Embed the Rust client

The v0.11.0 workspace declares a minimum Rust version of 1.93. Use a compatible stable toolchain; the website’s Node tooling is unrelated to the Rust library minimum.

Terminal window
cargo new first-read
cd first-read

Add these entries to the generated Cargo.toml dependency section:

[dependencies]
bacnet-client = "=0.11.0"
bacnet-types = "=0.11.0"
bacnet-encoding = "=0.11.0"
tokio = { version = "1", features = ["macros", "rt-multi-thread"] }

The exact BACnet versions make the tutorial’s release scope explicit. Your application can adopt its own version policy after migration and compatibility review.

Replace src/main.rs with the following. It expects an explicit remote IPv4 address and UDP port; analog input 1 must exist on that device.

use std::net::{Ipv4Addr, SocketAddrV4};
use bacnet_client::client::BACnetClient;
use bacnet_encoding::primitives::decode_application_value;
use bacnet_types::enums::{ObjectType, PropertyIdentifier};
use bacnet_types::primitives::ObjectIdentifier;
#[tokio::main]
async fn main() -> Result<(), Box<dyn std::error::Error>> {
let target: SocketAddrV4 = std::env::args()
.nth(1)
.ok_or("usage: first-read <IPv4:port>")?
.parse()?;
let client = BACnetClient::bip_builder()
.interface(Ipv4Addr::UNSPECIFIED)
.port(0)
.broadcast_address(Ipv4Addr::BROADCAST)
.build()
.await?;
let [a, b, c, d] = target.ip().octets();
let [hi, lo] = target.port().to_be_bytes();
let address = [a, b, c, d, hi, lo];
let object = ObjectIdentifier::new(ObjectType::ANALOG_INPUT, 1)?;
let ack = client
.read_property(&address, object, PropertyIdentifier::PRESENT_VALUE, None)
.await?;
let (value, _) = decode_application_value(&ack.property_value, 0)?;
println!("{value:?}");
Ok(())
}
Terminal window
cargo run -- 192.168.1.100:47808

This example uses an ephemeral local port and directed traffic. It is not a broadcast-discovery or server configuration example. The displayed value is typed BACnet data; consult the object’s name and units before interpreting it.

The Rust client returns encoded property data that this example decodes. Do not silently treat every property as a float, and do not assume that every complex BACnet value is interchangeable with a primitive value.

Transport features live on the crates that implement or expose them. Enabling a feature in one crate does not prove that a particular executable exposes it. Consult the manifests and transport guide.

Use the server and object crates for a hosted device model, and the transport/network layers where your application needs them. A library building successfully does not establish a combined client/server endpoint profile or full conformance. Start from the current examples and API documentation rather than copying an older README dependency block.

These instructions target v0.11.0. Source review is not a claim of hardware qualification.

Workspace versions and minimum · Rust API guide · Existing client example.

Release v0.11.0 ·Current development. Follow the scope named on each page. Pre-1.0 APIs; partial conformance.Support & limitations