Python shared endpoints

One transport that runs both the client and server roles. The Python reference lists every group. Each page opens with its main classes, then the other classes, the dictionaries (TypedDict) and the type aliases, in stub order.

B/IP endpoint: one UDP socket that both initiates and executes.

Two separately constructed objects (BACnetClient + BACnetServer) are two connections (two sockets/ports). The endpoint is the one-transport path: one socket serves both roles.

Admission is lifecycle-lock acquisition, not Future creation. Explicit second start raises BacnetError; context reentry returns this endpoint. Close cancels pending connection preparation, then joins earlier admitted startup and teardown. A later start may restart without old registrations. Cancelled waiters do not abandon admitted session startup or cleanup; cancellation can race publication, so always await close for cleanup. Setup errors are delivered by awaiting start/context entry. BIPv6/Ethernet have no endpoint owner.

Properties:

  • device_instance: int
  • vendor_id: int
def __init__(
self,
device_instance: int,
device_name: str = "BACnet Device",
vendor_id: int = 555,
interface: str = "0.0.0.0",
port: int = 0xBAC0,
broadcast_address: str = "255.255.255.255",
network_number: int = 0,
network_port_instance: int = 1,
max_apdu: int = 1476,
segmentation: Optional[Segmentation] = None,
services: Optional[list[int]] = None,
device_uuid: Optional[Union[bytes, bytearray]] = None,
queue_capacity: int = 16,
apdu_timeout_ms: int = 6000,
apdu_retries: int = 0,
registered_network_port: Optional[int] = None,
*,
read_work_limit: int = 256,
share_port_by_address: bool = False,
min_request_interval_ms: int = 0,
bbmd: Optional[Bbmd] = None,
foreign_device: Optional[ForeignDevice] = None,
multicast: Optional[Multicast] = None,
on_reinitialize: Optional[ReinitializeHandler] = None,
after_reinitialize: Optional[AfterReinitialize] = None,
reinit_password: Optional[str] = None,
device_write_policy: Optional[MutationHandler] = None,
) -> None

on_reinitialize / after_reinitialize: execute ReinitializeDevice, as BACnetServer’s keywords do (#1566); reinit_password (needs on_reinitialize, else ValueError; 1 to 20 characters, else ValueError) is the password a request must carry. The callable runs on the session’s one dispatch task, so a slow one stalls every request. device_write_policy: a callable that decides each WriteProperty to the local Device’s Description or installed Audit recipient (#2033). It gets a MutationContext and returns a bool, with the fail-closed rules of BACnetServer’s mutation_policy callable: an exception, a non-bool or interpreter shutdown denies with SERVICES / SERVICE_REQUEST_DENIED. Without it the endpoint executes no WriteProperty. It runs with no lock held, but on the session’s one dispatch task, so it too should decide quickly: while it runs, other requests and close() wait for it. bbmd / foreign_device (at most one, else ValueError): run the endpoint as a BBMD, or register it as a foreign device (#938). read_work_limit: result rows one ReadProperty served by the server role may expand, a Group’s member rows included; a read past it is aborted with OUT_OF_RESOURCES. Zero raises ValueError. share_port_by_address (default False): bind the interface address itself, so endpoints on other addresses of this host can share the port. Needs an explicit interface and a nonzero port; broadcasts and unicast are still handled in the order they arrived. min_request_interval_ms (default 0, no pacing; at most 3,600,000, else ValueError) paces the client role’s confirmed requests to each destination exactly as BACnetClient’s keyword does (#1542). A retry keeps its request’s turn; replies, notifications and unconfirmed requests aren’t paced.

def add_analog_input(
self,
instance: int,
name: str,
units: EngineeringUnits | int = 62,
present_value: float = 0.0,
) -> None
def add_analog_value(
self,
instance: int,
name: str,
units: EngineeringUnits | int = 62,
*,
audit_level: Literal["default", "none", "audit_config", "audit_all"] | None = None,
auditable_operations: int | None = None,
audit_priority_filter: int | Literal["inherit"] | None = None,
) -> None

Optional AV Audit rows: None is absent; priority ‘inherit’ is present NULL.

def add_binary_input(self, instance: int, name: str) -> None
def add_binary_value(
self,
instance: int,
name: str,
*,
audit_level: Literal["default", "none", "audit_config", "audit_all"] | None = None,
auditable_operations: int | None = None,
audit_priority_filter: int | Literal["inherit"] | None = None,
) -> None

