Troubleshoot by symptom
Capture the exact program version, command or API call, transport, host platform, and failure symptom. Keep a sanitized record of the local address/port, target address, object/property, and whether a smaller operation works.
The executable or module does not start
Section titled “The executable or module does not start”Check installation before the network. The reviewed Linux CLI release dynamically links libpcap; a missing libpcap.so.0.8 can prevent even --version from starting. Install the platform’s libpcap runtime through its package manager, or use the basic Cargo build without pcap. A Python wheel/import problem is a different path: use the correct interpreter and run the native import check.
A local fixture can separate installation and protocol basics from network configuration. Try the bounded loopback lab.
Nothing is discovered
Section titled “Nothing is discovered”Try a directed Who-Is to one known device, then a read of a known property. Verify the local interface, intended broadcast destination, BACnet UDP port, remote port, routing, and firewall. Consider VPNs, containers, virtual machines, and subnet boundaries.
An empty discovery result does not prove that a building has no devices. A successful directed read does not prove that broadcasts can traverse the same path.
A device instance works in the shell but not in a script
Section titled “A device instance works in the shell but not in a script”The shell can retain discovered devices in its session. A separate process does not inherit that session’s cache. Use an explicit target address for a one-shot operation, or keep discovery and device-instance lookup within the same supported session.
For v0.11.0, do not promise a one-shot read to DNET:instance; the reviewed dispatch rejects that target form. A routed network requires more than finding a router’s IP address.
The socket is already in use
Section titled “The socket is already in use”Identify other local BACnet tools and services using the intended address/port. Close or reconfigure the conflicting lab application deliberately. An ephemeral port can suit a directed-read example, but changing ports is not a universal discovery fix.
On a multi-interface machine, verify actual transport behavior rather than assuming the configured interface input guarantees receive isolation.
Unknown object or property
Section titled “Unknown object or property”Confirm the selected device identity and object instance. Read the name/type before expanding to bulk requests. A service can be implemented while a particular object property is absent or read-only. Treat a per-property RPM error as a per-property result, not a complete call success or total network outage.
Small reads work; large reads time out
Section titled “Small reads work; large reads time out”Reduce the request to one object/property. Investigate the peer’s APDU limits, routing path, response size, and segmentation behavior. Do not make an unsupported peer work by endlessly increasing concurrency or retry counts. Record the smallest working and smallest failing requests.
BACnet/SC connection fails
Section titled “BACnet/SC connection fails”Check whether the binary includes SC support, then distinguish URL/connectivity, certificate trust, hostname/validity, client identity, hub acceptance, and BACnet target errors. The v0.11.0 CLI uses native trust roots; Python has an explicit CA argument. There is no reviewed --sc-ca-cert CLI flag. Current dev instead requires --sc-ca; see the migration links above.
The exact message no native root certificates found points to an empty root store in the v0.11.0 CLI’s SC construction path. Fix the trust deployment using approved procedures; do not disable verification.
The serial port opens but MS/TP is unstable
Section titled “The serial port opens but MS/TP is unstable”Check duplicate MACs, baud, Max_Master, adapter/driver behavior, transmit-direction timing, and the physical trunk. Test representative host load and observe the wire. Opening a serial file and completing one read do not establish deterministic token timing or full Clause 9 behavior.
Use the MS/TP guide for the qualification boundary. A real-time kernel recommendation must be tied to evidence from the actual host and adapter, not merely the language used by the stack.
A write succeeded but the present value did not change
Section titled “A write succeeded but the present value did not change”Check commandability, priority arbitration, datatype, and the active higher-priority slots. Verify the physical process through the approved site procedure. Do not escalate to a stronger priority just to override an unexplained result.
What to include in an issue
Section titled “What to include in an issue”Describe the task, version/build features, platform and transport, minimal reproduction, expected result, actual result, and sanitized logs. For serial issues, include the adapter and driver as well as baud and direction-control mode. For SC issues, identify the failing stage without attaching private keys.
Open a project issue. Use the repository’s current security-reporting instructions for sensitive findings rather than publishing operational credentials or sensitive site data.
Sources and release scope
Section titled “Sources and release scope”These instructions target v0.11.0. Source review is not a claim of hardware qualification.
CLI behavior · SC error and trust implementation · Versioned API · MS/TP timing work.
Release v0.11.0 ·Current development. Follow the scope named on each page. Pre-1.0 APIs; partial conformance.Support & limitations