Commission an MS/TP lab

MS/TP is a token-passing serial transport. Fast protocol code is useful, but it does not by itself prove that a host, driver, and RS-485 adapter meet the required on-wire timing.

Use an isolated, authorized lab trunk first. The included Python example is a token-participating master, not a passive serial sniffer.

The Python package supports transport="mstp" on BACnetClient and BACnetServer, and MstpEndpoint for one device that both requests and responds; every release wheel includes it. Rust has the serial transport itself. The bacnet CLI joins a trunk as a master station with --mstp PORT and --mstp-mac (in the Linux release executables, or a source build with the serial feature), and bacnet mstp-ports lists the ports; the CLI reference has the flags, the Linux dialout group and the FTDI latency timer.

Treat Linux as the initial documentation/qualification lane. Serial path examples for macOS or Windows are not evidence that those platform/adapter combinations are qualified.

Use the release package, or a source build with the serial feature, and an adapter whose transmit-direction behavior is suitable for this deployment. The example asks for automatic transmit-direction control; adapter and driver behavior vary.

Choose a unique local master MAC in 0..=127, a suitable device instance, and a baud rate matching the existing trunk. Coordinate Max_Master with the actual station address plan. Check wiring, polarity, common/reference arrangements, isolation, termination, and biasing against the equipment and adapter documentation; this page is not an electrical wiring specification.

MS/TP qualification spans host scheduling, adapter behavior, and the RS-485 wire.
From application to RS-485 wire

MS/TP qualification spans host scheduling, adapter behavior, and the RS-485 wire.

From application to RS-485 wire

MS/TP qualification spans host scheduling, adapter behavior, and the RS-485 wire.

MS/TP qualification spans host scheduling, adapter behavior, and the RS-485 wire.

From a v0.15.0 source checkout, which holds the example script, with the Python package installed:

Terminal window
python examples/python/mstp_mini_device.py \
--serial /dev/serial/by-id/usb-YOUR_ADAPTER \
--baud 38400 \
--mac 3 \
--max-master 127 \
--max-info-frames 1 \
--instance 123001

Replace the serial path, MAC, baud, and device instance before connecting. The example’s default baud is 38400; it is not a universal setting for every trunk. The Python path accepts configured rates of 9600, 19200, 38400, 57600, 76800, and 115200; acceptance of a numeric setting does not establish a tested hardware matrix.

The example passes serial_port, mstp_baud, mstp_mac, mstp_max_master, and mstp_max_info_frames to BACnetServer. The Python API documents the same options for BACnetClient and the MstpEndpoint alternative, and the rest they all take: mstp_extended_frames (off by default) for NPDUs of up to 1497 octets, mstp_echo and mstp_echo_grace_ms for an adapter that hears its own frames, and mstp_transmit_latency_pad_ms, mstp_usage_timeout_ms and mstp_reply_timeout_ms for USB adapter latency (by default a 4 ms pad on Windows and none elsewhere, and 35 ms and 300 ms waits).

Confirm stable discovery and a small property read with a peer. Then qualify under representative host and bus load. Record the operating system/kernel, adapter, driver, baud rate, station count, direction-control mode, and load conditions.

On-wire timing measurements are more informative than an average Rust function duration. USB buffering and host scheduling can change when bytes reach the wire or application. Do not infer full Clause 9 behavior, extended-frame coverage (off unless mstp_extended_frames=True), segmented MS/TP behavior, or a combined client/server endpoint from one successful mini-device demonstration.

Do not make a blanket claim either way. Determine the result on the target hardware under representative load. The project’s timing-qualification issue tracks the evidence needed to decide whether ordinary Linux is sufficient or whether a different adapter, native UART, a dedicated execution mode, PREEMPT_RT, or a separate serial front-end is justified.

On Linux, the Rust transport’s dedicated thread and the CLI (--mstp-rt-priority, --mstp-cpus) can run the MS/TP loop under SCHED_FIFO and pin it to CPUs; the Python bindings don’t expose these settings. Keep an MS/TP trunk reliable on Linux covers the timing, these settings, privileges and how to measure the result.

Repeated token loss, unstable latency, duplicate station addresses, or unexplained retries are reasons to stop expanding the test—not reasons to claim success because one read completed. Return to serial configuration, direction timing, and independent bus measurements.

These instructions target v0.15.0. Source review is not a claim of hardware qualification.

Mini-device source · Python example requirements · On-wire qualification work.

Release v0.15.0 ·Build and integrate. Pre-1.0 APIs; partial conformance.Support & limitations