of SpecialEvent mappings;
effective_period a (start_date, end_date) pair, each date
specific or wholly unspecified (the default covers every date). What
the Schedule refuses, such as a time given twice in a day, a value
that isn’t primitive or a priority outside 1 to 16, raises
BacnetProtocolError and nothing is registered.
BACnetServer.add_date_value
Section titled “BACnetServer.add_date_value”def add_date_value(self, instance: int, name: str) -> NoneBACnetServer.add_time_value
Section titled “BACnetServer.add_time_value”def add_time_value(self, instance: int, name: str) -> NoneBACnetServer.add_date_time_value
Section titled “BACnetServer.add_date_time_value”def add_date_time_value(self, instance: int, name: str) -> NoneBACnetServer.add_date_pattern_value
Section titled “BACnetServer.add_date_pattern_value”def add_date_pattern_value(self, instance: int, name: str) -> NoneBACnetServer.add_time_pattern_value
Section titled “BACnetServer.add_time_pattern_value”def add_time_pattern_value(self, instance: int, name: str) -> NoneBACnetServer.add_date_time_pattern_value
Section titled “BACnetServer.add_date_time_pattern_value”def add_date_time_pattern_value(self, instance: int, name: str) -> NoneBACnetServer.add_notification_class
Section titled “BACnetServer.add_notification_class”def add_notification_class( self, instance: int, name: str, notification_class: int = 0, storage_path: Optional[str] = None, *, recipients: Optional[list[Destination]] = None,) -> NoneAdd a Notification Class (Clause 12.21). With storage_path, a
Recipient_List a client writes is kept in that file across restarts; a
write whose list cannot be saved is refused with DEVICE /
OPERATIONAL_PROBLEM and the old list stays. Without it the list lives in
memory only.
storage_path is a str; a pathlib.Path raises TypeError, as
for add_notification_forwarder. Give each class a file of its own:
the file names the class it belongs to, so one that holds another
object’s list, or anything this backend did not write, makes this call
raise BacnetError (BacnetProtocolError for a saved list a client’s write
would be refused).
recipients seeds Recipient_List with Destination mappings, in
order, with the checks and errors add_notification_forwarder’s
recipients has: more than 32, or an address MAC past 18 octets,
raises BacnetProtocolError, and nothing is registered. With
storage_path, a Recipient_List a client wrote, once saved, wins:
until a write sets the list, the seed applies at every start and is
not saved.
BACnetServer.add_notification_forwarder
Section titled “BACnetServer.add_notification_forwarder”def add_notification_forwarder( self, instance: int, name: str, process_identifier_filter: Optional[int] = None, local_forwarding_only: bool = False, storage_path: Optional[str] = None, *, recipients: list[Destination] | None = None, port_filter: list[tuple[int, bool]] | None = None,) -> NoneAdd a Notification Forwarder (Clause 12.51) that sends the event
notifications this server receives on to its Recipient_List and
Subscribed_Recipients. process_identifier_filter=None forwards every
process identifier. With storage_path, Recipient_List and
Subscribed_Recipients are kept in that file across restarts.
recipients seeds Recipient_List in order; more than 32 destinations,
or an address MAC past 18 octets, raises BacnetProtocolError, as a
client’s write would be refused. With storage_path, a
Recipient_List a client wrote, once saved, wins over the seed. port_filter serves Port_Filter as
(port_id, enabled) pairs; the server receives through Port_ID 0.
Without it Port_Filter is absent.
BACnetServer.add_trend_log
Section titled “BACnetServer.add_trend_log”def add_trend_log( self, instance: int, name: str, buffer_size: int = 100, *, reference: tuple[ObjectIdentifier, PropertyIdentifier] | tuple[ObjectIdentifier, PropertyIdentifier, Optional[int]] | DeviceObjectPropertyReference | None = None, log_interval: int | None = None, logging_type: Literal["polled", "triggered", "cov"] | None = None, client_cov_increment: float | None = None, cov_resubscription_interval: int | None = None, start_time: tuple[tuple[int, int, int, int], tuple[int, int, int, int]] | None = None, stop_time: tuple[tuple[int, int, int, int], tuple[int, int, int, int]] | None = None, align_intervals: bool | None = None, interval_offset: int | None = None, storage_path: Optional[str] = None, total_record_count: int = 0,) -> NoneAdd a Trend Log (Clause 12.25) that the server polls, triggers or logs by COV (before starting).
reference sets Log_DeviceObjectProperty, one element in any form
add_trend_log_multiple takes for members. log_interval,
start_time, stop_time, align_intervals and
interval_offset are as there. logging_type "polled" with
no log_interval takes a one-minute interval; "triggered"
zeroes Log_Interval and makes it read-only, so a log_interval
with it raises BacnetProtocolError (WRITE_ACCESS_DENIED); "cov"
zeroes it too, and a nonzero log_interval then turns the log back
to polled (Clause 12.25.9). Any other string raises ValueError, and
so does "polled" with log_interval=0, a pair that would make a
COV log; log_interval=0 alone leaves the new log polled and idle.
While COV, the poller looks at the referenced property of this
device on each pass and logs it, with its object’s Status_Flags,
whenever it changes as a COV notification would report it. Enable
turned off and on again within one pass (about 100 ms) isn’t seen.
client_cov_increment (a REAL) is the increment a numeric value is
held to; None, the default, is NULL: the object’s own COV_Increment
for a numeric Present_Value, any change otherwise. A negative or
non-finite one raises BacnetProtocolError (VALUE_OUT_OF_RANGE).
cov_resubscription_interval is in seconds, nonzero; it is served
but unused, since the server doesn’t subscribe to other devices: a
reference to one logs a single OPTIONAL_FUNCTIONALITY_NOT_SUPPORTED
failure.
Log_DeviceObjectProperty reads as one
device_object_property_reference value whose mapping includes all
four keys; while unset its object is Analog Input
4194303’s Present_Value, and writing a reference to instance 4194303
unsets it. A null written to it succeeds and changes nothing.
total_record_count seeds Total_Record_Count, an Unsigned32, so
the log’s first record is numbered one past it: seeded at
4294967294, records number 4294967295, then 1, 2 and on, which lets
a reader’s handling of the wrap be tested. Out of range raises
OverflowError.
storage_path keeps the log in files, as on
add_trend_log_multiple. client_cov_increment and
cov_resubscription_interval aren’t saved: they apply on every
start, reopened or not.
BACnetServer.add_trend_log_multiple
Section titled “BACnetServer.add_trend_log_multiple”def add_trend_log_multiple( self, instance: int, name: str, buffer_size: int = 100, *, members: Optional[list[tuple[ObjectIdentifier, PropertyIdentifier] | tuple[ObjectIdentifier, PropertyIdentifier, Optional[int]] | DeviceObjectPropertyReference]] = None, log_interval: int | None = None, logging_type: Literal["polled", "triggered"] | None = None, start_time: tuple[tuple[int, int, int, int], tuple[int, int, int, int]] | None = None, stop_time: tuple[tuple[int, int, int, int], tuple[int, int, int, int]] | None = None, align_intervals: bool | None = None, interval_offset: int | None = None, storage_path: Optional[str] = None, total_record_count: int = 0,) -> NoneAdd a Trend Log Multiple (Clause 12.30) that the server polls or triggers, logging one value per member in each record.
members fills Log_DeviceObjectProperty in order, each an
(object, property) or (object, property, array_index) tuple
or a DeviceObjectPropertyReference mapping; one naming this
server’s Device is kept in its local form. More than 64 raises
BacnetProtocolError (NO_SPACE_TO_WRITE_PROPERTY), and a
device_identifier that isn’t a Device raises ValueError.
log_interval is in hundredths of a second. logging_type
"polled" with no log_interval takes a one-minute interval;
"triggered" zeroes Log_Interval and makes it read-only, so a
log_interval with it raises BacnetProtocolError
(WRITE_ACCESS_DENIED). "cov" raises BacnetProtocolError
(VALUE_OUT_OF_RANGE), as a client’s write of COV does, since a Trend
Log Multiple never logs by COV; any other string raises ValueError. With neither, Log_Interval stays 0 and
nothing is polled.
start_time and stop_time bound when records are kept, each a
((full_year, month, day, day_of_week), (hour, minute, second, hundredths)) pair: every field 255 leaves that side open, 255
seconds or hundredths count as zero, and anything else that isn’t an
actual date and time raises BacnetProtocolError (VALUE_OUT_OF_RANGE). Records are kept from the
start up to, not including, the stop, and each opening and closing
is logged. align_intervals aligns a polled log’s acquisitions to
the clock when Log_Interval divides a day, shifted by
interval_offset hundredths (modulo Log_Interval).
Peers can write each of these. To ask a triggered log for one
record, write Trigger TRUE, from a peer or with
write_property_local; it reads TRUE until the poller acquires
the record. Read the records with read_range.
total_record_count seeds Total_Record_Count as on
add_trend_log.
storage_path keeps the log in <storage_path>.slot0 and
.slot1. It is a str; a pathlib.Path raises TypeError. The
log commits a snapshot every 100 records or, while it changes, once a
minute, and once more at stop(), so a power loss costs at most
about a minute of records; a failed commit is retried. A log reopened
from those files serves its saved records, Total_Record_Count,
BUFFER_READY counts and Notification_Threshold, Enable,
Stop_When_Full and every setting a peer can write, and appends one
LOG_INTERRUPTED record to mark the restart (none when it reopens full
and stopped); the saved state wins over the keyword arguments.
buffer_size wins over the saved Buffer_Size: a smaller one keeps
the newest records. A durable Trend Log Multiple holds at most 15849
records (178437 for an Event Log, 828302 for a Trend Log); a larger
buffer_size, or a file pair that can’t be read or holds another
object’s state, raises BacnetError. To tell whether a log will
reopen, check whether either slot file exists before the call. The
files outlive the log: one added again on them reopens.
