Python client
The client, its options and what its methods return. The Python reference lists every group. Each page opens with its main classes, then the other classes, the dictionaries (TypedDict) and the type aliases, in stub order.
BACnetClient
Section titled “BACnetClient”Async BACnet client for reading/writing properties on remote devices.
Supports BACnet/IP ("bip"), BACnet/IPv6 ("ipv6"),
BACnet/SC ("sc"), and BACnet MS/TP ("mstp") transports, and a
BACnetRouter’s own application entity ("router", #2071).
For SC, sc_ca_cert, sc_client_cert, and sc_client_key must be nonempty paths; omission, None, or empty strings raise ValueError at construction. Their None defaults preserve non-SC use and positional layout only. Async entry loads the explicit site CA and operational cert/key; invalid TLS configuration raises RuntimeError before dialing. No system-root or unauthenticated-client fallback is available.
SC also requires keyword-only sc_device_uuid: exactly 16 bytes, not all zero, copied at construction. Missing, None, wrong length, or all-zero values raise ValueError after credential-presence validation, before file/network I/O. Provision before deployment and durably reuse the same UUID for the device’s lifetime. No generation, persistence, change detection, or version/variant enforcement is provided. Non-SC transports ignore this option.
Keyword-only reconnect=None preserves the default without automatic redial. Supply ScReconnect for SC retries with the same loaded TLS policy, VMAC, UUID and heartbeat settings. Other transports reject this option.
stop() and context exit refuse new work, drain outstanding native operations and join teardown. Cancelling the close Future leaves shutdown running; await stop() again to join it. Drain duration depends on outstanding requests. Entry is exclusive; entering an already running or closing client fails.
Usage:
async with BACnetClient() as client: await client.who_is() devices = await client.discovered_devices() value = await client.read_property("192.168.1.100:47808", oid, pid) print(value.tag, value.value)
# MS/TP peer address is a station MAC string ("7" or "mstp:7")async with BACnetClient(transport="mstp", serial_port="/dev/ttyUSB0", mstp_mac=3) as client: value = await client.read_property("7", oid, pid)
# A B/IPv6 peer is named by its VMAC: "bip6:1234" for device 1234,# "bip6:0x40ABCD" for any VMAC. resolve_vmac finds it from "[ip]:port".# ipv6_device_instance gives the client a stable VMAC of its own.async with BACnetClient(transport="ipv6", port=0, ipv6_device_instance=4321) as client: vmac = await client.resolve_vmac("[2001:db8::10]:47808") value = await client.read_property(vmac, oid, pid)Every address takes "ip:port" (B/IP), "bip6:<device instance>" or "bip6:0x<6 hex digits>" (a B/IPv6 VMAC, ipv6 only),
colon hex such as "01:02:03:04:05:06" (SC, or "00:04:d2" for a
VMAC), or an MS/TP station. "[ip]:port" raises ValueError: use
resolve_vmac. So does a bip6: address on any other transport.
BACnetClient.init
Section titled “BACnetClient.init”def __init__( self, interface: str = "0.0.0.0", port: int = 0xBAC0, broadcast_address: str = "255.255.255.255", apdu_timeout_ms: int = 6000, transport: str = "bip", sc_hub: Optional[str] = None, sc_vmac: Optional[bytes] = None, sc_ca_cert: Optional[str] = None, sc_client_cert: Optional[str] = None, sc_client_key: Optional[str] = None, sc_heartbeat_interval_ms: Optional[int] = None, sc_heartbeat_timeout_ms: Optional[int] = None, ipv6_interface: Optional[str] = None, *, serial_port: Optional[str] = None, mstp_baud: int = 38400, mstp_mac: int = 1, mstp_max_master: int = 127, mstp_max_info_frames: int = 1, mstp_extended_frames: bool = False, mstp_echo: bool = False, mstp_echo_grace_ms: Optional[int] = None, mstp_transmit_latency_pad_ms: Optional[int] = None, mstp_usage_timeout_ms: Optional[int] = None, mstp_reply_timeout_ms: Optional[int] = None, sc_device_uuid: Optional[bytes | bytearray] = None, share_port_by_address: bool = False, min_request_interval_ms: int = 0, ipv6_device_instance: Optional[int] = None, bbmd: Optional[Bbmd] = None, foreign_device: Optional[ForeignDevice] = None, multicast: Optional[Multicast] = None, reconnect: Optional[ScReconnect] = None, sc_npdu_per_origin_limit: int | None = None, sc_failover_hub: str | None = None, sc_connect_timeout_ms: int | None = None, sc_control_rate_limit: tuple[int, int] | None = None, router: Optional[BACnetRouter] = None,) -> Nonetransport="router" with router (a BACnetRouter built
with application="client" or "client_and_server"): run the
client on the router’s own application entity (#2071), with the
router’s address on each network as its own. Entry takes the client’s
share from the running router, once per router start: before the
router starts, or when a client already took it, entry raises
RuntimeError. Requests go out through the router’s table, so name
each device by its network: discover it, then use the
_from_device / _to_device methods. A send to an ip:port
names no network and raises BacnetError. Once the router closes,
each request fails at once with BacnetTransportError (errno
ENOTCONN); stop the client as usual. With
application="client_and_server" the APDU timeout must be under
60000 ms. router without transport="router", or the reverse,
raises ValueError.
sc_failover_hub (SC only, needs reconnect, else
ValueError): a second hub’s wss:// URL, dialled with the same TLS
settings when the primary can’t be reached; the client keeps trying
the primary and returns to it. sc_connect_timeout_ms (SC only, at
least 1, default 10000) bounds each hub dial and Connect-Request.
Follow the link with connection_events() and
connection_status() (#1829).
bbmd / foreign_device (at most one, else ValueError): run
the client as a BBMD (B/IP only), or register it with a BBMD on
another subnet as a foreign device, so its Who-Is reaches that
subnet (#938). foreign_device also applies to
transport="ipv6" with a B/IPv6 BBMD, and then needs
ipv6_device_instance (#1941). See Bbmd and
ForeignDevice.
ipv6_device_instance (B/IPv6 only, default None): the device
instance whose VMAC the client uses (Clause H.7.2), 0 to 4194303, so
peers know it by a stable VMAC such as bip6:0x0010E1. Give a
client an instance to get a stable VMAC; without one it picks a
random VMAC at each start, and that needs a multicast-capable link at
start, which Linux loopback is not. Another transport, or an instance
out of range, raises ValueError.
sc_npdu_per_origin_limit (SC only, default None): maximum
queued, unconsumed NPDUs per ingress path and source. None keeps 32;
explicit values must be 1 through 256. Invalid values or a non-SC
transport raise ValueError before file or network I/O. Negative or
unrepresentably large values raise OverflowError. The aggregate
receive queue remains 256; see sc_npdu_drop_counts.
sc_control_rate_limit (SC only, default None): (burst, per_second), the network-layer messages one source may send back to
back and then each second (#1969). None keeps 256 then 32 a second.