Optional BV Audit rows: None is absent; priority ‘inherit’ is present NULL.

def add_group(
self,
instance: int,
name: str,
members: Optional[list[tuple[ObjectIdentifier, list[tuple[PropertyIdentifier, Optional[int]]]]]] = None,
) -> None

Group whose Present_Value is rebuilt from members on each read.

members has the read_property_multiple spec shape. A member with no properties, or one reporting a group’s Present_Value, raises ValueError naming its position and the rule. Any property identifier is taken, those ASHRAE assigns above 4194303 included. Indexes outside unsigned32 raise OverflowError.

def start(self) -> Awaitable[None]

Admit one startup; second start while running raises BacnetError.

def close(self) -> Awaitable[None]

Join earlier startup and cleanup; idempotent and safe after cancellation.

def __aenter__(self) -> Awaitable[BipEndpoint]
def __aexit__(
self,
_exc_type: Any = None,
_exc_val: Any = None,
_exc_tb: Any = None,
) -> Awaitable[None]
def client(self) -> Awaitable[EndpointClient]

Clone the client role (RuntimeError before start/after close).

def server(self) -> Awaitable[EndpointServer]

Clone the server role (RuntimeError before start/after close).

def local_address(self) -> Awaitable[str]

Active announced IP and actual UDP port; RuntimeError outside active state.

def status(self) -> Awaitable[EndpointStatus]

Bounded snapshot (RuntimeError before start/after close).

def foreign_registration(self) -> Awaitable[ForeignRegistrationStatus]

How the foreign-device registration is going (#938), as for BACnetClient. RuntimeError before start and after close.

def broadcast_i_am(self) -> Awaitable[None]

Broadcast one I-Am consistent with the composed identity.

SC endpoint: one hub connection that both initiates and executes.

sc_device_uuid is the single durable lifetime identity for both the hub dial and DEVICE_UUID. Lifecycle mirrors BipEndpoint.

Properties:

  • device_instance: int
  • vendor_id: int
def __init__(
self,
device_instance: int,
sc_hub: str,
sc_vmac: Union[bytes, bytearray],
sc_ca_cert: str,
sc_client_cert: str,
sc_client_key: str,
*,
sc_device_uuid: Union[bytes, bytearray],
device_name: str = "BACnet Device",
vendor_id: int = 555,
sc_heartbeat_interval_ms: int = 30000,
sc_heartbeat_timeout_ms: int = 60000,
network_number: int = 0,
network_port_instance: int = 2,
max_apdu: int = 1476,
segmentation: Optional[Segmentation] = None,
services: Optional[list[int]] = None,
queue_capacity: int = 16,
read_work_limit: int = 256,
min_request_interval_ms: int = 0,
on_reinitialize: Optional[ReinitializeHandler] = None,
after_reinitialize: Optional[AfterReinitialize] = None,
reinit_password: Optional[str] = None,
device_write_policy: Optional[MutationHandler] = None,
) -> None

read_work_limit, min_request_interval_ms, on_reinitialize, after_reinitialize, reinit_password and device_write_policy are as for BipEndpoint.

def add_analog_input(
self,
instance: int,
name: str,
units: EngineeringUnits | int = 62,
present_value: float = 0.0,
) -> None
def add_analog_value(
self,
instance: int,
name: str,
units: EngineeringUnits | int = 62,
*,
audit_level: Literal["default", "none", "audit_config", "audit_all"] | None = None,
auditable_operations: int | None = None,
audit_priority_filter: int | Literal["inherit"] | None = None,
) -> None

Optional AV Audit rows: None is absent; priority ‘inherit’ is present NULL.

def add_binary_input(self, instance: int, name: str) -> None
def add_binary_value(
self,
instance: int,
name: str,
*,
audit_level: Literal["default", "none", "audit_config", "audit_all"] | None = None,
auditable_operations: int | None = None,
audit_priority_filter: int | Literal["inherit"] | None = None,
) -> None

Optional BV Audit rows: None is absent; priority ‘inherit’ is present NULL.

def add_group(
self,
instance: int,
name: str,
members: Optional[list[tuple[ObjectIdentifier, list[tuple[PropertyIdentifier, Optional[int]]]]]] = None,
) -> None

Group whose Present_Value is rebuilt from members on each read.