BACnetServer.add_event_log
Section titled “BACnetServer.add_event_log”def add_event_log( self, instance: int, name: str, buffer_size: int = 100, log_received_notifications: bool = False, *, storage_path: Optional[str] = None, total_record_count: int = 0,) -> NoneRegister an Event Log of buffer_size records before start().
The log records each event notification the server builds. With
log_received_notifications it also records the Confirmed and
UnconfirmedEventNotifications the server receives, unicast or
broadcast, as they decoded; each source is held to a few records a
second, and the rest show in event_notification_counters() as
received_not_logged.
The log reports BUFFER_READY to its Notification Class once its
Notification_Threshold is set (zero, the default, reports nothing);
write it and Notification_Class with write_property_local or
from a peer.
total_record_count seeds Total_Record_Count as on
add_trend_log; BUFFER_READY counts from the seeded value.
storage_path keeps the log in files, as on
add_trend_log_multiple. log_received_notifications isn’t
saved and applies on every start.
BACnetServer.add_audit_log
Section titled “BACnetServer.add_audit_log”def add_audit_log( self, instance: int, name: str, storage_path: str, buffer_size: int = 100,) -> NoneBACnetServer.add_device_binding
Section titled “BACnetServer.add_device_binding”def add_device_binding(self, device_instance: int, address: str) -> NoneRegister a direct B/IP (IPv4) Device binding on a transport=“bip” server.
Accept IPv4:port or exactly six hex bytes (four IPv4 octets and two port octets). Other transports or parsed address lengths raise ValueError without retention. The shared parser’s broader grammar remains available to other APIs, not bindings. Invalid instance/address or duplicate Device raises ValueError. No overwrite, routing or discovery. Syntax validation precedes the frozen-state check; after start() consumes configuration, parseable calls raise RuntimeError before the transport/shape checks, including after stop. start() refuses a binding at a broadcast or other group address of the link (a multicast address, 255.255.255.255, or the broadcast IP at another port), raising BacnetError naming the device and the address; bind each device at its unicast address.
BACnetServer.configure_audit_log_parent
Section titled “BACnetServer.configure_audit_log_parent”def configure_audit_log_parent( self, instance: int, *, parent_device_instance: int, parent_audit_log_instance: int,) -> NoneSet a registered Audit Log’s remote parent; valid pre-start calls replace it.
Identifiers are integers in 0..=4194303, not bool. Invalid/missing/duplicate local logs or a local parent Device raise ValueError without mutation. Startup revalidates local identity; settings freeze at ownership transfer. Reapply on a new server after reopen. Only the selected inbound sink forwards, using a configured direct B/IP binding with the existing one-attempt confirmed policy, never deletion or a durable queue. IPv6/SC/MS/TP forwarding is not exposed.
BACnetServer.configure_audit_notification_sink
Section titled “BACnetServer.configure_audit_notification_sink”def configure_audit_notification_sink( self, instance: int, *, policy: Literal["deny_all", "allow_all"],) -> NoneSelect one registered Audit Log before start(); omission denies receipt.
Invalid policy/instance, missing or duplicate log raises ValueError without mutation. Startup revalidates before transport preparation/registration transfer. A running server raises RuntimeError. Payload Source_Device and Target_Device remain peer-reported, not verified origin. No Python callbacks.
BACnetServer.add_audit_reporter
Section titled “BACnetServer.add_audit_reporter”def add_audit_reporter(self, instance: int, name: str) -> NoneBACnetServer.configure_audit_recipient
Section titled “BACnetServer.configure_audit_recipient”def configure_audit_recipient(self, recipient: AuditRecipientInput) -> NoneProvision the copied Device-owned recipient before startup.
Accepts a concrete remote Device (not instance 4194303), or a supported direct unicast IPv4 BACnetAddress on B/IP. The selected target Reporter requires provision even at Audit_Level NONE. Add Device routes with add_device_binding independently. Missing Device routes start with CONFIGURATION_ERROR; live changes require usable old and new routes. This setter freezes at ownership transfer. Use Device property writes after start for atomic old/new delivery. No NULL recipient sentinel.
BACnetServer.configure_audit_reporters
Section titled “BACnetServer.configure_audit_reporters”def configure_audit_reporters(self, reporters: list[AuditReporterConfiguration]) -> NoneReplace the complete target Reporter set before start (one through 64).
Each configuration identifies a registered concrete Reporter (0..4194302).
Invalid instance values (including bool and non-int), duplicate identities,
invalid settings or missing objects raise ValueError. Wrong container types
and wrong types for other setting fields raise TypeError. The entire input
is copied and validated before pending changes. Startup freezes this API.
Omitted optional fields reset to catch-all selectors, all priorities and
absent delay/control properties. maximum_send_delay accepts None or an
integer 0..3600: zero exposes immediate Maximum_Send_Delay/Send_Now;
positive values enable bounded ordinary target batching. Bool/non-integer
delay raises TypeError; an integer outside unsigned32 raises
OverflowError and one past 3600 ValueError. An instance,
auditable_operations or audit_priority_filter outside its
integer type (unsigned32, unsigned64, unsigned16) raises OverflowError
too.
Enabled nominal overlaps expose CONFIGURATION_ERROR on every affected
Reporter’s RELIABILITY; the lowest instance emits, before operation filters.
Empty/all-None selectors select no nominal targets. Mandatory Reporter
writes and Device recipient changes have separate bounded capture rules.
All Reporters use the one provisioned Device recipient and share the same
64-operation admission budget. Source reporting remains exactly one.
BACnetServer.add_loop
Section titled “BACnetServer.add_loop”def add_loop( self, instance: int, name: str, output_units: EngineeringUnits | int = 62, *, controlled_variable_units: Optional[EngineeringUnits | int] = None, proportional_constant_units: Optional[EngineeringUnits | int] = None, integral_constant_units: Optional[EngineeringUnits | int] = None, derivative_constant_units: Optional[EngineeringUnits | int] = None, priority_for_writing: Optional[int] = None,) -> NoneAdd a Loop (PID) object to the server (before starting).
The keyword arguments set rows that are read-only over the network: Controlled_Variable_Units and the three gain units rows (NO_UNITS when omitted) and Priority_For_Writing (16 when omitted). Units above 65535 or a priority outside 1..=16 raise BacnetProtocolError with VALUE_OUT_OF_RANGE; a priority outside 0..=255 raises OverflowError. Peers can write Action (DIRECT until written).
Controlled_Variable_Reference and Manipulated_Variable_Reference read
as application_data holding the context-tagged reference; while
unset they name instance 4194303 (an Analog Input and an Analog Output
respectively), and writing a reference to that instance unsets them.
A null written to any Loop reference succeeds and changes nothing.
BACnetServer.add_command
Section titled “BACnetServer.add_command”def add_command( self, instance: int, name: str, *, action: Optional[list[list[ActionCommand]]] = None, action_text: Optional[list[str]] = None,) -> NoneAdd a Command object; writing N to its Present_Value runs action[N-1].
action_text serves Action_Text and needs one text per list. A
command whose device_identifier isn’t a Device raises ValueError.
A priority outside 1..=16, a value with no encoding, or a text count
that differs from the list count raises BacnetProtocolError with
VALUE_OUT_OF_RANGE.
BACnetServer.add_timer
Section titled “BACnetServer.add_timer”def add_timer(self, instance: int, name: str) -> NoneBACnetServer.add_load_control
Section titled “BACnetServer.add_load_control”def add_load_control(self, instance: int, name: str) -> NoneBACnetServer.add_program
Section titled “BACnetServer.add_program”def add_program(self, instance: int, name: str) -> NoneBACnetServer.add_lighting_output
Section titled “BACnetServer.add_lighting_output”def add_lighting_output( self, instance: int, name: str, *, high_end_trim: Optional[float] = None, low_end_trim: Optional[float] = None, trim_fade_time: Optional[int] = None, color_reference: Optional[ObjectIdentifier] = None, color_override: Optional[bool] = None, override_color_reference: Optional[ObjectIdentifier] = None, tags: Optional[list[NameValue]] = None, profile_location: Optional[str] = None, profile_name: Optional[str] = None,) -> NoneAdd a Lighting Output object.
Its Lighting_Command reads and writes as application_data holding
the context-tagged BACnetLightingCommand, operation NONE
(b"\x09\x00") until written. An octet_string or any other
datatype is refused with INVALID_DATA_TYPE, and a command its operation
can’t take with VALUE_OUT_OF_RANGE. The object carries each command
out: a fade or ramp puts its level in Present_Value at once and moves
Tracking_Value there over time, with In_Progress showing FADE_ACTIVE
or RAMP_ACTIVE; a step changes the level at once; and with
Blink_Warn_Enable TRUE the warn commands hold the level for
Egress_Time seconds before relinquishing or turning it off.
A Present_Value or Relinquish_Default level above 0.0 and below 1.0 is stored as 1.0, and one outside 0.0 to 100.0 is refused with VALUE_OUT_OF_RANGE, but for Present_Value’s warn values -1.0 (WARN), -2.0 (WARN_RELINQUISH) and -3.0 (WARN_OFF). Tracking_Value reads the same level as Present_Value whenever no fade or ramp is running.
high_end_trim and low_end_trim (1.0 to 100.0 percent) serve
the trims that bound Tracking_Value, and with either one
Trim_Fade_Time, set in milliseconds (0 to 86400000) by
trim_fade_time; without a trim none of the three rows is served.
A value out of range raises BacnetProtocolError (VALUE_OUT_OF_RANGE).
The colour keywords are as on add_binary_lighting_output, and the
profile keywords as on add_analog_input.