The burst must be 1 through 4096 and the rate at least 1; invalid
values or a non-SC transport raise ValueError before file or network
I/O, and negative values raise OverflowError. A message over its
source’s budget is dropped and counted in control_rate_drops.
mstp_extended_frames (MS/TP only, default False): take and send
extended frames (Types 32 and 33), which carry NPDUs of up to 1497
octets, so APDUs of up to 1476; without it MS/TP carries 480-octet
APDUs and counts an extended frame it hears as invalid.
mstp_echo (MS/TP only, default False): the adapter returns every
octet this station sends (a transceiver whose receiver stays on while
it transmits), so the transport drops that echo rather than take it
for line traffic. mstp_echo_grace_ms (default None, 40 ms; needs
mstp_echo=True and at least 1, else ValueError at start) is how
long after a frame its echo may still be arriving. A negative value,
or one above 4294967295, raises OverflowError when the client is
built.
mstp_transmit_latency_pad_ms, mstp_usage_timeout_ms and
mstp_reply_timeout_ms (MS/TP only, default None, the transport’s
own): the time added to a frame’s wire time on a port that can’t
report its end (4 ms on Windows, where the port has none, 0 elsewhere;
at most 15), and T_usage_timeout (20 to 35, default 35) and
T_reply_timeout (255 to 300, default 300), in milliseconds. A value
outside those ranges raises ValueError at start, before the port
opens.
share_port_by_address (B/IP only, default False): bind the
interface address itself, so clients and devices on other addresses
of this host can share the port. Needs an explicit interface and a
nonzero port; broadcasts and unicast are still handled in the order
they arrived.
min_request_interval_ms (default 0, no pacing; at most
3,600,000, else ValueError) paces the confirmed requests to each
destination: each waits until that long after the latest one sent to
the same destination finished (reply, error or the caller giving up),
or after it was sent while it is still outstanding, checking again
when it wakes. Requests waiting together go one at a time, in no
promised order. Paging a log or polling
then leaves a slow device room for its other clients; requests to
different destinations don’t wait on each other. Behind a router the
pause after a reply holds for requests made one after another only
(#1535).
BACnetClient.aenter
Section titled “BACnetClient.aenter”def __aenter__(self) -> Awaitable[BACnetClient]BACnetClient.aexit
Section titled “BACnetClient.aexit”def __aexit__( self, _exc_type: Any = None, _exc_val: Any = None, _exc_tb: Any = None,) -> Awaitable[None]BACnetClient.read_property
Section titled “BACnetClient.read_property”def read_property( self, address: str, object_id: ObjectIdentifier, property_id: PropertyIdentifier, array_index: Optional[int] = None,) -> Awaitable[PropertyValue]Read a single property from a remote device.
ACK object/property/index must match. Device/Network Port instance 4194303
requests accept a same-type concrete ACK. Malformed/mismatched ACKs raise
BacnetError; this method returns the property value, not ACK metadata,
shaped as PropertyValue describes for read results.
BACnetClient.write_property
Section titled “BACnetClient.write_property”def write_property( self, address: str, object_id: ObjectIdentifier, property_id: PropertyIdentifier, value: PropertyValue, priority: Optional[int] = None, array_index: Optional[int] = None,) -> Awaitable[None]Write a single property on a remote device.
Priority is None or 1..16. Invalid u8 priorities raise ValueError synchronously; integers outside u8 raise OverflowError.
BACnetClient.read_property_multiple
Section titled “BACnetClient.read_property_multiple”def read_property_multiple( self, address: str, specs: list[tuple[ObjectIdentifier, list[tuple[PropertyIdentifier, Optional[int]]]]],) -> Awaitable[list[ReadAccessResult]]Read multiple properties from a remote device (ReadPropertyMultiple).
specs is a list of (object_id, [(property_id, array_index), ...]) tuples.
Returns ordered object/result dictionaries. Empty request/property lists
are rejected; this standalone profile still permits property selectors.
BACnetClient.write_property_multiple
Section titled “BACnetClient.write_property_multiple”def write_property_multiple( self, address: str, specs: list[tuple[ObjectIdentifier, list[tuple[PropertyIdentifier, PropertyValue, Optional[int], Optional[int]]]]],) -> Awaitable[None]Write multiple properties on a remote device (WritePropertyMultiple).
specs is [(object_id, [(property_id, value, priority, array_index), ...]), ...].
Empty request/property lists, ALL/REQUIRED/OPTIONAL targets and u8
priorities outside 1..16 raise ValueError synchronously for the whole
request. Priorities outside u8 raise OverflowError. None, index zero,
proprietary properties, NULL and empty list values remain allowed.
A device error raises BacnetProtocolError with
first_failed_write_attempt set from its WritePropertyMultiple-Error.
BACnetClient.read_property_from_devices
Section titled “BACnetClient.read_property_from_devices”def read_property_from_devices( self, requests: list[tuple[int, ObjectIdentifier, PropertyIdentifier, Optional[int]]], max_concurrent: Optional[int] = None,) -> Awaitable[list[_DeviceReadBatchResult]]Read a property from multiple discovered devices concurrently.
requests is [(device_instance, object_id, property_id, array_index), ...].
max_concurrent must be positive and fit the native usize; None uses 32.
Zero raises ValueError synchronously; out-of-range integers raise OverflowError.
Returns an asyncio Future, accepted by await or asyncio.ensure_future,
not a coroutine for asyncio.create_task. Results are returned in completion
order; request_index is the zero-based
input occurrence, including identical duplicates. Errors are BacnetError
instances with their protocol attributes. Python construction failures
raise from the whole call; cancellation returns no partial list.
Returns [{"request_index": int, "device_instance": int, "value": PropertyValue | None, "error": BacnetError | None}, ...].
BACnetClient.read_property_multiple_from_devices
Section titled “BACnetClient.read_property_multiple_from_devices”def read_property_multiple_from_devices( self, requests: list[tuple[int, list[tuple[ObjectIdentifier, list[tuple[PropertyIdentifier, Optional[int]]]]]]], max_concurrent: Optional[int] = None,) -> Awaitable[list[_DeviceRpmBatchResult]]Read multiple properties from multiple devices concurrently (RPM batch).
max_concurrent must be positive and fit the native usize; None uses 32.
Zero raises ValueError synchronously; out-of-range integers raise OverflowError.
Returns an asyncio Future, accepted by await or asyncio.ensure_future,
not a coroutine for asyncio.create_task. Results are returned in completion
order; request_index is the zero-based
input occurrence, including identical duplicates. Errors are BacnetError
instances with their protocol attributes. Python construction failures
raise from the whole call; cancellation returns no partial list.
Returns [{"request_index": int, "device_instance": int, "results": list[ReadAccessResult] | None, "error": BacnetError | None}, ...].
