BACnet/IPv6 (B/IPv6, Annex U) carries BACnet over UDP on IPv6. Its broadcasts go to IPv6 multicast groups, and every node has a 3-octet virtual MAC address (VMAC) that the network and application layers use in place of its IPv6 address. This page shows how to start a B/IPv6 node from the CLI, Python and Rust, and how to name its peers.

The page describes v0.15.0.

A B/IPv6 node is addressed by its VMAC, not its IPv6 address (U.1.3). A device’s VMAC is its device instance (H.7.2), so device 1234 is bip6:1234 without any discovery. Any VMAC can be written as bip6:0x0004D2, the form the CLI, the terminal UI and Python print.

When you only know a node’s IPv6 address and port, resolve its VMAC first: the stack asks the node with a unicast Virtual-Address-Resolution (U.5), three times a second apart, and fails after three seconds without an answer. Unicast reaches a node that multicast doesn’t.

A node needs its own VMAC too. Give it a device instance (--device-instance, ipv6_device_instance or the transport’s device_instance) and the VMAC follows from it. Without one the node picks a random VMAC at each start, and first asks the link by multicast whether another node already has it. A link with no multicast, such as Linux loopback, can’t carry that question, so give a device instance there.

With ::, which is the default, startup picks one unambiguous usable link and address: a non-loopback multicast interface first, then a unique non-link-local address on it, otherwise a unique link-local one. Loopback is the last choice, taken only when no other interface qualifies. Several candidates fail startup rather than guessing; give a concrete local IPv6 address instead. Older releases asked the routing table for an address and fell back to ::1 when that failed; that fallback is gone. Loopback, chosen or given, stays on the host. See Select IPv6 explicitly.

Broadcasts go to FF05::BAC0, the site-local group, by default. In Rust, Bip6Transport::set_broadcast_scope selects the link-local (FF02::BAC0) or organization-local (FF08::BAC0) group instead. A group’s scope alone doesn’t prove that the group reaches another link: check what your routers forward.

--ipv6 selects B/IPv6, --ipv6-interface the local address and --device-instance the CLI’s own VMAC. A bracketed address is resolved to a VMAC before the command runs:

Terminal window
bacnet --ipv6 --ipv6-interface 2001:db8::20 --device-instance 4321 read '[2001:db8::10]:47808' dev:1234 object-name

Quote the bracketed target so the shell doesn’t treat it as a pattern. A link-local address carries its interface as a numeric zone, [fe80::1%3]:47809. read bip6:1234 ... names device 1234 by its VMAC; the CLI then finds the device’s address with a multicast Address-Resolution, so that form and discover need a multicast-capable link. A bip6: target without --ipv6 is refused. See Target Resolution in the CLI reference.

In Rust, call register_as_foreign_device with a Bip6ForeignDeviceConfig (the BBMD’s address, its port and a TTL) before start(), or pass one to foreign_device(..) on the B/IPv6 client builder. In Python, give BACnetClient or BACnetServer with transport="ipv6" a foreign_device=ForeignDevice("[2001:db8::10]:47808", ttl=600) (an IPv6 port needs the brackets); the client also needs ipv6_device_instance. The node needs a configured device instance, since a random VMAC is refused in this mode. With ::, it picks the source address it would use to reach the BBMD. The BBMD must be an IPv6 unicast host: an unspecified, multicast, link-local, IPv4-mapped or IPv4-compatible address is refused (ValueError in Python, and start() fails in Rust). A B/IPv6 foreign device renews at half the TTL, but never more often than every 30 seconds, so Python’s renewal= is B/IP only. A registered Network Port reports BACnet_IPv6_Mode FOREIGN and can move the registration to another BBMD, or change its TTL, at a ReinitializeDevice.

The CLI has no B/IPv6 foreign-device option. The stack is never a B/IPv6 BBMD: requests meant for one are refused with a NAK.

Surface B/IPv6 support in v0.15.0
CLI --ipv6 for device commands and the terminal UI (the BBMD commands are B/IP only); VMAC and bracketed targets; no foreign-device mode
Python Client and server with transport="ipv6"; resolve_vmac; add_bip6_network_port; foreign-device mode (foreign_device=); no shared endpoint
Rust Standalone client and server; foreign-device mode; registered Network Port; a shared endpoint composed over a Bip6Transport, with no endpoint builder
BBMD None: the stack doesn’t act as a B/IPv6 BBMD

Linux tests on isolated ULA bridges and macOS loopback tests cover multicast intake and unicast and control replies. Windows has compile evidence only. This is bounded transport evidence, not full Annex U conformance or a qualification of your network.

Release v0.15.0 ·Build and integrate. Pre-1.0 APIs; partial conformance.Support & limitations