BACnetServer.add_binary_lighting_output
Section titled “BACnetServer.add_binary_lighting_output”def add_binary_lighting_output( self, instance: int, name: str, *, color_reference: Optional[ObjectIdentifier] = None, color_override: Optional[bool] = None, override_color_reference: Optional[ObjectIdentifier] = None, tags: Optional[list[NameValue]] = None, profile_location: Optional[str] = None, profile_name: Optional[str] = None,) -> NoneAdd a Binary Lighting Output object.
color_reference serves Color_Reference, the Color or Color
Temperature object the output takes its colour from (instance
4194303 names none). override_color_reference adds Color_Override
and Override_Color_Reference, and color_override=True turns the
override on; it needs an override_color_reference, and both need
a color_reference (ValueError otherwise). color_override=False
on its own means no override. A reference to another object type raises
BacnetProtocolError (VALUE_OUT_OF_RANGE). All three rows take writes;
lighting_color follows them. Profile keywords as on
add_analog_input.
BACnetServer.add_color
Section titled “BACnetServer.add_color”def add_color( self, instance: int, name: str, *, present_value: Optional[tuple[float, float]] = None, default_color: Optional[tuple[float, float]] = None, storage_path: Optional[str] = None, value_source_tracking: bool = False, tags: Optional[list[NameValue]] = None, profile_location: Optional[str] = None, profile_name: Optional[str] = None,) -> NoneAdd a Color object: a CIE 1931 xy colour, D65 white
(0.3127, 0.3290) unless present_value gives an (x, y)
pair, each 0.0 to 1.0 (BacnetProtocolError otherwise). It reads as a
list of two real values. value_source_tracking serves
Value_Source, the writer of the last Present_Value or Color_Command
that set it. Profile keywords as on add_analog_input.
At start the server drives the output to default_color (D65
unless given), at once, over any present_value. (0.0, 0.0)
keeps the colour from before the restart instead, kept in
storage_path (the file the object keeps Present_Value in); with
nothing stored it keeps present_value, and with neither,
In_Progress reads NOT_CONTROLLED until a write drives the output.
A file that doesn’t load raises BacnetError.
BACnetServer.add_color_temperature
Section titled “BACnetServer.add_color_temperature”def add_color_temperature( self, instance: int, name: str, *, present_value: Optional[int] = None, min_pres_value: Optional[int] = None, max_pres_value: Optional[int] = None, default_color_temperature: Optional[int] = None, storage_path: Optional[str] = None, value_source_tracking: bool = False, tags: Optional[list[NameValue]] = None, profile_location: Optional[str] = None, profile_name: Optional[str] = None,) -> NoneAdd a Color Temperature object: a correlated colour temperature in
kelvin, 4000 unless present_value says otherwise.
min_pres_value and max_pres_value narrow the 1000 to 30000
range and come together (ValueError otherwise); present_value is
clamped to them. A value out of range raises BacnetProtocolError.
value_source_tracking is as on add_color.
default_color_temperature (4000 unless given, clamped to the
limits) and storage_path work as default_color and
storage_path on add_color, with 0 keeping the temperature
from before the restart.
BACnetServer.add_channel
Section titled “BACnetServer.add_channel”def add_channel( self, instance: int, name: str, channel_number: int, members: Optional[list[tuple[ObjectIdentifier, PropertyIdentifier] | tuple[ObjectIdentifier, PropertyIdentifier, Optional[int]] | DeviceObjectPropertyReference]] = None, execution_delay: Optional[list[int]] = None, control_groups: Optional[list[int]] = None, *, allow_group_delay_inhibit: bool = False,) -> NoneAdd a Channel; a write of its Present_Value is passed on to members.
channel_number (0..=65535) is the number a WriteGroup names. Each
member is an (object, property) or (object, property, array_index) tuple for a property in this device, or a
DeviceObjectPropertyReference mapping; one naming this server’s
Device is kept in its local form, and one naming another Device is
written there through the server’s device bindings
(add_device_binding or a heard I-Am). execution_delay holds
one delay in milliseconds per member (zeros when omitted),
control_groups the WriteGroup groups the Channel is in ([0],
none, when omitted), and allow_group_delay_inhibit lets a
WriteGroup that asks for no delays skip them. All of them are
writable over the network too.
A wrong shape or type raises TypeError. An unknown or missing mapping key or a device that isn’t a Device raises ValueError. A channel number outside unsigned16, or an index (a tuple’s or a mapping’s), a delay or a group outside unsigned32, raises OverflowError. A delay count that differs from the member count or an empty group list raises BacnetProtocolError with VALUE_OUT_OF_RANGE; more than 1024 members or 64 groups, NO_SPACE_TO_WRITE_PROPERTY. Nothing is registered after any of them.
BACnetServer.add_life_safety_point
Section titled “BACnetServer.add_life_safety_point”def add_life_safety_point(self, instance: int, name: str) -> NoneBACnetServer.add_life_safety_zone
Section titled “BACnetServer.add_life_safety_zone”def add_life_safety_zone(self, instance: int, name: str) -> NoneBACnetServer.add_group
Section titled “BACnetServer.add_group”def add_group( self, instance: int, name: str, members: Optional[list[tuple[ObjectIdentifier, list[tuple[PropertyIdentifier, Optional[int]]]]]] = None,) -> NoneGroup whose Present_Value is rebuilt from members on each read.
members has the read_property_multiple spec shape and the
endpoint add_group checks: a member with no properties, or one
reporting a group’s Present_Value, raises ValueError naming its
position and the rule. Any property identifier is taken, those ASHRAE
assigns above 4194303 included. Indexes outside unsigned32 raise
OverflowError.
BACnetServer.add_global_group
Section titled “BACnetServer.add_global_group”def add_global_group( self, instance: int, name: str, *, members: Optional[list[tuple[ObjectIdentifier, PropertyIdentifier] | tuple[ObjectIdentifier, PropertyIdentifier, Optional[int]] | DeviceObjectPropertyReference]] = None,) -> NoneAdd a Global Group object; members seeds Group_Members, in the
form a typed read of it gives. A member naming this server’s Device
is stored in its local form, and a device identifier that isn’t a
Device raises ValueError.
BACnetServer.add_structured_view
Section titled “BACnetServer.add_structured_view”def add_structured_view(self, instance: int, name: str) -> NoneBACnetServer.add_access_door
Section titled “BACnetServer.add_access_door”def add_access_door( self, instance: int, name: str, *, door_members: Optional[list[ObjectIdentifier | tuple[ObjectIdentifier, ObjectIdentifier]]] = None, alarm_values: Optional[list[int]] = None, fault_values: Optional[list[int]] = None, masked_alarm_values: Optional[list[int]] = None,) -> NoneAdd an Access Door object to the server (before starting).
door_members sets Door_Members, the objects that make up the door
(read-only over the network). Each element is an ObjectIdentifier
in this device or a (device, object) pair of identifiers for one
in another device. A pair whose device isn’t a Device object
identifier raises ValueError, and nothing is registered.
alarm_values, fault_values and masked_alarm_values set the
starting Alarm_Values, Fault_Values and Masked_Alarm_Values, as
BACnetDoorAlarmState numbers other than NORMAL (1 to 8, or 256 to
65535); peers can write all three. Door_Alarm_State stays NORMAL or a member of the
alarm or fault values, never a masked state: a simulated value
outside them is refused, and masking the current state returns the
door to NORMAL. An alarm value raises a CHANGE_OF_STATE alarm after
Time_Delay, and a fault value makes Reliability MULTI_STATE_FAULT. Any
other number, NORMAL (0) included, raises BacnetProtocolError with
VALUE_OUT_OF_RANGE, and nothing is registered.
BACnetServer.add_access_credential
Section titled “BACnetServer.add_access_credential”def add_access_credential( self, instance: int, name: str, *, assigned_access_rights: Optional[list[AssignedAccessRights]] = None, authorization_exemptions: Optional[list[int]] = None,) -> NoneConfigure a credential before starting; invalid input registers nothing.
Assignments default to an empty array. Each mapping needs its reference and an actual bool enable flag. Missing/unknown keys or a non-Device device member raise ValueError; incorrect Python types raise TypeError. Wrong object kinds raise BacnetProtocolError PROPERTY/VALUE_OUT_OF_RANGE, except instance 4194303, the existing unused marker.
Omitted/None exemptions leave the optional row absent; [] serves an empty row. Integers 0..6 and 64..255 are accepted by the Rust setter. Bool/non-int elements raise TypeError; values outside u32 raise OverflowError; reserved values within u32 raise BacnetProtocolError PROPERTY/VALUE_OUT_OF_RANGE. Value 2 exempts this rights criterion only.
BACnetServer.evaluate_access_rights
Section titled “BACnetServer.evaluate_access_rights”def evaluate_access_rights( self, credential: ObjectIdentifier, point: ObjectIdentifier,) -> Awaitable[AccessRightsEvaluation]Inspect the native local rights stage (Clause 12.34.9.2).
Returns a plain mapping. Every key is present; access_event and rule are None where inapplicable. A rule index is its one-based position in the positive/negative array. Unresolved assignments retain their original one-based indices, order, duplicates and device references; skipped entries do not compact later indices. Granted may coexist with unresolved rights; exempt has no unresolved entries.
Granted means this stage passed, not final authorization. Exempt applies only to this criterion (Clause 12.35.25). The denial event is evidence, not a recorded Access_Event. No remote reads, COV/event reports or physical actions occur. Credential validity, point health, threat, accompaniment, passback and occupancy remain separate checks.
Requires a started server (RuntimeError otherwise). Missing or wrong object types raise BacnetProtocolError OBJECT/UNKNOWN_OBJECT, checking the credential first. Future unmapped result variants raise RuntimeError.
