Configure BACnet/SC
BACnet/SC setup combines a WebSocket/TLS connection with BACnet-specific identities and hub behavior. A successful TCP or TLS connection alone does not establish a complete BACnet/SC deployment.
This guide covers CLI, Python and Rust setup, trust roles, durable device identity and failure stages. The upgrade guide lists the release’s changes to BACnet/SC liveness and timeouts.
Before connecting
Section titled “Before connecting”Obtain the hub URL, the CA certificate that verifies the hub, your node’s certificate and private key, and an allocated VMAC and device UUID. Ensure the hub’s certificate identity matches the hub name you are using and that the system clock is appropriate for certificate validation.
Keep private keys outside the repository and the generated site. Example names below are not deployable credentials.
Prepare identities and credentials before connecting
Section titled “Prepare identities and credentials before connecting”Obtain these from the installation owner:
- The hub’s
wss://URL and the CA PEM used to verify it, including the expected hostname. - This node’s operational certificate and matching private key.
- A nonreserved local VMAC and a nonzero 16-byte device UUID, distinct from other devices.
- A known remote VMAC, object and property for a bounded initial read.
The caller provisions and durably stores the device UUID before first deployment, then loads the same identity across restarts. Do not generate a new UUID in startup code. Distinct devices must not share it; the hub’s same-UUID replacement behavior is intentional. Credentials and UUIDs are different roles: a syntactically valid UUID does not establish certificate ownership.
CLI feature and identity setup
Section titled “CLI feature and identity setup”Every release CLI executable includes BACnet/SC. For a source build, enable the sc-tls feature:
cargo install --path crates/bacnet-cli --locked --features sc-tlsThe CLI requires a hub URL, the hub’s CA, a client certificate and private key, a local VMAC, and a nonzero local device UUID:
bacnet --sc \ --sc-url wss://hub.example.com/bacnet \ --sc-ca site-ca.pem \ --sc-cert node-cert.pem \ --sc-key node-key.pem \ --sc-vmac 22:01:02:03:04:05 \ --sc-device-uuid 00112233-4455-6677-8899-aabbccddeeff \ read 00:01:02:03:04:05 ai:1 pvReplace every identity and path with an approved value for your network. The final VMAC is the remote target; --sc-vmac is the local node identity. Do not reuse the example VMAC or UUID throughout a deployment.
The read targets the named peer without discovery. Check the CLI transport reference for parser and startup failures.
Trust the hub’s issuer, not the system roots
Section titled “Trust the hub’s issuer, not the system roots”--sc-ca names the CA PEM that verifies the hub’s certificate. The CLI has no fallback to the operating system’s root certificates, so a private hub CA needs no change to the host’s trust store.
Do not “fix” certificate failures by disabling certificate validation. A client certificate supplied through --sc-cert is not the same thing as trusting the issuer of the hub’s certificate.
Python trust configuration
Section titled “Python trust configuration”The Python client and server take sc_ca_cert, sc_client_cert, sc_client_key and a keyword-only sc_device_uuid; all four are required for transport="sc". The hub (ScHub) takes ca_cert for trusted node issuers. These are different roles: a node trusts the hub’s issuer, and the hub validates connecting node identities using its configured trust.
A hub always requires ca_cert and verifies each node’s certificate; there is no server-auth-only mode. Use the Python API and secure-connect example linked below for constructor details rather than translating CLI flags mechanically into Python names.
Use the same prerequisites in Python and Rust
Section titled “Use the same prerequisites in Python and Rust”Python BACnetClient and BACnetServer with transport="sc" require nonempty sc_ca_cert, sc_client_cert, sc_client_key and keyword-only sc_device_uuid. Load the latter as 16 bytes from caller-owned durable storage. Missing or invalid identity/credential presence fails construction; file loading and TLS configuration happen at async startup. A trusted hub’s verification policy remains a separate fact.