BACnetClient.write_property_to_devices
Section titled “BACnetClient.write_property_to_devices”def write_property_to_devices( self, requests: list[tuple[int, ObjectIdentifier, PropertyIdentifier, PropertyValue, Optional[int], Optional[int]]], max_concurrent: Optional[int] = None,) -> Awaitable[list[_DeviceWriteBatchResult]]Write a property to multiple devices concurrently.
Every priority must be None or 1..16; invalid u8 priorities raise ValueError synchronously before any batch dispatch. Integers outside u8 raise OverflowError.
requests is [(device_instance, object_id, property_id, value, priority, array_index), ...].
max_concurrent must be positive and fit the native usize; None uses 32.
Zero raises ValueError synchronously; out-of-range integers raise OverflowError.
Returns an asyncio Future, accepted by await or asyncio.ensure_future,
not a coroutine for asyncio.create_task. Results are returned in completion
order; request_index is the zero-based
input occurrence, including identical duplicates. Errors are BacnetError
instances with their protocol attributes. Python construction failures
raise from the whole call; cancellation returns no partial list.
Returns [{"request_index": int, "device_instance": int, "error": BacnetError | None}, ...].
BACnetClient.who_is
Section titled “BACnetClient.who_is”def who_is( self, low_limit: Optional[int] = None, high_limit: Optional[int] = None,) -> Awaitable[None]Broadcast a Who-Is request. Responses are collected asynchronously;
use discovered_devices() to retrieve them.
Give low_limit and high_limit together or not at all, each from
0 to 4194303: one alone, low_limit above high_limit, or a limit
past 4194303 raises ValueError before anything is sent.
BACnetClient.discover
Section titled “BACnetClient.discover”def discover( self, timeout_ms: int = 3000, low_limit: Optional[int] = None, high_limit: Optional[int] = None,) -> Awaitable[list[DiscoveredDevice]]Convenience: send WhoIs, wait timeout_ms, return discovered devices.
Give low_limit and high_limit together or not at all, each from
0 to 4194303: one alone, low_limit above high_limit, or a limit
past 4194303 raises ValueError before anything is sent.
BACnetClient.who_has_by_id
Section titled “BACnetClient.who_has_by_id”def who_has_by_id( self, object_id: ObjectIdentifier, low_limit: Optional[int] = None, high_limit: Optional[int] = None,) -> Awaitable[None]Broadcast Who-Has by object identifier.
Give low_limit and high_limit together or not at all, each from
0 to 4194303: one alone, low_limit above high_limit, or a limit
past 4194303 raises ValueError before anything is sent.
BACnetClient.who_has_by_name
Section titled “BACnetClient.who_has_by_name”def who_has_by_name( self, name: str, low_limit: Optional[int] = None, high_limit: Optional[int] = None,) -> Awaitable[None]Broadcast Who-Has by object name.
Give low_limit and high_limit together or not at all, each from
0 to 4194303: one alone, low_limit above high_limit, or a limit
past 4194303 raises ValueError before anything is sent.
BACnetClient.who_has_replies
Section titled “BACnetClient.who_has_replies”def who_has_replies( self, object: ObjectIdentifier | str, low_limit: Optional[int] = None, high_limit: Optional[int] = None, timeout_ms: int = 3000,) -> Awaitable[list[IHave]]Broadcast a Who-Has for object (an identifier, or a name) and
collect the I-Haves that answer it for timeout_ms: one per device
and object, in arrival order; an empty list when none answer. The
limits follow who_has_by_id()’s rule (#1850). It holds the
started client for the whole wait, so stop() waits up to
timeout_ms for it.
BACnetClient.i_have_events
Section titled “BACnetClient.i_have_events”def i_have_events(self) -> Awaitable[IHaveIterator]Follow every I-Have the client receives from now on, an answer to its own Who-Has or not (#1850). RuntimeError before start and after stop.
BACnetClient.discover_routers
Section titled “BACnetClient.discover_routers”def discover_routers( self, network: Optional[int] = None, timeout_ms: int = 3000,) -> Awaitable[list[DiscoveredRouter]]Broadcast a Who-Is-Router-To-Network for network (or every
network) and collect the routers that answer for timeout_ms, one
per router MAC in the order first heard; for a network, only the
routers listing it. An empty list when none answer. network 0 or
65535 raises BacnetError (#1850). It holds the started client for
the whole wait, so stop() waits up to timeout_ms for it.
BACnetClient.network_reports
Section titled “BACnetClient.network_reports”def network_reports(self) -> Awaitable[NetworkReportIterator]Follow the I-Am-Router-To-Network, Network-Number-Is and Reject-Message-To-Network messages the client receives from now on (#1850). RuntimeError before start and after stop.
BACnetClient.discovered_devices
Section titled “BACnetClient.discovered_devices”def discovered_devices(self) -> Awaitable[list[DiscoveredDevice]]Return all devices discovered so far.
BACnetClient.get_device
Section titled “BACnetClient.get_device”def get_device(self, instance: int) -> Awaitable[Optional[DiscoveredDevice]]Look up a discovered device by instance number.
BACnetClient.clear_devices
Section titled “BACnetClient.clear_devices”def clear_devices(self) -> Awaitable[None]Clear the discovered device table.
BACnetClient.resolve_vmac
Section titled “BACnetClient.resolve_vmac”def resolve_vmac(self, address: str) -> Awaitable[str]Find the VMAC of the B/IPv6 node at address, given as
"[ip]:port", and return it as "bip6:0x0004D2", the form the
other methods take.
A B/IPv6 node is addressed by its VMAC, not its IPv6 address (Clause
U.1.3). This asks the node with a Virtual-Address-Resolution sent by
unicast, up to three times a second apart (Clause U.5), unless the
client already knows which VMAC is at that address. A link-local
address may carry its interface as a numeric zone
("[fe80::1%3]:47808").
Needs a started client with transport="ipv6", else RuntimeError.
Any other address form raises ValueError. Raises BacnetTransportError
(errno ETIMEDOUT) when nothing answers within three seconds, or when
the node refuses.
BACnetClient.who_am_i
Section titled “BACnetClient.who_am_i”def who_am_i( self, vendor_id: int, model_name: str, serial_number: str,) -> Awaitable[None]Broadcast a Who-Am-I request announcing this device’s identity.
The three arguments should match the sender’s Device object properties
(vendor_id is 0-65535). Raises ValueError if a string cannot be
encoded, or OverflowError for a vendor_id that doesn’t fit.
BACnetClient.who_is_directed
Section titled “BACnetClient.who_is_directed”def who_is_directed( self, address: str, low_limit: Optional[int] = None, high_limit: Optional[int] = None,) -> Awaitable[None]Send a Who-Is to a specific device address (unicast).
Give low_limit and high_limit together or not at all, each from
0 to 4194303: one alone, low_limit above high_limit, or a limit
past 4194303 raises ValueError before anything is sent.