BACnetServer.add_access_point
Section titled “BACnetServer.add_access_point”def add_access_point( self, instance: int, name: str, *, access_doors: Optional[list[ObjectIdentifier | tuple[ObjectIdentifier, ObjectIdentifier]]] = None, number_of_authentication_policies: Optional[int] = None, authentication_policies: Optional[list[tuple[str, AuthenticationPolicy]]] = None, supported_authorization_modes: Optional[list[int]] = None, priority_for_writing: Optional[int] = None,) -> NoneAdd an Access Point object to the server (before starting).
access_doors sets Access_Doors (read-only over the network), in the
element forms add_access_door takes for door_members. A pair
whose device isn’t a Device object identifier raises ValueError, and a
reference to anything but an Access Door raises BacnetProtocolError
with VALUE_OUT_OF_RANGE; either way nothing is registered.
number_of_authentication_policies (1 when omitted, never 0) and
priority_for_writing (16 when omitted, else 1 to 16; outside
0..=255 OverflowError) set Number_Of_Authentication_Policies and
Priority_For_Writing, which are read-only over the network. supported_authorization_modes lists
the BACnetAuthorizationMode numbers the application carries out, the
values a write of Authorization_Mode can take: AUTHORIZE (0) alone
when omitted, and AUTHORIZE must be in any list given; proprietary
modes run from 64 to 65535. A value outside those raises
BacnetProtocolError with VALUE_OUT_OF_RANGE. Peers write
Active_Authentication_Policy (1 to the policy count) and
Authorization_Mode (one of the supported modes).
authentication_policies sets Authentication_Policy_List and
Authentication_Policy_Names as (name, policy) pairs, both
read-only over the network, and the policy count to their number. A
policy’s entries name the Credential Data Inputs and the step each
serves, from 1. An empty list, or more than 256 pairs, raises
BacnetProtocolError with VALUE_OUT_OF_RANGE; an index or timeout
outside 0..=4294967295 raises OverflowError. A policy with no
entries, a reference to anything but a Credential Data Input, or
indexes that don’t start at 1 and climb by at most one is kept but
can’t be in effect: while it is, Active_Authentication_Policy reads 0
until a peer writes a usable policy. While any such policy is listed,
or the active policy is 0, Reliability reads CONFIGURATION_ERROR and
the point takes no access events. A
number_of_authentication_policies given as well is applied after
and resizes both arrays, new policies empty and new names ""; it
can be at most 256 with the pairs (VALUE_OUT_OF_RANGE above).
BACnetServer.add_access_rights
Section titled “BACnetServer.add_access_rights”def add_access_rights( self, instance: int, name: str, *, positive_access_rules: Optional[list[AccessRule]] = None, negative_access_rules: Optional[list[AccessRule]] = None, enable: bool = True, accompaniment: Optional[ObjectIdentifier | tuple[ObjectIdentifier, ObjectIdentifier]] = None, storage_path: Optional[str] = None,) -> NoneAdd an Access Rights object to the server (before starting).
positive_access_rules and negative_access_rules set the two
rule arrays as AccessRule mappings, and enable sets Enable
(PropertyIdentifier.LOG_ENABLE, property 133), whose FALSE
disables every rule. Peers can write all three over the network. A
wrong shape or type raises TypeError, an unknown or missing key or a
device that isn’t a Device raises ValueError, and a location naming
anything but an Access Point or Access Zone raises BacnetProtocolError
with VALUE_OUT_OF_RANGE, and so does a list of more than 1024 rules
(NO_SPACE_TO_WRITE_PROPERTY). Nothing is registered after any of
them. The server stores and serves the rules. Applications can call
evaluate_access_rights to inspect the local rights stage.
accompaniment serves the optional Accompaniment row: the Access
Rights, Access Credential or Access User object that a second
credential, presented with the first, has to match. It takes an
ObjectIdentifier in this device or a (device, object) pair,
as door_members does; instance 4194303 asks for no
accompaniment. Left out, the object has no Accompaniment row and
clients can’t add one; once served, clients can write it. A pair
whose device isn’t a Device raises ValueError, and any other object
type raises BacnetProtocolError with VALUE_OUT_OF_RANGE. A read
gives the reference back in the form the keyword takes.
With storage_path, a rule array, Enable or Accompaniment that a
client writes is kept in that file across restarts, and wins over the
keyword given for it at the next start, which is then checked but not
applied; a saved Accompaniment is served even without the keyword.
To lift a saved requirement, write the no-accompaniment reference
(instance 4194303), which keeps the row; to drop the row, remove the
storage file, which also drops the saved rules and Enable. A
write that cannot be saved is refused with DEVICE /
OPERATIONAL_PROBLEM and the old value stays. Without it, written
values live in memory only. storage_path is a str; a
pathlib.Path raises TypeError. Give each object a file of its
own: one that holds another object’s state, or anything this backend
did not write, makes this call raise BacnetError
(BacnetProtocolError for a saved rule or Accompaniment the object
would refuse).
BACnetServer.add_access_user
Section titled “BACnetServer.add_access_user”def add_access_user( self, instance: int, name: str, *, credentials: Optional[list[ObjectIdentifier | tuple[ObjectIdentifier, ObjectIdentifier]]] = None, members: Optional[list[ObjectIdentifier | tuple[ObjectIdentifier, ObjectIdentifier]]] = None, member_of: Optional[list[ObjectIdentifier | tuple[ObjectIdentifier, ObjectIdentifier]]] = None,) -> NoneAdd an Access User object to the server (before starting).
credentials sets Credentials, the Access Credential objects the
user holds, and members and member_of set Members and
Member_Of, the Access Users one level below and above this one in a
hierarchy of users. All three are read-only over the network and
take the element forms add_access_door takes for
door_members. A pair whose device isn’t a Device object
identifier raises ValueError, and a reference to anything but an
Access Credential in credentials, or an Access User in the other
two, raises BacnetProtocolError with VALUE_OUT_OF_RANGE; either way
nothing is registered. A read of a list gives the references back in
the forms the keywords take, or [] while it is empty.
BACnetServer.add_access_zone
Section titled “BACnetServer.add_access_zone”def add_access_zone( self, instance: int, name: str, *, entry_points: Optional[list[ObjectIdentifier | tuple[ObjectIdentifier, ObjectIdentifier]]] = None, exit_points: Optional[list[ObjectIdentifier | tuple[ObjectIdentifier, ObjectIdentifier]]] = None, alarm_values: Optional[list[int]] = None,) -> NoneAdd an Access Zone object to the server (before starting).
entry_points and exit_points set Entry_Points and Exit_Points,
the Access Points leading into and out of the zone (read-only over
the network), in the element forms add_access_door takes for
door_members. A pair whose device isn’t a Device object
identifier raises ValueError, and a reference to anything but an
Access Point raises BacnetProtocolError with VALUE_OUT_OF_RANGE;
either way nothing is registered. A read of either list gives the
references back in the forms the keywords take.
alarm_values sets the starting Alarm_Values, the occupancy states
the zone reports with a CHANGE_OF_STATE alarm after Time_Delay, as
BACnetAccessZoneOccupancyState numbers other than NORMAL (1 to 6, or
64 to 65535); peers can write it too. Any other number, NORMAL (0)
included, raises BacnetProtocolError with VALUE_OUT_OF_RANGE and
first_failed_element_number naming it, from 1, and nothing is
registered. Left out, the list starts empty.
BACnetServer.add_credential_data_input
Section titled “BACnetServer.add_credential_data_input”def add_credential_data_input( self, instance: int, name: str, *, supported_formats: Optional[list[tuple[int | tuple[int, int | None, int | None], int]]] = None,) -> NoneAdd a Credential Data Input object to the server (before starting).
supported_formats sets Supported_Formats and
Supported_Format_Classes (read-only over the network) as
(format, format_class) pairs. A format is a
BACnetAuthenticationFactorType number, or a
(format_type, vendor_id, vendor_format) triple whose vendor
members may each be None (absent), as a read gives them; a CUSTOM
format (2) needs both. A format outside the closed production, a CUSTOM
format without its vendor members or a nonzero vendor member on
another format raises BacnetProtocolError with VALUE_OUT_OF_RANGE; a
vendor member above 65535 raises OverflowError. While Out_Of_Service is TRUE a client’s simulated
Present_Value must name one of these formats with its class, or be
the UNDEFINED or ERROR factor with class 0.
BACnetServer.add_alert_enrollment
Section titled “BACnetServer.add_alert_enrollment”def add_alert_enrollment( self, instance: int, name: str, initial_source: ObjectIdentifier,) -> NoneBACnetServer.add_event_enrollment
Section titled “BACnetServer.add_event_enrollment”def add_event_enrollment( self, instance: int, name: str, event_type: EventType = ...,) -> NoneAdd an Event Enrollment (Clause 12.12) to the server (before starting).
Event_Type follows Event_Parameters: it reads NONE while they are
unset (the none alternative) and the written algorithm’s type
after. event_type only applies to the legacy octet-string
Event_Parameters, which name no algorithm: it is the algorithm they
run and the Event_Type served while they are held.
Object_Property_Reference, read-only to peers, reads as one typed
device_object_property_reference mapping. It names Analog Input
4194303’s Present_Value while the enrollment has no reference.
Fault_Parameters reads as the context-tagged none choice while no
fault algorithm is set, and writing that clears it; a null written to
it succeeds and changes nothing.
BACnetServer.add_elevator_group
Section titled “BACnetServer.add_elevator_group”def add_elevator_group( self, instance: int, name: str, machine_room_id: Optional[ObjectIdentifier] = None,) -> NoneAdd an Elevator Group; machine_room_id must be a Positive Integer Value.
BACnetServer.add_escalator
Section titled “BACnetServer.add_escalator”def add_escalator(self, instance: int, name: str) -> NoneBACnetServer.add_lift
Section titled “BACnetServer.add_lift”def add_lift(self, instance: int, name: str, num_floors: int) -> NoneBACnetServer.add_staging
Section titled “BACnetServer.add_staging”def add_staging( self, instance: int, name: str, present_value: float, min_present_value: float, units: EngineeringUnits | int, priority_for_writing: int, stages: list[tuple[float, list[bool], float]], target_references: list[ObjectIdentifier], stage_names: list[str] | None = None,) -> NoneAdd a validated local-target Staging object before start().