members has the read_property_multiple spec shape. A member with no properties, or one reporting a group’s Present_Value, raises ValueError naming its position and the rule. Any property identifier is taken, those ASHRAE assigns above 4194303 included. Indexes outside unsigned32 raise OverflowError.

def start(self) -> Awaitable[None]

Admit one hub connection; second start while running raises BacnetError.

def close(self) -> Awaitable[None]

Join earlier startup and cleanup; idempotent and safe after cancellation.

def __aenter__(self) -> Awaitable[ScEndpoint]
def __aexit__(
self,
_exc_type: Any = None,
_exc_val: Any = None,
_exc_tb: Any = None,
) -> Awaitable[None]
def client(self) -> Awaitable[EndpointClient]

Clone the client role.

def server(self) -> Awaitable[EndpointServer]

Clone the server role.

def local_address(self) -> Awaitable[str]

VMAC hex for this SC node.

def status(self) -> Awaitable[EndpointStatus]

Bounded snapshot (RuntimeError before start/after close).

def broadcast_i_am(self) -> Awaitable[None]

Broadcast one I-Am via the hub relay.

MS/TP endpoint: one serial owner that both initiates and executes.

Opens a real serial device via TokioSerialPort like the current wrappers. Lifecycle mirrors BipEndpoint.

Properties:

  • device_instance: int
  • vendor_id: int
def __init__(
self,
device_instance: int,
serial_port: str,
device_name: str = "BACnet Device",
vendor_id: int = 555,
mstp_baud: int = 38400,
mstp_mac: int = 1,
mstp_max_master: int = 127,
mstp_max_info_frames: int = 1,
max_apdu: int = 480,
segmentation: Optional[Segmentation] = None,
services: Optional[list[int]] = None,
device_uuid: Optional[Union[bytes, bytearray]] = None,
queue_capacity: int = 16,
apdu_timeout_ms: int = 6000,
apdu_retries: int = 0,
*,
read_work_limit: int = 256,
min_request_interval_ms: int = 0,
mstp_extended_frames: bool = False,
mstp_echo: bool = False,
mstp_echo_grace_ms: Optional[int] = None,
mstp_transmit_latency_pad_ms: Optional[int] = None,
mstp_usage_timeout_ms: Optional[int] = None,
mstp_reply_timeout_ms: Optional[int] = None,
on_reinitialize: Optional[ReinitializeHandler] = None,
after_reinitialize: Optional[AfterReinitialize] = None,
reinit_password: Optional[str] = None,
device_write_policy: Optional[MutationHandler] = None,
) -> None

read_work_limit, min_request_interval_ms, on_reinitialize, after_reinitialize, reinit_password and device_write_policy are as for BipEndpoint. Here after_reinitialize runs once the SimpleACK is queued, before the token sends it: stopping the endpoint at once can drop the reply, so wait a short while first.

max_apdu must fit the link: 480 by default, or 1476 with mstp_extended_frames=True, which turns on extended frames (Types 32 and 33, NPDUs of up to 1497 octets) as for BACnetClient. Every node on the link must then take extended frames; each port’s transmit queues reserve 768 KiB instead of 272 KiB.

mstp_echo=True declares an adapter that returns every octet the station sends, and mstp_echo_grace_ms how long after a frame its echo may still arrive (None: 40 ms), as for BACnetClient. A grace of 0, or one given without mstp_echo=True, raises ValueError here; a negative grace, or one above 4294967295, raises OverflowError.

mstp_transmit_latency_pad_ms, mstp_usage_timeout_ms and mstp_reply_timeout_ms are as for BACnetClient, but a value out of range raises ValueError here.

def add_analog_input(
self,
instance: int,
name: str,
units: EngineeringUnits | int = 62,
present_value: float = 0.0,
) -> None
def add_analog_value(
self,
instance: int,
name: str,
units: EngineeringUnits | int = 62,
*,
audit_level: Literal["default", "none", "audit_config", "audit_all"] | None = None,
auditable_operations: int | None = None,
audit_priority_filter: int | Literal["inherit"] | None = None,
) -> None

Optional AV Audit rows: None is absent; priority ‘inherit’ is present NULL.

def add_binary_input(self, instance: int, name: str) -> None
def add_binary_value(
self,
instance: int,
name: str,
*,
audit_level: Literal["default", "none", "audit_config", "audit_all"] | None = None,
auditable_operations: int | None = None,
audit_priority_filter: int | Literal["inherit"] | None = None,
) -> None