BACnetClient.time_synchronization
Section titled “BACnetClient.time_synchronization”def time_synchronization( self, address: str, date: tuple[int, int, int, int], time: tuple[int, int, int, int],) -> Awaitable[None]Send a TimeSynchronization request (unconfirmed).
date is (year, month, day, day_of_week); time is
(hour, minute, second, hundredths). The request sets a clock, so
both must be specific: a real day with the full year (1900..2154),
month 1..12, day 1..31 and day_of_week that day’s own weekday
(1 = Monday), and every time field in range. A field that is
UNSPECIFIED (255) or a pattern value (an odd month, the last
day) raises ValueError before anything is sent.
BACnetClient.utc_time_synchronization
Section titled “BACnetClient.utc_time_synchronization”def utc_time_synchronization( self, address: str, date: tuple[int, int, int, int], time: tuple[int, int, int, int],) -> Awaitable[None]Send a UTCTimeSynchronization request (unconfirmed); arguments as
for time_synchronization.
BACnetClient.read_property_from_device
Section titled “BACnetClient.read_property_from_device”def read_property_from_device( self, device_instance: int, object_id: ObjectIdentifier, property_id: PropertyIdentifier, array_index: Optional[int] = None,) -> Awaitable[PropertyValue]Read a property from a device by instance number (auto-routing).
BACnetClient.read_property_multiple_from_device
Section titled “BACnetClient.read_property_multiple_from_device”def read_property_multiple_from_device( self, device_instance: int, specs: list[tuple[ObjectIdentifier, list[tuple[PropertyIdentifier, Optional[int]]]]],) -> Awaitable[Any]Read multiple properties from a device by instance number (auto-routing).
BACnetClient.write_property_to_device
Section titled “BACnetClient.write_property_to_device”def write_property_to_device( self, device_instance: int, object_id: ObjectIdentifier, property_id: PropertyIdentifier, value: PropertyValue, priority: Optional[int] = None, array_index: Optional[int] = None,) -> Awaitable[None]Write a property on a device by instance number (auto-routing).
Priority is None or 1..16. Invalid u8 priorities raise ValueError synchronously before lookup; integers outside u8 raise OverflowError.
BACnetClient.write_property_multiple_to_device
Section titled “BACnetClient.write_property_multiple_to_device”def write_property_multiple_to_device( self, device_instance: int, specs: list[tuple[ObjectIdentifier, list[tuple[PropertyIdentifier, PropertyValue, Optional[int], Optional[int]]]]],) -> Awaitable[None]Write multiple properties to a device by instance number (auto-routing).
Same whole-request validation as write_property_multiple, synchronously before discovery or dispatch: nonempty request/property lists, no special selectors, priority None or 1..16. Invalid u8 priorities/structure raise ValueError; priorities outside u8 raise OverflowError.
BACnetClient.add_device
Section titled “BACnetClient.add_device”def add_device(self, device_instance: int, address: str) -> Awaitable[None]Add a device to the discovery table manually (useful when address is known without WhoIs).
BACnetClient.subscribe_cov
Section titled “BACnetClient.subscribe_cov”def subscribe_cov( self, address: str, subscriber_process_identifier: int, monitored_object_identifier: ObjectIdentifier, confirmed: bool, lifetime: Optional[int] = None,) -> Awaitable[None]Subscribe to Change-of-Value notifications for an object.
lifetime=None or 0 is indefinite; positive values are seconds. Use unsubscribe_cov for cancellation. confirmed always supplies the mode.
BACnetClient.unsubscribe_cov
Section titled “BACnetClient.unsubscribe_cov”def unsubscribe_cov( self, address: str, subscriber_process_identifier: int, monitored_object_identifier: ObjectIdentifier,) -> Awaitable[None]Cancel a COV subscription.
BACnetClient.subscribe_cov_property_multiple
Section titled “BACnetClient.subscribe_cov_property_multiple”def subscribe_cov_property_multiple( self, address: str, subscriber_process_identifier: int, specs: list[tuple[ObjectIdentifier, list[tuple[PropertyIdentifier, Optional[int], Optional[float], bool]]]], issue_confirmed_notifications: bool, max_notification_delay: Optional[int] = None, lifetime: Optional[int] = None,) -> Awaitable[None]Subscribe to COV notifications for multiple properties on multiple objects.
specs is [(object_id, [(property_id, array_index, cov_increment, timestamped), ...]), ...].
issue_confirmed_notifications is required, including for cancellation requests.
For subscriptions and re-subscriptions, lifetime and max_notification_delay are both required.
For whole-context cancellations, pass an empty specs list and omit both fields.
Complete timing and nested-reference validation raises ValueError synchronously,
before an awaitable, address parsing, client-state access or I/O. Each supplied
object needs references; ALL/REQUIRED/OPTIONAL selectors are prohibited and the
cumulative reference limit is 10,000. Empty outer lists remain encodable with
valid finite timing, without claiming bundled-server empty-context support.
A device error about one COV reference raises BacnetProtocolError with
first_failed_subscription set; a general failure leaves it None.
BACnetClient.cov_notifications
Section titled “BACnetClient.cov_notifications”def cov_notifications(self) -> Awaitable[CovNotificationIterator]Get an async iterator for incoming COV notifications.
BACnetClient.delete_object
Section titled “BACnetClient.delete_object”def delete_object(self, address: str, object_id: ObjectIdentifier) -> Awaitable[None]Delete an object on a remote device (DeleteObject service).
BACnetClient.create_object
Section titled “BACnetClient.create_object”def create_object( self, address: str, object_specifier: Union[ObjectType, ObjectIdentifier], initial_values: Optional[list[tuple[PropertyIdentifier, PropertyValue, Optional[int], Optional[int]]]] = None,) -> Awaitable[ObjectIdentifier]Create an object on a remote device (CreateObject service).
object_specifier is an ObjectType (server assigns instance) or
ObjectIdentifier (specific instance). initial_values is
[(property_id, value, priority, array_index), ...].
Returns the created object’s identifier from the CreateObject-ACK; an
acknowledgment that doesn’t decode raises BacnetError (the device may
still have created the object). A device error raises
BacnetProtocolError with first_failed_element_number set when the
device answers with a CreateObject-Error.
BACnetClient.device_communication_control
Section titled “BACnetClient.device_communication_control”def device_communication_control( self, address: str, enable_disable: EnableDisable, time_duration: Optional[int] = None, password: Optional[str] = None,) -> Awaitable[None]Send DeviceCommunicationControl to a remote device.
Raises ValueError, before anything is sent, for a password over 20 characters or an empty one (pass None to send no password).
BACnetClient.reinitialize_device
Section titled “BACnetClient.reinitialize_device”def reinitialize_device( self, address: str, reinitialized_state: ReinitializedState, password: Optional[str] = None,) -> Awaitable[None]Send ReinitializeDevice to a remote device.
Raises ValueError, before anything is sent, for a password over 20 characters or an empty one (pass None to send no password).