BACnetServer.add_averaging
Section titled “BACnetServer.add_averaging”def add_averaging( self, instance: int, name: str, *, window_interval: int | None = None, window_samples: int | None = None,) -> NoneAdd an Averaging object before start().
window_interval sets Window_Interval in seconds (900 when omitted)
and window_samples sets Window_Samples (15 when omitted). Peers
can write both, and each write discards the samples. An interval of 0,
or a sample count of 0 or above 1440, raises VALUE_OUT_OF_RANGE.
Object_Property_Reference reads as one
device_object_property_reference value whose mapping includes all
four keys; while unset its object is Analog Input
4194303’s Present_Value, and writing a reference whose object or
Device is at instance 4194303 unsets it. A null written to it succeeds
and changes nothing.
BACnetServer.add_integer_value
Section titled “BACnetServer.add_integer_value”def add_integer_value(self, instance: int, name: str) -> NoneBACnetServer.add_positive_integer_value
Section titled “BACnetServer.add_positive_integer_value”def add_positive_integer_value(self, instance: int, name: str) -> NoneBACnetServer.add_large_analog_value
Section titled “BACnetServer.add_large_analog_value”def add_large_analog_value(self, instance: int, name: str) -> NoneBACnetServer.add_character_string_value
Section titled “BACnetServer.add_character_string_value”def add_character_string_value(self, instance: int, name: str) -> NoneBACnetServer.add_octet_string_value
Section titled “BACnetServer.add_octet_string_value”def add_octet_string_value(self, instance: int, name: str) -> NoneBACnetServer.add_bit_string_value
Section titled “BACnetServer.add_bit_string_value”def add_bit_string_value(self, instance: int, name: str) -> NoneBACnetServer.add_accumulator
Section titled “BACnetServer.add_accumulator”def add_accumulator( self, instance: int, name: str, units: EngineeringUnits | int = 62, *, scale: float | int | None = None, prescale: Optional[tuple[int, int]] = None,) -> NoneAdd an Accumulator (Clause 12.61) to the server (before starting).
scale sets Scale: a float is a float scale, sent as a
single-precision REAL that multiplies Present_Value, and an int
an integer scale, the power of ten Present_Value is multiplied by.
Left out, Scale is the float scale 1.0. prescale, a
(multiplier, modulo_divide) pair of unsigned32 values, serves the
optional Prescale; left out, the object doesn’t serve it and a read
of it is UNKNOWN_PROPERTY. Both read back as these values (tags
"scale" and "prescale"). A bool or another type raises
TypeError, an integer outside its type OverflowError, a float that
isn’t finite as a REAL or a prescale of another length
ValueError; nothing is registered then.
BACnetServer.add_pulse_converter
Section titled “BACnetServer.add_pulse_converter”def add_pulse_converter( self, instance: int, name: str, units: EngineeringUnits | int = 62,) -> NoneAdd a Pulse Converter (Clause 12.23) to the server (before starting).
Input_Reference reads as application_data holding the
context-tagged reference; while unset it reads as Accumulator
4194303’s Present_Value, and writing a reference to instance 4194303
unsets it. A null written to it succeeds and changes nothing.
While the reference names a missing object, or a property that isn’t
an Unsigned or INTEGER, Reliability reads CONFIGURATION_ERROR and
Status_Flags FAULT; out of service, Reliability is writable for
simulation. The running server counts each increase of the named
property into Count at least once a second, across an Accumulator’s
wrap at Max_Pres_Value.
BACnetServer.add_file
Section titled “BACnetServer.add_file”def add_file( self, instance: int, name: str, file_type: str = "application/octet-stream",) -> NoneBACnetServer.set_file_access_method
Section titled “BACnetServer.set_file_access_method”def set_file_access_method(self, /, instance: int, access_method: str) -> NoneSelect "stream" or "record" on a pending built-in File.
This synchronous operation is valid only before start(). Select the
access method before loading the corresponding payload; changing modes
does not convert stream data to records or vice versa.
BACnetServer.set_file_data
Section titled “BACnetServer.set_file_data”def set_file_data(self, /, instance: int, data: bytes) -> NoneCopy bytes into a pending stream-access built-in File before start().
BACnetServer.get_file_data
Section titled “BACnetServer.get_file_data”def get_file_data(self, /, instance: int) -> bytesReturn a fresh bytes copy from a pending stream File before start().
BACnetServer.set_file_records
Section titled “BACnetServer.set_file_records”def set_file_records(self, /, instance: int, records: list[bytes]) -> NoneCopy records into a pending record-access built-in File before start().
BACnetServer.get_file_records
Section titled “BACnetServer.get_file_records”def get_file_records(self, /, instance: int) -> list[bytes]Return a fresh list and fresh bytes from a pending record File before start().
BACnetServer.set_max_file_size
Section titled “BACnetServer.set_max_file_size”def set_max_file_size(self, /, instance: int, max_octets: int) -> intSet and return the effective octet growth cap before start().
The built-in File clamp is authoritative. This does not truncate preloaded content.
BACnetServer.set_max_record_count
Section titled “BACnetServer.set_max_record_count”def set_max_record_count(self, /, instance: int, max_records: int) -> intSet and return the effective record growth cap before start().
The built-in File clamp is authoritative. This does not truncate preloaded records.
BACnetServer.add_bip_network_port
Section titled “BACnetServer.add_bip_network_port”def add_bip_network_port( self, instance: int, name: str, *, ip_address: str = "0.0.0.0", udp_port: int = 47808, network_number: int = 0, apdu_length: int = 1476, subnet_mask: str = "0.0.0.0", default_gateway: str = "0.0.0.0", dns_servers: Optional[List[str]] = None,) -> NoneAdd a configured, unbound IPV4 (B/IP) Network Port snapshot.
Every configuration row is read-only and nothing binds a socket.
Raises ValueError for an address that isn’t IPv4 (ip_address,
subnet_mask, default_gateway or a DNS server);
BacnetProtocolError for an instance outside 1..255, a
network_number of 65535, an apdu_length under 50 or an empty
dns_servers; OverflowError for a number too large for its type;
RuntimeError once the server has started.
BACnetServer.add_bip6_network_port
Section titled “BACnetServer.add_bip6_network_port”def add_bip6_network_port( self, instance: int, name: str, *, ip_address: str = "::", udp_port: int = 47808, network_number: int = 0, apdu_length: int = 1476, prefix_length: int = 64, default_gateway: str = "::", dns_servers: Optional[List[str]] = None, multicast_address: str = "ff05::bac0", vmac: Optional[bytes] = None,) -> NoneAdd a configured, unbound IPV6 (B/IPv6) Network Port snapshot.
The B/IPv6 counterpart of add_bip_network_port: every row is
read-only and nothing binds a socket. vmac is the 3-octet
MAC_Address until a registered transport="ipv6" server publishes
the VMAC it uses; multicast_address is the broadcast group.
Raises ValueError for an address that isn’t IPv6 or a vmac that
isn’t 3 octets; BacnetProtocolError for an instance outside 1..255,
a network_number of 65535, an apdu_length under 50, an empty
dns_servers, a prefix_length outside 1..128, a
multicast_address that isn’t multicast or an IPv4-mapped
ip_address; OverflowError for a number too large for its type;
RuntimeError once the server has started.
BACnetServer.start
Section titled “BACnetServer.start”def start(self) -> Awaitable[None]Start the server and begin accepting BACnet requests.
BACnetServer.stop
Section titled “BACnetServer.stop”def stop(self) -> Awaitable[None]Join admitted work and release the owned transport.
Cancelling the returned Future retains shutdown ownership. Call stop() again to join it; a cleanup error also retains the owner for retry. Local mutation is rejected once shutdown starts.
A Notification Forwarder, Notification Class or Audit Log write staged for a request that stop() cut short is dropped, and stop() waits, with no limit, until every save those objects queued has run, so storage holds what they serve. While storage holds it up, a warning naming the objects still saving is logged after 5 s and every 30 s after that.
BACnetServer.local_address
Section titled “BACnetServer.local_address”def local_address(self) -> Awaitable[str]Get the retained server instance’s last bound address snapshot.
B/IP gives "ip:port". B/IPv6 gives the VMAC peers address the
server by, "bip6:0x0004D2" for device_instance=1234: an ipv6
server’s VMAC is its device instance (Clauses U.1.3, H.7.2), and
startup fails when another node on the link already uses it. MS/TP
gives the station, SC the colon-hex VMAC.
Available during interrupted shutdown; successful stop clears the instance and subsequent address queries raise RuntimeError.
BACnetServer.foreign_registration
Section titled “BACnetServer.foreign_registration”def foreign_registration(self) -> Awaitable[ForeignRegistrationStatus]How the foreign-device registration is going (#938), as for
BACnetClient. RuntimeError before start and after stop.
BACnetServer.read_property
Section titled “BACnetServer.read_property”def read_property( self, object_id: ObjectIdentifier, property_id: PropertyIdentifier, array_index: Optional[int] = None,) -> Awaitable[PropertyValue]Read a property from a local object through the server’s ReadProperty evaluator, the one network reads use.
The result equals what a network read_property of the same
property returns: a Group’s Present_Value is rebuilt from its
members, Device instance 4194303 names this server’s Device, and the
Device’s COV subscription lists are live. Its Device_Address_Binding
is a list with one "address_binding" element per device binding
the server holds (each add_device_binding, and each device whose
I-Am it heard in the last ten minutes): a mapping of
device_identifier, network_number (0 on this network) and
mac_address. An unknown object or
property raises BacnetProtocolError with the network error, and a
Group whose member rows exceed rpm_max_result_elements raises
BacnetAbortError (reason 9, OUT_OF_RESOURCES).
