Configure BACnet/SC
BACnet/SC setup combines a WebSocket/TLS connection with BACnet-specific identities and hub behavior. A successful TCP or TLS connection alone does not establish a complete BACnet/SC deployment.
Before connecting
Section titled “Before connecting”Obtain the hub URL, your node’s certificate and private key, the trust arrangement for the hub’s certificate chain, and an allocated VMAC and device UUID where the interface requires them. Ensure the certificate identity matches the hub name you are using and that the system clock is appropriate for certificate validation.
Keep private keys outside the repository and the generated site. Example names below are not deployable credentials.
CLI feature and identity setup
Section titled “CLI feature and identity setup”From the v0.11.0 source checkout, build a CLI with the sc-tls feature:
cargo install --path crates/bacnet-cli --locked --features sc-tlsThe reviewed CLI requires a hub URL, client certificate, private key, local VMAC, and nonzero local device UUID:
bacnet --sc \ --sc-url wss://hub.example.com/bacnet \ --sc-cert node-cert.pem \ --sc-key node-key.pem \ --sc-vmac 22:01:02:03:04:05 \ --sc-device-uuid 00112233-4455-6677-8899-aabbccddeeff \ read 00:01:02:03:04:05 ai:1 pvReplace every identity and path with an approved value for your network. The final VMAC is the remote target; --sc-vmac is the local node identity. Do not reuse the example VMAC or UUID throughout a deployment.
The CLI trust store is not the Python trust argument
Section titled “The CLI trust store is not the Python trust argument”The v0.11.0 CLI constructs its trust store from native root certificates. Its reviewed parser does not offer a --sc-ca-cert flag. A private hub CA therefore needs an appropriate trust path on the actual execution host, following site policy, or a different supported application configuration.
Do not “fix” certificate failures by disabling certificate validation. A client certificate supplied through --sc-cert is not the same thing as trusting the issuer of the hub’s certificate.
Python trust configuration
Section titled “Python trust configuration”The Python client exposes sc_ca_cert, sc_client_cert, and sc_client_key. The hub exposes ca_cert for trusted node issuers. These are different roles: a node trusts the hub’s issuer, and the hub validates connecting node identities using its configured trust.
The v0.11.0 repository distinguishes a hub configured with a trusted issuer CA from an example that omits ca_cert. The latter is server-auth-only example mode, not claimed BACnet/SC mutual-TLS conformance evidence. Do not use server-auth-only example mode for deployment. Configure trusted node issuers and operational credentials; current dev has removed this example mode.
Use the versioned Python API and secure-connect example for release constructor details rather than translating CLI flags mechanically into Python names.
Validate the whole path
Section titled “Validate the whole path”Check the package/build feature, hub URL and port, certificate chain and validity, hostname, local VMAC/UUID, hub acceptance, and remote target identity. After joining the hub, perform a bounded read against a known object. Record sanitized failure stages; never attach a private key to an issue.
These instructions explain configuration boundaries. They are not a certificate-authority operating procedure or a BACnet/SC certification claim.
Sources and release scope
Section titled “Sources and release scope”These instructions target v0.11.0. Source review is not a claim of hardware qualification.
CLI SC construction and native roots · CLI flags · Python trust and hub guide · SC example.
Release v0.11.0 ·Current development. Follow the scope named on each page. Pre-1.0 APIs; partial conformance.Support & limitations