BACnetClient.acknowledge_alarm_request
Section titled “BACnetClient.acknowledge_alarm_request”def acknowledge_alarm_request( self, address: str, acknowledging_process_identifier: int, event_object_identifier: ObjectIdentifier, event_state_acknowledged: EventState, timestamp: BACnetTimeStamp, acknowledgment_source: str, time_of_acknowledgment: BACnetTimeStamp,) -> Awaitable[None]Acknowledge an alarm with exact caller-supplied BACnetTimeStamp values.
timestamp must echo the original event notification timestamp;
time_of_acknowledgment is selected by the caller.
BACnetClient.acknowledge_alarm
Section titled “BACnetClient.acknowledge_alarm”def acknowledge_alarm( self, address: str, acknowledging_process_identifier: int, event_object_identifier: ObjectIdentifier, event_state_acknowledged: EventState, acknowledgment_source: str,) -> Awaitable[None]Deprecated compatibility method.
This method fabricates sequence-number zero for both timestamps. Use
acknowledge_alarm_request for a lossless request.
BACnetClient.get_event_information
Section titled “BACnetClient.get_event_information”def get_event_information( self, address: str, last_received_object_identifier: Optional[ObjectIdentifier] = None,) -> Awaitable[dict[str, Any]]Get event information from a remote device: one GetEventInformation answer, decoded.
Returns {"summaries": [...], "more_events": bool}. Each summary is
{"object_id": ObjectIdentifier, "event_state": EventState, "acknowledged_transitions": BitString, "event_timestamps": [BACnetTimeStamp, BACnetTimeStamp, BACnetTimeStamp], "notify_type": NotifyType, "event_enable": BitString, "event_priorities": [int, int, int]}: the bit strings name TO_OFFNORMAL, TO_FAULT and
TO_NORMAL, and the timestamps and priorities are in that order.
While more_events is true, call again with the last summary’s
object_id as last_received_object_identifier.
BACnetClient.get_alarm_summary
Section titled “BACnetClient.get_alarm_summary”def get_alarm_summary(self, address: str) -> Awaitable[list[dict[str, Any]]]Get alarm summary from a remote device.
Returns [{"object_id": ObjectIdentifier, "alarm_state": EventState, "acknowledged_transitions": BitString}, ...], the bit string naming
TO_OFFNORMAL, TO_FAULT and TO_NORMAL.
BACnetClient.get_enrollment_summary
Section titled “BACnetClient.get_enrollment_summary”def get_enrollment_summary( self, address: str, acknowledgment_filter: AcknowledgmentFilter = ..., event_state_filter: Optional[EnrollmentSummaryEventStateFilter] = None, event_type_filter: Optional[EventType] = None, min_priority: Optional[int] = None, max_priority: Optional[int] = None, notification_class_filter: Optional[int] = None,) -> Awaitable[list[dict[str, Any]]]Get enrollment summary from a remote device.
Returns [{"object_id": ObjectIdentifier, "event_type": EventType, "event_state": EventState, "priority": int, "notification_class": Optional[int]}, ...].
BACnetClient.read_range
Section titled “BACnetClient.read_range”def read_range( self, address: str, object_id: ObjectIdentifier, property_id: PropertyIdentifier, array_index: Optional[int] = None, range_type: Optional[Literal["position", "sequence", "time"]] = None, reference_index: Optional[int] = None, reference_seq: Optional[int] = None, count: Optional[int] = None, *, reference_time: ReferenceTime | None = None, validation: Literal["strict", "lenient"] = "strict",) -> Awaitable[ReadRangeResult]Read a range of items from a list or log object.
range_type is "position", "sequence", "time" or
None (all-items). "time" reads the count items newer than
reference_time (older, for a negative count): a naive
datetime.datetime in the device’s local time, or a
((year, month, day, day_of_week), (hour, minute, second, hundredths)) pair; an aware datetime raises ValueError, since the
device’s zone isn’t known here (#1533). Invalid selectors, array index
zero, missing or zero counts and a time that isn’t specific raise
ValueError before I/O; a count outside INTEGER16 (-32768..=32767)
raises OverflowError before address parsing or I/O (#1360).
Position/sequence reference zero is valid; omitted references default
to zero.
validation="strict" refuses an answer that breaks a ReadRange rule
with BacnetReadRangeViolationError, whose rule names it;
"lenient" keeps it and lists the rules in violations (#1531).
Decode a log’s records with decode_log_records.
BACnetClient.read_log_page
Section titled “BACnetClient.read_log_page”def read_log_page( self, address: str, object_id: ObjectIdentifier, cursor: LogCursor = None, page_size: int = 100,) -> Awaitable[LogPage]Read one page of a log’s Log_Buffer from cursor (#1530).
cursor is None or "oldest" (the oldest record, found from
Record_Count and Total_Record_Count), ("sequence", n),
("position", n) or ("time", reference_time); lists work
too, so a checkpoint survives JSON. Loop on page["next"] until
page["done"], then keep next as the checkpoint. One request
is outstanding at a time. A first record past the one asked for sets
gap; when the log drops the record asked for, the read starts
over from the oldest. A page answered from before the one asked for,
or none where the counts say records are, raises
BacnetLogNotAdvancingError: such a device’s sequence numbers are
inconsistent, so read it from ("position", 1). wrapped marks
a page that reached the top of the sequence range. A page whose
records don’t decode raises BacnetError, dropping the records before
the failing one; an answer that breaks a rule the reader can’t
tolerate, such as an echo that doesn’t match, raises
BacnetReadRangeViolationError. A non-log object or a page_size
outside 1..=32767 raises ValueError before I/O.
BACnetClient.atomic_read_file
Section titled “BACnetClient.atomic_read_file”def atomic_read_file( self, address: str, file_identifier: ObjectIdentifier, access_method: str, start_position: int = 0, requested_octet_count: int = 0, start_record: int = 0, requested_record_count: int = 0,) -> Awaitable[AtomicReadFileResult]Read from a file object. access_method is "stream" or "record".
Returns the decoded acknowledgment: access_method, end_of_file,
then start_position and data for stream access, or
start_record, record_count and records for record access.
An acknowledgment in the other access method, or with more octets or
records than requested, raises BacnetError.
BACnetClient.atomic_write_file
Section titled “BACnetClient.atomic_write_file”def atomic_write_file( self, address: str, file_identifier: ObjectIdentifier, access_method: str, start_position: int = 0, file_data: bytes = b"", start_record: int = 0, record_count: int = 0, file_record_data: Optional[list[bytes]] = None,) -> Awaitable[AtomicWriteFileResult]Write to a file object. access_method is "stream" or "record".
Returns the decoded acknowledgment: access_method, then
start_position for stream access or start_record for record
access, where the device says the write took place. An
acknowledgment in the other access method raises BacnetError.