BACnetServer.write_property_local
Section titled “BACnetServer.write_property_local”def write_property_local( self, object_id: ObjectIdentifier, property_id: PropertyIdentifier, value: PropertyValue, priority: Optional[int] = None, array_index: Optional[int] = None, *, source_object: Optional[ObjectIdentifier],) -> Awaitable[None]Write locally with an explicit source: None selects the server Device.
A source object must exist in the database. Tracked commands require a
concrete server Device; corrections retain the original Device owner.
The value is encoded and decoded as a network WriteProperty’s would
be, so any value a network write takes works, including whatever
read_property returns, and array-index errors match the network’s.
BACnetServer.lighting_color
Section titled “BACnetServer.lighting_color”def lighting_color( self, object_id: ObjectIdentifier,) -> Awaitable[Optional[tuple[ObjectIdentifier, tuple[float, float] | int]]]The colour the lighting output object_id shows now: the
Tracking_Value of the colour object its Color_Reference names, or its
Override_Color_Reference while Color_Override is TRUE, so a colour
fade shows as it runs.
Returns (source, colour), the colour object’s identifier and an
(x, y) pair for a Color object or an int in kelvin for a
Color Temperature object, or None when the output has no
Color_Reference, the reference in use names no object (instance
4194303), the server holds no colour object by that identifier, or
that object reads In_Progress NOT_CONTROLLED (nothing has driven it).
Raises RuntimeError before start().
BACnetServer.set_present_value_local
Section titled “BACnetServer.set_present_value_local”def set_present_value_local( self, object_id: ObjectIdentifier, value: PropertyValue,) -> Awaitable[None]Update Present_Value through the narrow, non-generic application Input authority.
Accepted values are a finite REAL for Analog Input and for a Loop’s
control output, logical Enumerated 0/1 (INACTIVE/ACTIVE) for Binary Input,
and Unsigned 1..=Number_Of_States for Multi-state Input. A noncommandable
Analog, Binary or Multi-state Value takes the same datatype as its Input
counterpart; a commandable one raises OPTIONAL_FUNCTIONALITY_NOT_SUPPORTED
(use write_property_local with a priority). Binary values are
BACnet logical values after Polarity, not raw hardware/interface levels.
An object with Out_Of_Service set rejects this update to preserve
network simulation ownership. A Life Safety Point or Zone takes an
Enumerated BACnetLifeSafetyState (standard, or 256..=65535) whether or
not Out_Of_Service is set, since clients never write its Present_Value;
Tracking_Value, Silenced and Operation_Expected stay as they are. Other
object types are not writable through this method.
BACnetServer.report_access_event_local
Section titled “BACnetServer.report_access_event_local”def report_access_event_local( self, object_id: ObjectIdentifier, event: int, tag: int, *, time: Optional[BACnetTimeStamp] = None, credential: Optional[ObjectIdentifier | tuple[ObjectIdentifier, ObjectIdentifier]] = None, authentication_factor: Optional[tuple[int, int, bytes]] = None,) -> Awaitable[None]Report an access event at an Access Point the server holds.
Access_Event (event, a BACnetAccessEvent number),
Access_Event_Tag (tag, the access transaction), Access_Event_Time
(time, the Device clock’s when omitted), Access_Event_Credential
(credential, the no-credential reference when omitted) and
Access_Event_Authentication_Factor (authentication_factor as
(format_type, format_class, value), the UNDEFINED factor when
omitted) change together. A credential that isn’t an Access
Credential, a factor format outside the closed production, or an
event that is neither a named BACnetAccessEvent nor a proprietary one
from 512 to 65535, raises VALUE_OUT_OF_RANGE. While the point is out
of service, or its Reliability isn’t NO_FAULT_DETECTED, the event is
refused with WRITE_ACCESS_DENIED and nothing changes. An unknown
object raises UNKNOWN_OBJECT and any object other than an Access
Point OPTIONAL_FUNCTIONALITY_NOT_SUPPORTED. A new time sends the
point’s COV report, and a time the point stamps itself always moves,
so events of one transaction each send one.
BACnetServer.report_credential_read_local
Section titled “BACnetServer.report_credential_read_local”def report_credential_read_local( self, object_id: ObjectIdentifier, factor: tuple[int, int, bytes], *, update_time: Optional[BACnetTimeStamp] = None,) -> Awaitable[None]Report a factor a Credential Data Input’s reader has read.
Present_Value takes factor, (format_type, format_class, value), and Update_Time update_time, the Device clock’s when
omitted, together. The factor must name one of the reader’s
supported_formats with its class, or be the UNDEFINED (0) or
ERROR (1) factor with class 0, else VALUE_OUT_OF_RANGE. While the
reader is out of service the read is kept aside, in place of the
reader’s earlier one: a client’s simulated values stay served, no
COV report goes out, and the return to service serves the latest
read. An unknown object raises UNKNOWN_OBJECT and any object other
than a Credential Data Input OPTIONAL_FUNCTIONALITY_NOT_SUPPORTED. A
new Update_Time sends the reader’s COV report.
BACnetServer.report_door_state_local
Section titled “BACnetServer.report_door_state_local”def report_door_state_local( self, object_id: ObjectIdentifier, *, door_status: Optional[int] = None, lock_status: Optional[int] = None, door_alarm_state: Optional[int] = None,) -> Awaitable[None]Report an Access Door’s hardware state.
Whichever of Door_Status, Lock_Status and Door_Alarm_State is given, as BACnetDoorStatus, BACnetLockStatus and BACnetDoorAlarmState numbers, changes together; the others keep their values. A number outside its production, or an alarm state the door’s Alarm_Values, Fault_Values and Masked_Alarm_Values don’t admit, raises VALUE_OUT_OF_RANGE and nothing changes. While the door is out of service the values are kept aside, in place of the device’s earlier ones: a client’s simulated values stay served, no COV report or event follows, and the return to service serves the latest values reported. An unknown object raises UNKNOWN_OBJECT and any object other than an Access Door OPTIONAL_FUNCTIONALITY_NOT_SUPPORTED. In service a new Door_Alarm_State sends the door’s COV report, and the door’s event algorithm sees it at once.
BACnetServer.set_tracking_value_local
Section titled “BACnetServer.set_tracking_value_local”def set_tracking_value_local( self, object_id: ObjectIdentifier, value: PropertyValue,) -> Awaitable[None]Set a Life Safety Point’s or Zone’s Tracking_Value, the live state the application derived.
The value is an Enumerated BACnetLifeSafetyState, standard or from 256..=65535: another number raises VALUE_OUT_OF_RANGE and another datatype INVALID_DATA_TYPE. An unknown object raises UNKNOWN_OBJECT and any object other than a Life Safety Point or Zone OPTIONAL_FUNCTIONALITY_NOT_SUPPORTED. Present_Value, Silenced and Operation_Expected stay as they are, so an application that latches Present_Value until reset keeps reporting the live state here. While Out_Of_Service is set the value is held for the return to service and a client’s simulated Tracking_Value stays in place. In service a SubscribeCOVProperty on Tracking_Value is notified of the change; a SubscribeCOV report doesn’t carry it.
BACnetServer.report_device_reset_local
Section titled “BACnetServer.report_device_reset_local”def report_device_reset_local(self) -> Awaitable[None]Record a reset the application makes for its own reasons: a DEVICE_RESET Audit record from this device, with no invoke ID (#1564). A peer’s accepted restart is recorded already. RuntimeError when the server is not running.
BACnetServer.purge_audit_log
Section titled “BACnetServer.purge_audit_log”def purge_audit_log(self, object_id: ObjectIdentifier) -> Awaitable[None]Purge an Audit Log: clear its records and append a BUFFER_PURGED status record.
No peer can purge an Audit Log, since its Record_Count is read-only, so this is the application’s route. The record is appended whether or not logging is enabled, and also carries LOG_DISABLED while logging is off; Total_Record_Count keeps counting. The purge reaches storage before the log serves it. An unknown object raises UNKNOWN_OBJECT, any object other than an Audit Log OPTIONAL_FUNCTIONALITY_NOT_SUPPORTED, and a missing clock or a failed commit DEVICE / OPERATIONAL_PROBLEM, leaving the log as it was. A server that is not running raises RuntimeError.
BACnetServer.set_controlled_variable_value_local
Section titled “BACnetServer.set_controlled_variable_value_local”def set_controlled_variable_value_local( self, object_id: ObjectIdentifier, value: PropertyValue,) -> Awaitable[None]Feed a Loop’s measured Controlled_Variable_Value while the application runs its algorithm.
The value must be a finite REAL: another datatype raises INVALID_DATA_TYPE and NaN or an infinity VALUE_OUT_OF_RANGE. An unknown object raises UNKNOWN_OBJECT and any object other than a Loop OPTIONAL_FUNCTIONALITY_NOT_SUPPORTED. Unlike Present_Value, the update is accepted while Out_Of_Service is set. A SubscribeCOVProperty on the property is notified of the change; a SubscribeCOV on the Loop is not, and its next notification carries the new value. The property stays read-only over the network.
BACnetServer.add_averaging_sample_local
Section titled “BACnetServer.add_averaging_sample_local”def add_averaging_sample_local( self, object_id: ObjectIdentifier, value: PropertyValue | None,) -> Awaitable[None]Record one sample for an Averaging object, taken by the application.
The server samples an object holding an Object_Property_Reference
itself, every Window_Interval / Window_Samples seconds. For an object
without one (its reference reads as the unset form, instance
4194303), the application samples about that often and passes each
result here; on one the server samples, a call is one more attempt and
doesn’t move the server’s schedule. The value is a BOOLEAN (FALSE and
TRUE count as 0 and 1), Signed, Unsigned, Enumerated or finite REAL;
None records an attempt that produced no value, which counts
toward Attempted_Samples but not Valid_Samples. Another datatype,
Double included, raises INVALID_DATA_TYPE and NaN or an infinity
VALUE_OUT_OF_RANGE, and a refused sample isn’t counted. An unknown
object raises UNKNOWN_OBJECT and any object other than an Averaging
object OPTIONAL_FUNCTIONALITY_NOT_SUPPORTED. Each call fills the next
slot of the Window_Samples window, dropping the oldest once it is
full, and Minimum_Value, Maximum_Value, Average_Value and the sample
counts change together; with no valid sample in the window they read
positive infinity, negative infinity and NaN. A SubscribeCOVProperty
on one of them is notified when it changes (by the subscription’s COV
increment, if it gave one); SubscribeCOV on an Averaging object is
refused.
