Compose a shared endpoint
Current development / Shared endpoints
Unreleased source APIs. Use an endpoint when one local device needs to initiate requests and serve a bounded request set through the same transport. Keep standalone BACnetClient for a requester or BACnetServer for the full server service set; both remain public APIs.
One session owns the connection
Section titled “One session owns the connection”Rust’s EndpointSession owns transport startup, ingress and shared outbound coordination. Choose ClientOnly, ServerOnly or Both before startup. The role handles use that owner and cannot independently restart its transport.
This B/IP example binds an ephemeral loopback port, creates both roles, then explicitly stops the owner. It does not discover or write to another device:
use std::net::Ipv4Addr;use bacnet_endpoint::{bip::BipEndpointBuilder, DeviceIdentity, SessionRole};
async fn example() -> Result<(), bacnet_types::error::Error> { let identity = DeviceIdentity::new(1001, 42)? .with_bip_port(1, 0, Ipv4Addr::LOCALHOST, 0)?; let db = identity.build_database()?; let mut session = BipEndpointBuilder::new( Ipv4Addr::LOCALHOST, 0, Ipv4Addr::BROADCAST, ) .role(SessionRole::Both) .database(db) .identity(identity) .build_session()?; session.start().await?; let local = session.bip_local_address(); println!("Bound endpoint: {local:?}"); session.stop().await?; Ok(())}The declared Network Port above is not automatically registered. Explicit registration is a separate receiving-port contract. A successful start exposes the actual B/IP address, including the ephemeral port; after stop it is unavailable.
For SC, ScEndpointBuilder composes a caller-dialed TlsWebSocket with build_hub_session under the sc-tls feature. For MS/TP, MstpEndpointBuilder owns one serial link. Python exposes BipEndpoint, ScEndpoint and MstpEndpoint, with async with endpoint, await endpoint.client() and await endpoint.server(). B/IPv6 and Ethernet have no shared endpoint builder; use their standalone owners.
Check requester and responder scope separately
Section titled “Check requester and responder scope separately”| Role | Current bounded contract |
|---|---|
| Requester reads | ReadProperty, ReadRange and ReadPropertyMultiple; unsegmented requests/responses |
| Requester RPM | 1–64 explicit property occurrences; concrete objects; no ALL, REQUIRED, OPTIONAL or wildcard object selectors |
| Requester writes | Direct IPv4 B/IP WriteProperty only; required commandability declaration; no routed WP or WPM in this profile |
| Default responder | ReadProperty, with Reject/Abort handling; no responder RPM, COV or full-server parity |
| Opt-in responder writes | One built-in local Device’s Description and, with a complete source profile, Audit_Notification_Recipient; mandatory mutation authorizer |
The Device’s advertised services must match the responder. Server-role declarations include RP and cannot add unsupported services; explicit write opt-in advertises RP+WP only after validation. The endpoint responder does not expose Device COV list properties.
A requester write’s commandability is a declaration about the remote property, not permission to write it. Rust requires Commandability::{Commandable, Noncommandable}; Python requires commandability="commandable" or "noncommandable". For a first integration, exercise reads before enabling mutations. Consult request admission limits for the shared budgets.
Add source READ or WRITE Audit reporting deliberately
Section titled “Add source READ or WRITE Audit reporting deliberately”The optional Rust source Reporter profile belongs to this session and currently covers direct IPv4 B/IP. Configure it before startup:
- Put exactly one concrete built-in Device and the selected Audit Reporter in the database.
- Provision the Device’s typed Audit recipient. A Device recipient needs an immutable
source_audit_device_binding; a direct Address recipient needs none. - Set the Reporter’s audit level and READ/WRITE operation policy.
Monitored_Objectsmust be absent, including no empty or NULL-only list. - Select
with_source_audit_reporter. ABothsession also requires an explicit Device write authorizer.
The canonical source Reporter example supplies the exact setup. Python exposes endpoint requests but no source Reporter configuration.
READ reporting covers RP, ReadRange and RPM. Records retain attempted identities and outcomes; returned values remain caller-only. An RPM operation can produce a separate record for each eligible occurrence. WRITE reporting records eligible attempts across retries, with a complete Target_Value only when its encoding fits 0–32 bytes. It never invents remote Current_Value, target timestamp or proof that a write executed. Notification delivery failure does not replace the request’s result.
This source profile is separate from the full server’s target Reporter ownership, Device recipient and Audit Log forwarding contracts.
Close the owner, including after cancellation
Section titled “Close the owner, including after cancellation”In Rust, await session.stop(); in Python, await close() or leave the async context. Exported role handles do not keep a closed session usable. Stop owns admitted work and transport cleanup; dropping a caller’s request is not a substitute for stopping the endpoint.
Eligible source-reported requests retain terminal observation after caller cancellation. Other caller-owned requests can cancel queued sends, but an already attempted send may have reached its peer. Cancellation never proves that a remote write did not execute.
Python startup and close serialize through the native lifecycle owner. If startup cancellation races publication, explicitly await close. A canceled admitted close waiter leaves cleanup owned; another awaited close joins it. Successful start consumes registrations, so restart does not replay them. See the full lifecycle contract for startup rollback boundaries.
Next steps
Section titled “Next steps”Register a NORMAL B/IP receiving port · Compare transport evidence · Exact Rust endpoint APIs
Release v0.11.0 ·Current development. Follow the scope named on each page. Pre-1.0 APIs; partial conformance.Support & limitations