Network Port and Number controls
Build and integrate / Network Port and Number controls
A Network Port object, a transport’s bound socket and a learned network number are related but distinct. Choose the contract that fits your task.
Three different actions
Section titled “Three different actions”| Action | What it establishes |
|---|---|
Declare NetworkPortObject::new_bip or a DeviceIdentity port |
A configured object snapshot; no socket bind, NIC discovery or automatic authority |
| Register one B/IP receiving port | An explicit association between one selected built-in object and this owner’s actual bound address and B/IP mode |
| Receive local Number controls | Passive nonrouter learning and replies on an opted-in transport; no new registration, router or configured-number API |
Register a B/IP receiving port
Section titled “Register a B/IP receiving port”Use registration when a full server or shared B/IP endpoint should expose its actual receiving port through the selected Network Port object.
- Create a built-in IPV4 Network Port with a concrete unicast interface, configured UDP port and local Port ID 1–255. UDP port zero is allowed before bind; it is not the Port ID.
- Add it to the database and explicitly select its object identifier with
ServerConfig.registered_network_port, the server builder’s.registered_network_port(oid), orBipEndpointBuilder::registered_network_port(oid). - Start the owner. It validates the bound B/IP capability and reconciles the selected IP, actual UDP port, derived MAC and B/IP mode: NORMAL, FOREIGN or BBMD.
- Read the selected object or, on the documented RP/RPM paths, the Network Port wildcard instance 4194303. Successful responses name the concrete selected object.
Mask, gateway and DNS stay explicit configuration. Port APDU_Length (399) describes local capacity independently of Device Max_APDU_Length_Accepted (62), remote requester limits and routed path limits. Do not copy one limit into all four roles.
The port follows the transport’s mode (#939). A foreign device adds FD_BBMD_Address and FD_Subscription_Lifetime; a BBMD adds its BDT, FDT and BBMD_Accept_FD_Registrations, read live from the transport’s tables. With a ReinitializeDevice handler, the BDT, BBMD_Accept_FD_Registrations and the two foreign-device rows are writable and take effect on ACTIVATE_CHANGES or WARMSTART. Registration rejects a transport that is both a BBMD and a foreign device, a wildcard interface and links that are neither B/IP nor B/IPv6. It protects the selected object against replacement/removal and activation-dependent changes while admitted work and the socket remain owned. A declaration in a shared database cannot give an unregistered responder another owner’s association. The canonical registration contract covers alias resolution and cleanup details.
A full server on B/IPv6 registers the same way with an IPV6 object, NetworkPortObject::new_bip6 (#1579), and so does a shared endpoint composed over a Bip6Transport, which declares the port with DeviceIdentity::with_bip6_port (#1940). Build the transport with Some(instance) of the served Device: that instance is the VMAC the port publishes, and another instance or a random VMAC fails at start (#2057). Startup publishes the bound address and UDP port, the VMAC as MAC_Address, the multicast group and BACnet_IPv6_Mode, and the port serves the IPv6 address, prefix length, gateway and DNS rows instead of the IPv4 ones. Bip6Transport runs NORMAL or FOREIGN, and has no BBMD mode. With a ReinitializeDevice handler its two foreign-device rows are writable, and ACTIVATE_CHANGES moves the running registration, as on B/IP. Registration also refuses IPv4-mapped and link-local addresses.
Let passive Number learning do its work
Section titled “Let passive Number learning do its work”Supported owners consume What-Is-Network-Number and Network-Number-Is automatically. They make no announcement at startup; a BACnetRouter port does, broadcasting Network-Number-Is before its I-Am-Router-To-Network. An unregistered runtime starts UNKNOWN even if its database contains an unrelated configured object. A registered nonzero configured number starts CONFIGURED and retains that authority.
| Current state and input | Result |
|---|---|
| UNKNOWN + valid local query | No reply because the owner knows no number |
| UNKNOWN or LEARNED + valid broadcast NNI, flag 0 | Learn the announced number |
| Any nonconfigured learned state + valid broadcast NNI, flag 1 | Learn with configured precedence; later flag-0 announcements cannot replace it |
| Locally CONFIGURED + conflicting NNI | Keep configuration; emit a debug diagnostic |
| Known state + valid local unicast or broadcast query | Send a local-broadcast NNI; learned states transmit flag 0 |
Routed controls, malformed payloads and unicast NNI are ignored. Rejection of zero, reserved 65535 and flags beyond 0/1 is the implementation’s validation policy. A Forwarded-NPDU can be a logical broadcast even when its UDP hop is unicast; it still has to pass that mode’s transport admission rules. Learning a number does not authenticate its origin.
Standalone clients use the same learning rules without a Device object, registration or configured-number setter. Reconstructing an unregistered runtime resets it to UNKNOWN; learned state is not persistent configuration.
Know which owner and link were exercised
Section titled “Know which owner and link were exercised”Full servers and shared endpoints cover NORMAL B/IP, SC and MS/TP; B/IP BBMD/foreign Number controls also have bounded shared-endpoint wire evidence. Standalone Rust clients have independent Number wire evidence for NORMAL/BBMD/foreign B/IP, SC, Linux Ethernet and normal/configured-foreign B/IPv6. Full B/IPv6 servers cover both modes. The standalone B/IP client cases independently capture BBMD Original-Broadcast and configured-foreign DBTN through admission/refusal, alternate forwarding and registration NAK/retry, with requester progress and stopped-socket release. MS/TP LoopbackSerial tests cover the standalone client too, in both execution modes. These are Number-specific claims; broader BBMD/foreign endpoint administration remains experimental.
Each owner has a bounded serial Number worker separate from APDU dispatch. Holding that producer does not stop independent incoming request/ACK processing, but a shared physical writer still serializes outgoing bytes. Stop cancels and joins owned control work. Already transmitted bytes cannot be retracted.
Next steps
Section titled “Next steps”Use the transport and evidence matrix to distinguish actual wire, simulated and platform coverage. For complete state, capacity and per-media rules, read Local Network Number controls.