BACnetServer.comm_state
Section titled “BACnetServer.comm_state”def comm_state(self) -> Awaitable[EnableDisable]Get the DeviceCommunicationControl state.
Returns EnableDisable.ENABLE or EnableDisable.DISABLE_INITIATION;
the server refuses the deprecated DISABLE, so it never reports it.
Raises RuntimeError before start and after stop.
BACnetServer.cov_counters
Section titled “BACnetServer.cov_counters”def cov_counters(self) -> Awaitable[CovCounters]Sample COV subscription and notification telemetry; zero at each start.
Every field of the Rust CovCounters under the same name. subscriptions_active is a gauge; the rest are running totals. timed_changes_dropped counts timestamped COV-multiple changes lost for good, in whole or in part, the running signal for a subscriber whose maximum APDU can’t hold one timestamped value. untimed_references_oversized counts each report that left out an untimestamped reference too large for one notification. Raises RuntimeError before start and after stop.
BACnetServer.event_notification_counters
Section titled “BACnetServer.event_notification_counters”def event_notification_counters(self) -> Awaitable[EventNotificationCounters]Sample the totals of event notifications the server did not deliver.
Every field of the Rust EventNotificationCounters under the same name, zero at each start. The recipient-list fields count transitions whose Notification Class lookup failed closed: the class is missing, its Recipient_List can’t be read or decoded, or it serves more than 32 destinations. An empty or fully filtered list, DCC and Event_Enable are not counted. The next three count matched destinations skipped while their route was resolved: a Device recipient with no current binding, a recipient that can’t be routed as configured, and a confirmed recipient at a group address (a broadcast or a multicast one). The confirmed fields count notifications to one recipient that found no free invoke ID, were answered with an Error, Reject or Abort, or drew no acknowledgment after the last retry. unconfirmed_send_failed counts unconfirmed notifications the transport refused to send, once per destination. apdu_too_large counts notifications not sent to one destination because they exceed the local APDU size, received_not_forwarded counts received event notifications no Notification Forwarder took, and forwarding_cap_dropped counts destinations dropped because one notification already had 64 across the forwarders. Fields are sampled independently. Raises RuntimeError before start and after stop.
BACnetServer.forwarder_save_counters
Section titled “BACnetServer.forwarder_save_counters”def forwarder_save_counters(self) -> Awaitable[dict[int, ForwarderSaveCounters]]Sample each Notification Forwarder’s save counters, keyed by instance.
The totals belong to the objects: they count from registration, and
a forwarder without storage_path stays at zero. Raises
RuntimeError before start and after stop.
BACnetServer.dcc_outcome_counters
Section titled “BACnetServer.dcc_outcome_counters”def dcc_outcome_counters(self) -> Awaitable[DccOutcomeCounters]Sample completed admitted DCC handlers; zero on each new server lifetime.
Accepted means state/timer commit, not response delivery. Independent samples are not an atomic aggregate. Excludes incomplete cancellation, duplicates, pre-handler rejection and timer expiry. No trace bridge or subscriber installation. Raises RuntimeError before start/after stop.
BACnetServer.sc_npdu_drop_counts
Section titled “BACnetServer.sc_npdu_drop_counts”def sc_npdu_drop_counts(self) -> Awaitable[ScNpduDropCounts]Copy SC ingress counters; requires a started SC owner.
Available while disconnected. Each call returns an independent dictionary; a new transport starts fresh counters. No network I/O is performed.
BACnetServer.request_admission_counters
Section titled “BACnetServer.request_admission_counters”def request_admission_counters(self) -> Awaitable[RequestAdmissionCounters]Sample counters; RuntimeError before start and after stop.
Admitted totals count registered work, not successful response sends.
BACnet/SC Hub for relaying messages between SC nodes.
Usage:
hub = ScHub("0.0.0.0:47809", "cert.pem", "key.pem", b"\x02\x00\x00\x00\x00\x01", ca_cert="ca.pem", device_uuid=provisioned_hub_uuid)await hub.start()print(await hub.url())print(await hub.status())print(await hub.shutdown_gracefully()) # "graceful" or "forced"The hub also works as an async context manager (starts on entry, forcefully stops on exit):
async with ScHub(..., device_uuid=provisioned_hub_uuid) as hub: ...ca_cert must name trusted issuer CA PEM certificates for mutual TLS.
Omitted, None, or empty values raise ValueError at construction. The None
default retains the existing positional layout only; there is no insecure
mode. Invalid/unreadable credentials raise BacnetError from start(), before
binding. Connections require TLS 1.3 and a valid trusted client certificate.
device_uuid is required, keyword-only and copied from bytes/bytearray into
owned storage. Missing/None, wrong length or all-zero UUID raises ValueError
before file I/O. The caller provisions this hosting device identity before
deployment and durably reuses the same bytes for its entire lifetime, including
stop/start and fresh objects. No generation/storage or UUID-bit validation is
provided. The hosting port’s vmac must be six bytes (RuntimeError for wrong
length), neither all zero nor all ff (ValueError). CA presence remains first,
then VMAC validation, then UUID. No certificate-to-identity binding is implied.
Admission and timeout policy is constructor-validated, before bind:
max_clients/max_handshakes caps (zero/overflowing raise ValueError,
negative values raise OverflowError); admission_policy is the static
string "allow_all" (default), "deny_all" or
"deny_uuid_replacement" (unknown strings raise
ValueError, non-strings including callables raise TypeError — no Python
callback can run under the native registry lock). Replacement refusal is a
local security policy before protocol acceptance: it preserves an incumbent
when the same claimed UUID requests its current or another VMAC. Default
mode retains Annex AB replacement; a different-UUID VMAC collision keeps its
standard NAK. UUID equality is not certificate identity proof. Graceful per-peer ack /
close / overall millisecond bounds and handshake TLS / WebSocket-upgrade /
Connect-Request millisecond bounds (out-of-range values raise ValueError).
Optional Hub probes use probe_scan_interval_ms / probe_idle_age_ms /
probe_ack_age_ms / probe_send_budget_ms (defaults 30000/60000/5000/5000).
Strictly exceeded ages are checked at scans; ACK age starts at reservation,
not completed send, and is not a hard closure deadline. Delayed ticks are
skipped. Only matching valid ACKs refresh activity. Node keepalive is separate.
A connector need not answer probes (#2141): an unanswered probe retires it
only after probe_liveness_bound_ms (default 360000, at most 86400000)
passes with nothing received from it since the probe, and is not repeated
until it sends something. Its own Heartbeat-Request keeps it registered; a
dead connector lingers that much longer.
relay_send_budget_ms bounds each NPDU/opaque unicast, concurrent broadcast
recipient and forwarded BVLC-Result acquisition+send attempt (default 5000),
without timeout-driven retirement, retry or fabricated Result. Probe, control,
cleanup and graceful shutdown stay separate. Unicast counters keep their scope.
These values must be positive whole milliseconds <=2**63-1 and fit the native
monotonic clock. Broadcast sender/global burst/per-second settings use native
token buckets: bounds 1..=(2**64-1)//1_000_000_000, silent drops, existing counters.
All are constructor-validated before I/O. Negative/over-u64 integers raise
OverflowError, nonintegers TypeError, other invalid bounds ValueError.
certificate_bindings=None retains CA-valid admission. A nonempty group
sequence enables mapped-only UUID/VMAC reservations, including offline nodes;
existing admission_policy can further deny. Shared native validation rejects
overlapping ownership and local Hub VMAC conflicts before PEM I/O/bind.
Inputs are copied; status/repr/errors do not expose certificate contents.
This is installation policy, not end-to-end relayed authentication.
stop() is forceful and idempotent; shutdown_gracefully() runs the
Disconnect/Ack/close exchange and consumes the hub; dropping the hub
without awaiting close only seals admission and cannot guarantee cleanup.
ScHub.init
Section titled “ScHub.init”def __init__( self, listen: str, cert: str, key: str, vmac: bytes, ca_cert: Optional[str] = None, *, device_uuid: Optional[Union[bytes, bytearray]] = None, max_clients: int = 256, max_handshakes: int = 256, admission_policy: Literal["allow_all", "deny_all", "deny_uuid_replacement"] = "allow_all", graceful_disconnect_ack_ms: int = 5000, graceful_ws_close_ms: int = 5000, graceful_overall_ms: int = 15000, handshake_tls_ms: int = 10000, handshake_websocket_upgrade_ms: int = 10000, handshake_connect_request_ms: int = 10000, probe_scan_interval_ms: int = 30000, probe_idle_age_ms: int = 60000, probe_ack_age_ms: int = 5000, probe_send_budget_ms: int = 5000, probe_liveness_bound_ms: int = 360000, broadcast_sender_burst: int = 1024, broadcast_sender_per_second: int = 128, broadcast_global_burst: int = 4096, broadcast_global_per_second: int = 512, relay_send_budget_ms: int = 5000, certificate_bindings: Sequence[ScHubCertificateBinding] | None = None,) -> NoneScHub.start
Section titled “ScHub.start”def start(self) -> Awaitable[None]Start the SC hub.
ScHub.stop
Section titled “ScHub.stop”def stop(self) -> Awaitable[None]Stop the SC hub (forceful, idempotent).
ScHub.shutdown_gracefully
Section titled “ScHub.shutdown_gracefully”def shutdown_gracefully(self) -> Awaitable[Literal["graceful", "forced"]]Graceful shutdown; consumes the hub (RuntimeError if not started).