BACnetClient.add_list_element
Section titled “BACnetClient.add_list_element”def add_list_element( self, address: str, object_id: ObjectIdentifier, property_id: PropertyIdentifier, list_of_elements: bytes, array_index: Optional[int] = None,) -> Awaitable[None]Add elements to a list property (AddListElement service). Requires nonempty, completely framed element bytes and a nonzero optional index. Invalid framing/index zero raises ValueError synchronously before client access; indexes outside u32 raise OverflowError. Empty-valued, constructed/context/vendor elements are retained without remote datatype validation. Shared limits: 1 MiB per tag, 32 context levels including the service wrapper; application Boolean has no payload bytes. A device error raises BacnetProtocolError with first_failed_element_number set when the device answers with a ChangeList-Error.
BACnetClient.remove_list_element
Section titled “BACnetClient.remove_list_element”def remove_list_element( self, address: str, object_id: ObjectIdentifier, property_id: PropertyIdentifier, list_of_elements: bytes, array_index: Optional[int] = None,) -> Awaitable[None]Remove elements from a list property (RemoveListElement service). Requires nonempty, completely framed element bytes and a nonzero optional index. Invalid framing/index zero raises ValueError synchronously before client access; indexes outside u32 raise OverflowError. Empty-valued, constructed/context/vendor elements are retained without remote datatype validation. Shared limits: 1 MiB per tag, 32 context levels including the service wrapper; application Boolean has no payload bytes. A device error raises BacnetProtocolError with first_failed_element_number set when the device answers with a ChangeList-Error.
BACnetClient.confirmed_private_transfer
Section titled “BACnetClient.confirmed_private_transfer”def confirmed_private_transfer( self, address: str, vendor_id: int, service_number: int, service_parameters: Optional[bytes] = None,) -> Awaitable[dict[str, Any]]Send a ConfirmedPrivateTransfer request.
Returns {"vendor_id": int, "service_number": int, "result_block": bytes | None}.
A device error raises BacnetProtocolError with vendor_id,
service_number and error_parameters set from its
ConfirmedPrivateTransfer-Error. An ACK that is malformed, cut short
or has octets after its last member raises BacnetError.
BACnetClient.unconfirmed_private_transfer
Section titled “BACnetClient.unconfirmed_private_transfer”def unconfirmed_private_transfer( self, address: str, vendor_id: int, service_number: int, service_parameters: Optional[bytes] = None,) -> Awaitable[None]Send an UnconfirmedPrivateTransfer request.
BACnetClient.confirmed_text_message
Section titled “BACnetClient.confirmed_text_message”def confirmed_text_message( self, address: str, source_device: ObjectIdentifier, message_priority: MessagePriority, message: str, message_class_type: Optional[str] = None, message_class_value: Optional[Any] = None,) -> Awaitable[None]Send a ConfirmedTextMessage.
message_class_type is "numeric" or "text" (or None for no class).
BACnetClient.unconfirmed_text_message
Section titled “BACnetClient.unconfirmed_text_message”def unconfirmed_text_message( self, address: str, source_device: ObjectIdentifier, message_priority: MessagePriority, message: str, message_class_type: Optional[str] = None, message_class_value: Optional[Any] = None,) -> Awaitable[None]Send an UnconfirmedTextMessage.
BACnetClient.life_safety_operation
Section titled “BACnetClient.life_safety_operation”def life_safety_operation( self, address: str, requesting_process_identifier: int, requesting_source: str, operation: LifeSafetyOperation, object_identifier: Optional[ObjectIdentifier] = None,) -> Awaitable[None]Send a LifeSafetyOperation request.
BACnetClient.write_group
Section titled “BACnetClient.write_group”def write_group( self, address: Optional[str], group_number: int, write_priority: int, change_list: list[tuple[int, Optional[int], Union[PropertyValue, bytes, bytearray]]], inhibit_delay: Optional[bool] = None, *, network: Optional[int] = None,) -> Awaitable[None]Send a WriteGroup request (unconfirmed).
With an address the request goes to that one device. With
address=None it is broadcast: on the local network, or with
network on that remote network (1-65534), or on every network when
network is 65535. Give network only with address=None.
group_number is 1-4294967295 (group 0 is reserved) and
write_priority is 1-16. change_list is a non-empty list of
(channel, override_priority_or_none, value) tuples, where
channel is a channel number 0-65535, the override priority is 1-16 or
None, and value is a PropertyValue, which is encoded for you,
or a bytes or bytearray holding one encoded BACnetChannelValue.
Either way the value must be one BACnetChannelValue: a single
application-tagged primitive (PropertyValue.real(72.0)), or a
context-0 lighting command, context-1 xy colour or context-2 colour
command (as bytes, or the same octets in
PropertyValue.application_data), with no wrapper tag. Raises
ValueError for anything else, a list for one, TypeError for a
value of another type (a list of ints included), and OverflowError
for integers that don’t fit.
BACnetClient.vt_open
Section titled “BACnetClient.vt_open”def vt_open( self, address: str, vt_class: VTClass, local_vt_session_identifier: int,) -> Awaitable[int]Open a virtual terminal session. Returns the remote session identifier.
local_vt_session_identifier (0-255) is the caller’s own number for
the session, which the peer quotes when it sends data back.
BACnetClient.vt_close
Section titled “BACnetClient.vt_close”def vt_close(self, address: str, session_ids: list[int]) -> Awaitable[None]Close one or more virtual terminal sessions.
session_ids must not be empty and each identifier is 0-255. Raises
ValueError for an empty list, or OverflowError for an integer that
doesn’t fit, before anything is sent. A device error that lists the
sessions it could not close raises BacnetProtocolError with
vt_session_identifiers set.
BACnetClient.vt_data
Section titled “BACnetClient.vt_data”def vt_data( self, address: str, session_id: int, data: bytes, data_flag: bool,) -> Awaitable[dict[str, Any]]Send data over a virtual terminal session.
data_flag is the sequence flag that alternates on each new request
for a session; it is sent as an Unsigned 0 or 1.
Returns {"all_new_data_accepted": bool, "accepted_octet_count": int | None};
the count is an int only when all_new_data_accepted is False.
BACnetClient.confirmed_audit_notification_typed
Section titled “BACnetClient.confirmed_audit_notification_typed”def confirmed_audit_notification_typed( self, address: str, request: AuditNotificationRequestInput,) -> Awaitable[None]Send a validated mapping through the native confirmed Audit helper.
BACnetClient.unconfirmed_audit_notification_typed
Section titled “BACnetClient.unconfirmed_audit_notification_typed”def unconfirmed_audit_notification_typed( self, address: str, request: AuditNotificationRequestInput,) -> Awaitable[None]Send a validated mapping through the native unconfirmed Audit helper.
BACnetClient.audit_log_query_typed
Section titled “BACnetClient.audit_log_query_typed”def audit_log_query_typed( self, address: str, request: AuditLogQueryRequestInput,) -> Awaitable[AuditLogQueryAck]Send a typed Audit Log query and return a canonical decoded mapping.
