Python module functions

Functions at the top of the rusty_bacnet module. The Python reference lists every group. Each page opens with its main classes, then the other classes, the dictionaries (TypedDict) and the type aliases, in stub order.

def enum_name(property: PropertyIdentifier, value: int) -> str | None

The name of enumerated value as read from property (enum_name(PropertyIdentifier.EVENT_STATE, 3) == "HIGH_LIMIT"), or None when the property’s enumeration isn’t known from the property alone (Present_Value, vendor properties) or the number has no name in it.

def decode_log_records(result: ReadRangeResult) -> list[dict[str, Any]]

Decode the records of a read_range result of a log’s Log_Buffer (#1534).

Each record is a dict with timestamp as a (date, time) pair and datum, a dict whose kind names the choice and whose key of the same name holds its value: log_status (a BitString naming LOG_DISABLED, BUFFER_PURGED, LOG_INTERRUPTED), boolean, real, enumerated, unsigned, signed, bitstring (a BitString of no known type), null (no value), failure ((ErrorClass, ErrorCode) members), time_change (seconds), any (the value’s encoding), values (a Trend Log Multiple record’s list of such dicts), notification (an Event Log record’s event notification, its event_values None or a dict whose kind names the event type in snake case, out_of_range, with each value under its member’s name; see docs/python-api.md) or audit_notification (an Audit Log record, as audit_log_query shows it). A Trend Log record adds status_flags (a BitString naming IN_ALARM, FAULT, OVERRIDDEN, OUT_OF_SERVICE), or None.

Raises ValueError for a result that isn’t a log’s Log_Buffer, or whose item data doesn’t decode as item_count records, naming the first record that fails by index and offset.

def list_serial_ports() -> list[str]

List the serial ports the operating system reports, as names to pass as serial_port= for transport="mstp" (/dev/ttyUSB0, /dev/cu.usbserial-1410, COM3).

macOS lists them through IOKit, Windows through SetupAPI and the registry, and Linux from sysfs, so a port another program has open is listed too. An empty list means the system reports none. Raises OSError (or the subclass for the failure’s kind) if the operating system can’t be asked.

def refresh_logging() -> None

Read the logging levels again, so that a level lowered since the last read forwards the stack’s events it now allows.

The stack’s log events go to the logger rusty_bacnet.<module path>, rusty_bacnet.bacnet_transport.bip for bacnet_transport::bip; only the crate-level names (rusty_bacnet.bacnet_transport and so on) are stable. TRACE goes out at level 5, which importing rusty_bacnet names TRACE. The package logger has a NullHandler, so nothing prints until the application configures logging.

The bridge decides which events to forward from a copy of the levels, taken at import, whenever a client, server, hub or endpoint starts, and by this function, so a disabled level never takes the GIL. Raised levels filter at delivery as well.

Records arrive from one background thread, in order, shortly after the event, and carry the event’s fields as record.bacnet_fields. Past 4,096 waiting records, newer ones are dropped and a warning on rusty_bacnet counts them. At exit, records already queued are delivered first (waiting up to two seconds).

def inspect_sc_pem(
identity_pem: bytes | bytearray,
*,
peer_trust_pem: bytes | bytearray | None = None,
private_key_pem: bytes | bytearray | None = None,
inspected_at_unix: int | None = None,
) -> ScPemInspection

Inspect bounded PEM bytes synchronously. Time is a signed 64-bit integer second.

ValueError: malformed/empty/oversized supplied PEM. TypeError: wrong input type, including bool time. OverflowError: time outside the signed 64-bit range. DER defects and key/date observations are returned in the report.

def inspect_sc_pem_files(
identity_path: str | os.PathLike[str],
*,
peer_trust_path: str | os.PathLike[str] | None = None,
private_key_path: str | os.PathLike[str] | None = None,
inspected_at_unix: int | None = None,
) -> ScPemInspection

Read selected files once and inspect them without network I/O; OSError retains errno.

None time samples the clock once. A later connection may read changed files. Same interpretation and input limits as inspect_sc_pem; no chmod or startup gate.