ScHub.status
Section titled “ScHub.status”def status(self) -> Awaitable[ScHubStatus]Bounded redacted snapshot (RuntimeError before start/after stop).
ScHub.aenter
Section titled “ScHub.aenter”def __aenter__(self) -> Awaitable[ScHub]ScHub.aexit
Section titled “ScHub.aexit”def __aexit__( self, _exc_type: Any = None, _exc_val: Any = None, _exc_tb: Any = None,) -> Awaitable[None]ScHub.address
Section titled “ScHub.address”def address(self) -> Awaitable[Optional[str]]Get the address the hub is listening on (None before start).
ScHub.url
Section titled “ScHub.url”def url(self) -> Awaitable[Optional[str]]Get the WebSocket URL of the hub (None before start).
ReinitializeRequest
Section titled “ReinitializeRequest”A ReinitializeDevice request handed to on_reinitialize and
after_reinitialize (#1566). The addresses are what the request
claims, not an authenticated identity. Not copyable or picklable.
Properties:
state: ReinitializedState: The requested state.source_mac: bytes: The immediate link source: the requester, or the last router.source_network: Optional[int]: The originating network of a routed request, else None.source_address: Optional[bytes]: The originating MAC of a routed request, else None.invoke_id: int
MutationContext
Section titled “MutationContext”One mutation a mutation_policy callable is asked to allow
(#1966): a frozen, redacted copy of the request. It holds the target’s
coordinates, never written values or file data. The addresses are what
the request claims, not an authenticated identity. Its repr shows the
service and invoke ID only. Not copyable or picklable.
Properties:
service: Literal['write_property', 'write_property_multiple', 'create_object', 'delete_object', 'add_list_element', 'remove_list_element', 'atomic_write_file', 'subscribe_cov', 'subscribe_cov_property', 'subscribe_cov_property_multiple', 'write_group']: The service. WritePropertyMultiple asks once per element and WriteGroup once per Channel.object_identifier: Optional[ObjectIdentifier]: The target object (the Channel for WriteGroup, the File for AtomicWriteFile); None for a CreateObject that names only a type and for SubscribeCOVPropertyMultiple.object_type: Optional[ObjectType]: The target’s type, also for a CreateObject by type; None for SubscribeCOVPropertyMultiple.property_identifier: Optional[PropertyIdentifier]: The property written, listed or subscribed to, else None.array_index: Optional[int]priority: Optional[int]: The write priority of a WriteProperty, a WritePropertyMultiple element or a WriteGroup, when there is one.source_mac: bytes: The immediate link source: the requester, or the last router.source_network: Optional[int]: The originating network a routed request claims, else None.source_address: Optional[bytes]: The originating MAC a routed request claims, else None.provenance: Literal["unverified", "relayed_origin", "hub_channel", "direct_peer"]: How the request arrived:unverifiedfor B/IP, B/IPv6, MS/TP and Ethernet,relayed_originthrough a BACnet/SC hub.principal: Optional[bytes]: The SHA-256 of the originating peer’s verified leaf certificate, for a direct BACnet/SC connection without a routed source. A Python server has no direct SC listener, so this is None.forwarding_peer_principal: Optional[bytes]: The SHA-256 of the forwarding direct SC peer’s leaf certificate, a router included; None, likeprincipal, for a Python server.certificate: None: Always None: a Python server has no direct BACnet/SC listener, and hub-relayed, routed and non-SC requests carry no certificate.forwarding_peer_certificate: None: Always None, for the reasoncertificategives.invoke_id: Optional[int]: A confirmed request’s invoke ID; None for WriteGroup.
ScHubCertificateBinding
Section titled “ScHubCertificateBinding”Frozen installation group; exact leaf DER SHA-256, with redacted repr.
Inputs are copied. UUID must be nonzero; VMAC and digest lists must be nonempty and distinct; reserved VMACs are invalid. Raises ValueError.
Properties:
uuid: bytesallowed_vmacs: tuple[bytes, ...]leaf_sha256: tuple[bytes, ...]
ScHubCertificateBinding.init
Section titled “ScHubCertificateBinding.init”def __init__( self, *, uuid: bytes, allowed_vmacs: Sequence[bytes], leaf_sha256: Sequence[bytes],) -> NoneCovCounters
Section titled “CovCounters”class CovCounters(TypedDict)
COV telemetry, zero at each start; fields are sampled one by one, not atomically.
Keys:
subscriptions_active: intsubscriptions_created: intsubscriptions_rejected_quota: intsubscriptions_rejected_capacity: intsubscriptions_rejected_indefinite: intsubscriptions_cancelled: intsubscriptions_purged: intnotifications_sent: intnotifications_confirmed: intnotifications_unconfirmed: intnotification_bytes_sent: intnotifications_throttled_fanout: intnotifications_throttled_peer: inttimed_changes_dropped: intuntimed_references_oversized: int
CovPolicy
Section titled “CovPolicy”class CovPolicy(TypedDict, total=False)
BACnetServer(cov_policy=…) COV limits, checked at construction; omitted keys keep their defaults.
Keys:
max_subscriptions_global: intmax_subscriptions_per_peer: intreserved_capacity: intreserved_peers: list[bytes]reserved_recipients: list[tuple[int | None, bytes]]allow_indefinite_subscriptions: boolmax_indefinite_per_peer: intmax_notifications_per_event: intmax_notification_bytes_per_event: intmax_confirmed_in_flight_per_peer: int
TimeSyncPolicy
Section titled “TimeSyncPolicy”class TimeSyncPolicy(TypedDict, total=False)
BACnetServer(time_sync_policy=…) inbound clock limits, checked at construction; omitted keys keep their defaults.
Keys:
enabled: boolsource_restriction: list[tuple[int | None, bytes]] | Nonemax_step_ms: int | Noneper_source_rate: tuple[float, int] | Noneglobal_rate: tuple[float, int] | Nonecoalesce_window_ms: intglobal_coalesce_window_ms: intmax_sources: int
ForwarderSaveCounters
Section titled “ForwarderSaveCounters”class ForwarderSaveCounters(TypedDict)
One Notification Forwarder’s Subscribed_Recipients save totals, saturating at 2**64-1.
Keys:
failed_saves: int
EventNotificationCounters
Section titled “EventNotificationCounters”class EventNotificationCounters(TypedDict)
Undelivered event notifications, zero at each start; independent u64 totals, saturating at 2**64-1.
Keys:
notification_class_missing: intrecipient_list_unavailable: intrecipient_list_invalid: intrecipient_list_too_long: intdevice_recipient_unbound: intrecipient_unroutable: intconfirmed_broadcast_recipient: intconfirmed_no_invoke_id: intconfirmed_rejected: intconfirmed_unanswered: intunconfirmed_send_failed: intapdu_too_large: intreceived_not_forwarded: intforwarding_cap_dropped: intreceived_not_logged: int
DccOutcomeCounters
Section titled “DccOutcomeCounters”class DccOutcomeCounters(TypedDict)
Independent u64 lifetime totals, saturating at 2**64-1; not an audit log.
Keys:
accepted_total: intpolicy_denied_total: intpassword_failure_total: intdeprecated_denied_total: intmalformed_total: int
ScNpduDropCounts
Section titled “ScNpduDropCounts”class ScNpduDropCounts(TypedDict)
Owned, queue-wide lifetime counters for one started SC transport.
Keys:
control_rate_drops: intfairness_drops: intfull_drops: intclosed_drops: int
RequestAdmissionCounters
Section titled “RequestAdmissionCounters”class RequestAdmissionCounters(TypedDict)
Independent counter samples, not a transactionally atomic aggregate.
Keys:
recovery_active: intrecovery_admitted_total: intrecovery_overloaded_total: intconfirmed_active: intconfirmed_admitted_total: intconfirmed_overloaded_total: intconfirmed_global_overloaded_total: intconfirmed_peer_overloaded_total: intconfirmed_shutdown_rejected_total: intunconfirmed_active: intunconfirmed_admitted_total: intunconfirmed_overloaded_total: intunconfirmed_global_overloaded_total: intunconfirmed_peer_overloaded_total: intunconfirmed_shutdown_rejected_total: intabort_active: intabort_admitted_total: intconfirmed_fallback_dropped_total: intabort_shutdown_rejected_total: int
ScHubOutcomeCounts
Section titled “ScHubOutcomeCounts”class ScHubOutcomeCounts(TypedDict)
Per-start saturating outcomes; selected refusals are not delivered NAK counts.
Keys:
uuid_replacements: intvmac_collision_rejections: intregistered_capacity_rejections: inttotal_active_accept_drops: inthandshake_accept_drops: inttls_timeouts: intwebsocket_timeouts: intconnect_timeouts: intunicast_no_target: intunicast_target_limit: intunicast_send_timeout: intunicast_send_error: intheartbeat_retirements: int
ScHubStatus
Section titled “ScHubStatus”class ScHubStatus(TypedDict)
Bounded hub snapshot: counts and kind labels only (no keys/VMAC maps).
Keys:
listening: boolmax_clients: intmax_handshakes: intclient_count: inthandshake_count: intadmin_denied: intbroadcast_sender_exhausted: intbroadcast_global_exhausted: intoutcomes: ScHubOutcomeCounts
ReinitializeHandler
Section titled “ReinitializeHandler”ReinitializeHandler = Callable[ [ReinitializeRequest], Union[None, bool, tuple[ErrorClass, ErrorCode]]]AfterReinitialize
Section titled “AfterReinitialize”AfterReinitialize = Callable[[ReinitializeRequest], Optional[Awaitable[None]]]MutationHandler
Section titled “MutationHandler”MutationHandler = Callable[[MutationContext], bool]Release v0.15.0 ·Build and integrate. Pre-1.0 APIs; partial conformance.Support & limitations