Optional BV Audit rows: None is absent; priority ‘inherit’ is present NULL.

def add_group(
self,
instance: int,
name: str,
members: Optional[list[tuple[ObjectIdentifier, list[tuple[PropertyIdentifier, Optional[int]]]]]] = None,
) -> None

Group whose Present_Value is rebuilt from members on each read.

members has the read_property_multiple spec shape. A member with no properties, or one reporting a group’s Present_Value, raises ValueError naming its position and the rule. Any property identifier is taken, those ASHRAE assigns above 4194303 included. Indexes outside unsigned32 raise OverflowError.

def start(self) -> Awaitable[None]

Admit one serial owner; second start while running raises BacnetError.

def close(self) -> Awaitable[None]

Join earlier startup and cleanup; idempotent and safe after cancellation.

def __aenter__(self) -> Awaitable[MstpEndpoint]
def __aexit__(
self,
_exc_type: Any = None,
_exc_val: Any = None,
_exc_tb: Any = None,
) -> Awaitable[None]
def client(self) -> Awaitable[EndpointClient]

Clone the client role.

def server(self) -> Awaitable[EndpointServer]

Clone the server role.

def local_address(self) -> Awaitable[str]

Station MAC as a decimal string.

def status(self) -> Awaitable[EndpointStatus]

Bounded snapshot (RuntimeError before start/after close).

def broadcast_i_am(self) -> Awaitable[None]

Broadcast one I-Am (MS/TP local broadcast).

Client role cloned from a running endpoint (no lifecycle).

Initiates read_property, read_range, read_property_multiple and direct B/IP write_property through the owner’s single transport. After the owner closes, calls fail closed with BacnetError.

def read_property(
self,
address: str,
object_id: ObjectIdentifier,
property_id: PropertyIdentifier,
array_index: Optional[int] = None,
) -> Awaitable[PropertyValue]

Read a property through the shared transport.

ACK object/property/index must match. Device/Network Port instance 4194303 requests accept a same-type concrete ACK. Malformed/mismatched ACKs raise BacnetError; this method returns the property value, not ACK metadata, shaped as PropertyValue describes for read results.

def write_property(
self,
address: str,
object_id: ObjectIdentifier,
property_id: PropertyIdentifier,
value: PropertyValue,
priority: Optional[int] = None,
array_index: Optional[int] = None,
*,
commandability: Literal["commandable", "noncommandable"],
) -> Awaitable[None]

Write to a direct IPv4 B/IP peer through the shared requester.

Commandability is required even without a source Reporter. It controls Audit filtering, never the wire priority. Omitted commandable priority means effective 16, including NULL. Invalid literals, priority, raw TLV framing and APDU size raise ValueError synchronously (out-of-u8 priorities raise OverflowError). Empty encoded lists are valid. Eligible source records preserve complete 0–32-byte values and omit longer values. After source admission, caller cancellation does not cancel the attempt.

def read_property_multiple(
self,
address: str,
specs: list[tuple[ObjectIdentifier, list[tuple[PropertyIdentifier, Optional[int]]]]],
) -> Awaitable[list[ReadAccessResult]]

Read 1–64 explicit property occurrences on concrete objects.

Empty lists, ALL/REQUIRED/OPTIONAL and wildcard instances raise ValueError before address parsing or I/O. Index zero is valid. Complete ordered ACK correlation permits an inline error to omit its requested index; successful values must echo it. Byte limits and malformed/mismatched ACKs raise BacnetError. Returned dictionaries share standalone RPM conversion.

def read_range(
self,
address: str,
object_id: ObjectIdentifier,
property_id: PropertyIdentifier,
array_index: Optional[int] = None,
range_type: Optional[Literal["position", "sequence", "time"]] = None,
reference_index: Optional[int] = None,
reference_seq: Optional[int] = None,
count: Optional[int] = None,
*,
reference_time: ReferenceTime | None = None,
validation: Literal["strict", "lenient"] = "strict",
) -> Awaitable[ReadRangeResult]

Read a range of items from a list or log object.