BACnetClient.confirmed_audit_notification
Section titled “BACnetClient.confirmed_audit_notification”def confirmed_audit_notification( self, address: str, service_data: bytes,) -> Awaitable[None]Send a pre-encoded Clause 21 ConfirmedAuditNotification payload.
This is a raw escape hatch; the bundled server does not execute the service.
BACnetClient.unconfirmed_audit_notification
Section titled “BACnetClient.unconfirmed_audit_notification”def unconfirmed_audit_notification( self, address: str, service_data: bytes,) -> Awaitable[None]Send a pre-encoded Clause 21 UnconfirmedAuditNotification payload.
This is a raw escape hatch; the bundled server does not execute the service.
BACnetClient.audit_log_query
Section titled “BACnetClient.audit_log_query”def audit_log_query(self, address: str, service_data: bytes) -> Awaitable[bytes]Send a pre-encoded Clause 21 AuditLogQuery payload.
This raw escape hatch returns the peer’s response payload. The bundled server does not execute the service.
BACnetClient.sc_npdu_drop_counts
Section titled “BACnetClient.sc_npdu_drop_counts”def sc_npdu_drop_counts(self) -> Awaitable[ScNpduDropCounts]Copy SC ingress counters; requires a started SC owner.
Available while disconnected. Each call returns an independent dictionary; a new transport starts fresh counters. No network I/O is performed.
BACnetClient.sc_peer_info
Section titled “BACnetClient.sc_peer_info”def sc_peer_info(self) -> Awaitable[ScPeerInfo | None]Observe the accepted active SC Hub without I/O; None while disconnected. RuntimeError for non-SC, stopped or closing clients. Historical results own data only. Observation time is not certificate validation time.
BACnetClient.read_bdt
Section titled “BACnetClient.read_bdt”def read_bdt(self, address: str) -> Awaitable[list[tuple[str, str]]]Read a BBMD’s Broadcast Distribution Table as ("ip:port", "mask") rows.
BACnetClient.write_bdt
Section titled “BACnetClient.write_bdt”def write_bdt( self, address: str, entries: Sequence[str | tuple[str, str]],) -> Awaitable[None]Ask a BBMD to take entries (rows as Bbmd(bdt=) takes them)
as its BDT. A BBMD that follows the 2020 standard refuses with 0x0010.
BACnetClient.read_fdt
Section titled “BACnetClient.read_fdt”def read_fdt(self, address: str) -> Awaitable[list[FdtEntry]]Read a BBMD’s Foreign Device Table.
BACnetClient.delete_fdt_entry
Section titled “BACnetClient.delete_fdt_entry”def delete_fdt_entry(self, address: str, entry: str) -> Awaitable[None]Ask a BBMD to delete the foreign device at entry
("ip:port") from its FDT; a refusal is 0x0050.
BACnetClient.register_foreign_device_bvlc
Section titled “BACnetClient.register_foreign_device_bvlc”def register_foreign_device_bvlc(self, address: str, ttl: int) -> Awaitable[None]Register once as a foreign device for ttl seconds (0 to
65535); a refusal is 0x0030. Nothing is renewed and broadcasts don’t
go through the BBMD: foreign_device= does that.
BACnetClient.connection_events
Section titled “BACnetClient.connection_events”def connection_events(self) -> Awaitable[ScEventIterator]Subscribe to the SC hub-connector events (#1829). The first call
after a start gets the events since the client was built, starting
with the first connected (#1908); if that first call comes long
after the start, its first events may be old ones from the build. A
later call is a late subscriber and gets the events from that call
on. A slow reader never holds up the connector: see
ScEventIterator.missed.
RuntimeError for a stopped or non-SC client.
BACnetClient.connection_status
Section titled “BACnetClient.connection_status”def connection_status(self) -> Awaitable[ScLinkStatus]Snapshot the SC hub link without I/O (#1829). RuntimeError for a stopped or non-SC client.
BACnetClient.foreign_registration
Section titled “BACnetClient.foreign_registration”def foreign_registration(self) -> Awaitable[ForeignRegistrationStatus]How the foreign-device registration is going (#938), a refusal
included. Sends nothing. Outside foreign_device= only manual
registrations show. RuntimeError before start and after stop; a
non-B/IP client raises BacnetError.
BACnetClient.stop
Section titled “BACnetClient.stop”def stop(self) -> Awaitable[None]Refuse new work, drain operations, and join native teardown.
Cancelling this Future leaves shutdown running; call stop() again to join it. Drain duration depends on existing requests. Errors retain closing state for another stop attempt.
ScReconnect
Section titled “ScReconnect”Frozen SC client retry settings, copied when passed to BACnetClient.
Delays must be nonzero, initial <= maximum, and maximum <= 86,400,000 ms. Invalid settings raise ValueError; unsigned integer overflow raises OverflowError. Zero retries allows the initial connection and disables active-hub retries after loss. Validation is not deployment qualification.
Properties:
initial_delay_ms: intmax_delay_ms: intmax_retries: int
ScReconnect.init
Section titled “ScReconnect.init”def __init__( self, *, initial_delay_ms: int = 10000, max_delay_ms: int = 600000, max_retries: int = 10,) -> NoneScCertificateMetadata
Section titled “ScCertificateMetadata”Frozen informational metadata; ASCII-escaped fields are at most 1024 bytes.
Properties:
subject: strissuer: strnot_before_unix: intnot_after_unix: intpublic_key_algorithm_oid: strsignature_algorithm_oid: strtext_truncated: boolsubject_alt_names: tuple[ScSubjectAltName, ...]: The DNS, URI, email and IP Subject Alternative Names, in certificate order (#2022); other name forms are left out.
ScSubjectAltName
Section titled “ScSubjectAltName”One Subject Alternative Name exactly as the certificate wrote it:
no case folding, wildcards such as *.example.com as written. Compare
value for equality, never by suffix. Frozen; its repr shows the
kind only.
Properties:
kind: Literal["dns", "uri", "email", "ip"]value: str | ipaddress.IPv4Address | ipaddress.IPv6Address: Astr, or anipaddressaddress for anipname.
ScInspectionFinding
Section titled “ScInspectionFinding”Frozen local interpretation finding; never a TLS acceptance decision.
Properties:
area: Literal["certificate", "san", "key_usage", "extended_key_usage"]kind: Literal["malformed", "duplicate", "unsupported", "truncated"]
ScExtensionInspection
Section titled “ScExtensionInspection”Frozen bounded display. Read certificate findings alongside these values.
Properties:
assessed: boolpresent: boolvalues: tuple[str, ...]
ScInspectedCertificate
Section titled “ScInspectedCertificate”Frozen exact DER fingerprint and optional interpretation, without retained DER.
