Choose a transport and evidence scope
Current development / Transport evidence
Current source, not a v0.11 support promise. Select the application owner, binding and data link separately. This is a navigation map to scoped evidence, not a second conformance database or an all-platform support badge.
Match the link to an owner
Section titled “Match the link to an owner”| Data link | Current entry points | Setup and important boundary |
|---|---|---|
| B/IP, NORMAL | Rust/Python standalone client and server; shared endpoint | Explicit local IPv4 interface and UDP port; selected Network Port registration is a separate opt-in |
| B/IP, BBMD or foreign | Rust transport configuration; bounded endpoint composition | BDT/FDT or configured BBMD; shared-endpoint Number evidence does not qualify every administrative operation |
| B/IPv6 | Standalone Rust/Python client and server; Rust configured foreign-device mode | Select one usable interface/address; no shared endpoint builder or Python foreign-device entry point |
| BACnet/SC | Rust/Python standalone owners and shared endpoint | Operational credentials, explicit CA and durable UUID/VMAC configuration; Rust TLS paths require sc-tls |
| MS/TP | Rust transport/server/endpoint; Python standalone and endpoint paths | Serial adapter, station, baud and token participation; do not infer physical timing from simulation |
| Ethernet | Linux Rust standalone client and server | AF_PACKET raw socket permissions; no shared endpoint builder or Python Ethernet API |
The CLI has its own configuration surface. A Rust transport does not imply a matching CLI command or Python constructor. For exact feature gates, use the crate manifests and Rust API; do not enable every feature merely to discover which one you need.
Read the Number-control evidence at its actual scope
Section titled “Read the Number-control evidence at its actual scope”| Evidence | Exercised behavior | Limit |
|---|---|---|
| B/IP loopback | Server/endpoint NORMAL controls; independent standalone-client NORMAL/BBMD/foreign replies; full-server and shared-endpoint BBMD Original-Broadcast and foreign DBTN captures | Linux supplies BBMD broadcast observation; no physical-LAN qualification |
| Constrained local SC TLS | Full server/shared endpoint and standalone client Number bytes and Hub broadcast VMAC; direct query replies use Hub broadcast | Generic controlled tests separately prove queued/pending cancellation; TLS trust does not authenticate a relayed NPDU origin |
| MS/TP LoopbackSerial | Full server/shared endpoint standard frames, token opportunity, mode parity and producer cancellation | Simulator evidence, not RS-485 timing, transceiver control or hardware interoperability |
| Isolated Linux Ethernet | Full server/standalone client MAC, LLC, length, payload and padding; raw-FD stop/drop and canceled-stop ownership | Opt-in virtual-link fixture needs raw-socket capability; excluded from ordinary CI |
| Isolated Linux B/IPv6 | Full server/standalone Rust client selected-link OriginalBroadcast and configured-foreign DBTN; independent bytes/address/interface; normal installed-Python evidence | Explicit external ignored tests; no physical LAN, IPv6 endpoint builder or full Annex U claim |
Standalone-client BBMD/foreign cases retain BDT/FDT admission, alternate-sender compatibility and registration NAK/retry behavior, and prove requester progress plus awaited-stop socket release. Independent standalone-client MS/TP frame qualification remains under #879. Other implemented opt-ins are not automatically independently qualified by this table. The authoritative row is BACNET-06-NONROUTER-NETWORK-NUMBER in the machine-readable conformance ledger. Its notes distinguish positive wire observations, FIFO refusal fences, controlled lifecycle tests and retained limitations.
Select IPv6 explicitly when discovery is ambiguous
Section titled “Select IPv6 explicitly when discovery is ambiguous”Current normal IPv6 startup chooses one unambiguous usable local link/address. A non-loopback multicast interface and a unique non-link-local address are preferred. If selection is ambiguous, supply a concrete local IPv6 address rather than assuming :: means all interfaces. There is no silent physical-selection fallback to ::1.
Incoming destination and interface checks run before VMAC learning/application delivery; outgoing data and controls keep the selected source and bound port. Explicit loopback remains node-local. Windows has compile evidence for the described selection path, not the isolated Linux runtime qualification. See the Python IPv6 contract before migrating a wildcard-bound release application.
Plan your own validation
Section titled “Plan your own validation”Record the source revision, interface, feature set, OS and native artifact. Start with a known peer and bounded read. Add registration, discovery, subscriptions or writes only when the intended operation needs them. Preserve the distinction between a successful build, a loopback test, simulated serial frames, an actual isolated wire capture and a hardware deployment test.
Support and conformance explains the ledger’s role. MS/TP qualification covers the separate hardware path. No page here claims BTL certification.
Next steps
Section titled “Next steps”Compose a shared endpoint · Configure current SC · Use passive Number controls
Release v0.11.0 ·Current development. Follow the scope named on each page. Pre-1.0 APIs; partial conformance.Support & limitations