range_type is "position", "sequence", "time" or None (all-items). "time" reads the count items newer than reference_time (older, for a negative count): a naive datetime.datetime in the device’s local time, or a ((year, month, day, day_of_week), (hour, minute, second, hundredths)) pair; an aware datetime raises ValueError, since the device’s zone isn’t known here (#1533). Invalid selectors, array index zero, missing or zero counts and a time that isn’t specific raise ValueError before I/O; a count outside INTEGER16 (-32768..=32767) raises OverflowError before address parsing or I/O (#1360). Position/sequence reference zero is valid; omitted references default to zero.

validation="strict" refuses an answer that breaks a ReadRange rule with BacnetReadRangeViolationError, whose rule names it; "lenient" keeps it and lists the rules in violations (#1531). Decode a log’s records with decode_log_records.

def read_log_page(
self,
address: str,
object_id: ObjectIdentifier,
cursor: LogCursor = None,
page_size: int = 100,
) -> Awaitable[LogPage]

Read one page of a log’s Log_Buffer from cursor (#1530).

cursor is None or "oldest" (the oldest record, found from Record_Count and Total_Record_Count), ("sequence", n), ("position", n) or ("time", reference_time); lists work too, so a checkpoint survives JSON. Loop on page["next"] until page["done"], then keep next as the checkpoint. One request is outstanding at a time. A first record past the one asked for sets gap; when the log drops the record asked for, the read starts over from the oldest. A page answered from before the one asked for, or none where the counts say records are, raises BacnetLogNotAdvancingError: such a device’s sequence numbers are inconsistent, so read it from ("position", 1). wrapped marks a page that reached the top of the sequence range. A page whose records don’t decode raises BacnetError, dropping the records before the failing one; an answer that breaks a rule the reader can’t tolerate, such as an echo that doesn’t match, raises BacnetReadRangeViolationError. A non-log object or a page_size outside 1..=32767 raises ValueError before I/O.

def service_scope(self) -> dict[str, Any]

Narrow scope: initiates reads and direct B/IP write_property.

Server role cloned from a running endpoint (no lifecycle).

The responder executes read_property automatically, WriteProperty to the local Device through the owner’s device_write_policy, and ReinitializeDevice through the owner’s on_reinitialize, the one Python callback that runs under a native lock; this handle exposes liveness plus the MS/TP deferred-reply seam.

def is_session_alive(self) -> bool

True while the owning endpoint is alive and open.

def suspend_next_reply(self) -> None

Arm one-shot deferred-reply suspension (MS/TP wiring).

def service_scope(self) -> dict[str, Any]

Narrow scope: executes read_property, plus write_property when the owner has device_write_policy and reinitialize_device when it has on_reinitialize.

class EndpointStatus(TypedDict)

Bounded endpoint snapshot: liveness, identity, transport, leases, policy counts.

Keys:

  • is_running: bool
  • device_instance: int
  • vendor_id: int
  • max_apdu: int
  • transport: str
  • local_address: str
  • active_leases: int
  • ingress_policy: int
  • no_server_role: int
  • no_client_role: int
  • unclaimed_terminal: int
  • responder_declined: int

class ReadRangeResult(TypedDict)

Keys:

  • object_id: ObjectIdentifier
  • property_id: PropertyIdentifier
  • array_index: int | None
  • result_flags: BitString
  • item_count: int
  • item_data: bytes
  • first_sequence_number: int | None
  • violations: list[str]

class LogGap(TypedDict)

A page whose first record isn’t the one asked for.

Keys:

  • expected: int
  • first: int
  • skipped: int | None

class LogPage(TypedDict)

One page of read_log_page.

records are dicts, oldest first, as decode_log_records returns them. next is never None or "oldest".

Keys:

  • records: list[dict[str, Any]]
  • first_sequence_number: int | None
  • result_flags: BitString
  • gap: LogGap | None
  • violations: list[str]
  • next: LogCursor
  • done: bool
  • wrapped: bool

class ReadPropertyResult(TypedDict)

Keys:

  • property_id: PropertyIdentifier
  • array_index: int | None
  • value: PropertyValue | bytes | None
  • error: tuple[ErrorClass, ErrorCode] | None

class ReadAccessResult(TypedDict)

Keys:

  • object_id: ObjectIdentifier
  • results: list[ReadPropertyResult]
ReferenceTime = Union[
datetime.datetime,
tuple[tuple[int, int, int, int], tuple[int, int, int, int]],
]
LogCursor = Union[
None,
Literal["oldest"],
tuple[Literal["sequence"], int],
tuple[Literal["position"], int],
tuple[Literal["time"], ReferenceTime],
]