Properties:
role: Literal["identity", "peer_trust"]index: intsha256: bytesmetadata: ScCertificateMetadata | Nonevalidity: Literal["unavailable", "invalid_interval", "not_yet_valid", "expired", "within_interval"]expiry: Literal["not_assessed", "none", "warning", "alarm"]san: ScExtensionInspectionkey_usage: ScExtensionInspectionextended_key_usage: ScExtensionInspectionfindings: tuple[ScInspectionFinding, ...]
ScKeyFilePermissions
Section titled “ScKeyFilePermissions”Frozen Unix read-mode observations from the opened key file; no ACL audit.
Properties:
group_readable: boolworld_readable: bool
ScPemInspection
Section titled “ScPemInspection”Frozen owned offline data. No credential bytes, client or TLS policy is retained.
Properties:
inspected_at_unix: intpeer_trust_supplied: boolcertificates: tuple[ScInspectedCertificate, ...]key_consistency: Literal["not_assessed", "match", "mismatch", "unusable", "unknown"]key_file_permissions: ScKeyFilePermissions | Nonedirect_issuer: Literal["not_assessed", "direct", "not_direct", "unknown"]: Whether apeer_trustcertificate signed the identity leaf directly (its subject is the leaf’s issuer and the leaf’s signature verifies with its key).not_assessedwithout peer trust;unknownwhen the leaf can’t be parsed or a candidate’s signature algorithm is unsupported. Informational: it changes no acceptance.direct_issuer_index: int | None: Zero-basedpeer_trustindex of the CA that signed the leaf whendirect_issuerisdirect; else None.
ScPeerCertificate
Section titled “ScPeerCertificate”Frozen original DER and optional display interpretation.
Properties:
der: bytesmetadata: ScCertificateMetadata | Noneinspection_error: Literal["certificate_parse_failed"] | None
ScUntrustedPeerInfo
Section titled “ScUntrustedPeerInfo”Frozen, owned untrusted certificates from one failed outbound TLS attempt.
No accepted connection identity or verification result is implied. Missing evidence does not prove that the peer sent no certificates. Metadata is informational; retaining this value owns no network resources.
Properties:
peer_address: strserver_name: strcertificates: tuple[ScPeerCertificate, ...]
ScPeerInfo
Section titled “ScPeerInfo”Frozen historical observation; does not retain a client or socket.
Properties:
connection_id: intobserved_at_unix: floatpeer_address: strserver_name: strhandshake_kind: Literal["full", "resumed", "unknown"]protocol_version: str | Nonecipher_suite: str | Noneleaf_sha256: bytescertificates: tuple[ScPeerCertificate, ...]
ScEvent
Section titled “ScEvent”One SC hub-connector event (#1829), frozen. Fields that don’t apply to the event’s kind are None.
A failover reads disconnected, then reconnect_attempt and
connect_failed for each failed primary attempt, then
failover_engaged and connected on the failover hub. A primary
restore reads primary_restored, then connected on the primary;
each failed restore probe, at most one per restore interval, reads
primary_restore_failed (#1828).
Properties:
kind: Literal['connected', 'disconnected', 'connect_failed', 'reconnect_attempt', 'failover_engaged', 'primary_restored', 'primary_restore_failed', 'reconnect_gave_up', 'other']hub: Literal["primary", "failover"] | None: The hub connected to, lost, failed or being dialled;primaryforprimary_restore_failed.hub_vmac: bytes | None: The hub’s VMAC from its Connect-Accept, onconnected.cause: Literal['local_close', 'peer_close', 'heartbeat_timeout', 'websocket', 'tls', 'nak', 'dial_timeout', 'connect_accept_timeout', 'upgrade_refused', 'malformed_result', 'unexpected_connect_reply', 'rejection_expired', 'other'] | None: Why adisconnectedlink ended, or aconnect_failedattempt orprimary_restore_failedprobe failed.dial_timeout: the dial (host lookup, TCP, TLS, WebSocket upgrade) ran out of time;connect_accept_timeout: the hub never answered the Connect-Request;upgrade_refused: the server answered the upgrade withhttp_status(#1839).dial_stage: Literal['host_lookup', 'tcp_connect', 'tls', 'websocket_upgrade', 'other'] | None: Where adial_timeoutdial stalled; None when it did not say.http_status: int | None: The HTTP status of anupgrade_refused, such as a proxy’s 502.cause_detail: str | None: Diagnostic text for awebsocket,tlsorothercause; not stable.error_class: ErrorClass | None: The NAK’s error class, for anakcause.error_code: ErrorCode | None: The NAK’s error code, for anakcause.attempt: int | None: Areconnect_attempt’s number, from 1; the attempts made, forreconnect_gave_up.backoff: float | None: Seconds areconnect_attemptwaited first.
ScLinkStatus
Section titled “ScLinkStatus”A frozen snapshot of the SC hub link (#1829).
Properties:
state: Literal["disconnected", "connecting", "connected", "disconnecting"]active_hub: Literal["primary", "failover"] | None: The hub in use or, while reconnecting, being dialled; None before the first attempt.hub_vmac: bytes | None: The connected hub’s VMAC; None while not connected.heartbeat_age: float | None: Seconds since the last message from the hub; None while not connected.heartbeat_rtt: float | None: Round-trip seconds of the latest answered Heartbeat-Request on this connection; None until one is answered.
ScEventIterator
Section titled “ScEventIterator”Async iterator over ScEvent from one connection_events() call.
The connector never waits for it: an iterator more than 64 events behind
loses the oldest and adds them to missed. A cancel that lands while an
event is being delivered, as a timed-out asyncio.wait_for does, puts
the event back: the next __anext__ returns it first. Concurrent
__anext__ calls complete one at a time. Read it from one running event
loop (asyncio.run is fine): an item on its way to a read whose loop
stops for good holds up later reads, which raise one RuntimeWarning
after 5 s and keep waiting. Iteration ends when the client stops.
Properties:
missed: int: Events lost so far: because this iterator fell behind the connector, or dropped on the way to a read, as when its event loop closed first.
ScEventIterator.aiter
Section titled “ScEventIterator.aiter”def __aiter__(self) -> ScEventIteratorScEventIterator.anext
Section titled “ScEventIterator.anext”def __anext__(self) -> Awaitable[ScEvent]_DeviceReadBatchResult
Section titled “_DeviceReadBatchResult”class _DeviceReadBatchResult(TypedDict)
Not importable: the stub defines it only to type what a method returns.
Keys:
request_index: intdevice_instance: intvalue: PropertyValue | Noneerror: BacnetError | None
_DeviceRpmBatchResult
Section titled “_DeviceRpmBatchResult”class _DeviceRpmBatchResult(TypedDict)
Not importable: the stub defines it only to type what a method returns.
Keys:
request_index: intdevice_instance: intresults: list[ReadAccessResult] | Noneerror: BacnetError | None
_DeviceWriteBatchResult
Section titled “_DeviceWriteBatchResult”class _DeviceWriteBatchResult(TypedDict)
Not importable: the stub defines it only to type what a method returns.
Keys:
request_index: intdevice_instance: interror: BacnetError | None