The Python credential example and UUID migration are the signature authority. Local TLS configuration errors can be repaired at the same paths and retried within the documented boundary; this does not promise rollback after every later peer/dial failure.
Rust uses ScNodeTlsConfig and the transport’s configured device identity. Raw ScTransport::new(ws, vmac) is initially unconfigured; set a valid UUID before start. Because the caller can dial ws first, transport validation cannot undo that earlier connection. A shared endpoint uses ScEndpointBuilder with a caller-dialed TLS WebSocket; see shared endpoints.
Know how idle links stay up
Section titled “Know how idle links stay up”A node sends a heartbeat once a heartbeat interval passes with nothing received, keeps a hub link that answers, and drops the link when the heartbeat stays unanswered one timeout after the last frame it received. Direct connections take part as well: an accepted connection answers Heartbeat-Request, and a dialed one sends a heartbeat after an interval of silence and closes the link when that goes unanswered.
Two bounds on the accepting side are local settings:
- Direct listener idle bound. A Rust
DirectListenerkeeps an idle accepted link for 360 seconds, which covers every heartbeat timeout up to 300 seconds with a margin. For an initiator set above 300 seconds, raise it withDirectAcceptConfig::with_idle_timeout.DirectListener::startrefuses an idle bound of zero or over one day, and a connect timeout of zero or over 300 seconds. - Hub liveness bound. A hub probes a silent connector, and retires it only after 360 seconds with nothing received from it since the probe, so a dead connector stays listed for about eight minutes after its last frame. Set the bound with
ScHubProbePolicy::with_liveness_boundin Rust orprobe_liveness_bound_mson Python’sScHub, up to one day. A bound under 300 seconds can retire a working connector whose heartbeat timeout is longer.
Diagnose the stage that failed
Section titled “Diagnose the stage that failed”| Stage | Useful check |
|---|---|
| Local configuration | CA/certificate/key file readability and PEM validity, matching key, required UUID and VMAC |
| TLS connection | URL, hostname, certificate validity and issuer trust; operational credentials on both peers |
| SC Connect | Nonzero peer UUID and nonzero advertised limits; hub admission/replacement policy |
| BACnet request | Remote VMAC, requested object/property, request limits and response/error |
| Shutdown | Await the owning client/server/session cleanup; separately stop and join any caller-owned direct listener |
Zero-limit rejection is a bounded local policy, not a claim that all positive limit combinations satisfy the full Standard. TLS 1.3 and explicit node credentials are local policy; successful connection does not prove that an arbitrary remote hub requested and verified the node certificate.
Keep transport identity separate from operation authority
Section titled “Keep transport identity separate from operation authority”A successful TLS connection authenticates a peer; it doesn’t authorize a write or a control request. Decide that in the server’s policy: Restrict who can change a device covers which requests carry a verified certificate principal (direct connections only, not hub-relayed or routed ones), the hub admission and rate limits, and what Python exposes. Outgoing client transactions retain their documented correlation/routing rules, not a universal same-leaf continuity guarantee.
Passive Number replies, including replies to direct queries, use the Hub broadcast path. These controls do not add configured SC Network Port authority or control-origin authorization.
Validate the whole path
Section titled “Validate the whole path”Check the package/build feature, hub URL and port, certificate chain and validity, hostname, local VMAC/UUID, hub acceptance, and remote target identity. After joining the hub, perform a bounded read against a known object. Record sanitized failure stages; never attach a private key to an issue.
These instructions explain configuration boundaries. They are not a certificate-authority operating procedure or a BACnet/SC certification claim.
Sources and release scope
Section titled “Sources and release scope”These instructions target v0.15.0. Source review is not a claim of hardware qualification.
CLI SC transport · CLI flags · Python credentials · SC example.
Next steps
Section titled “Next steps”SC Rust contracts · Shared endpoints · Transport evidence · Network Number controls
Release v0.15.0 ·Build and integrate. Pre-1.0 APIs; partial conformance.Support & limitations