Benchmark results

Muse Spark rebuilds open-control-library’s 137 fault-detection rules from scrubbed prose tasks (no block class names, no block ids, no other rule ids), and each draft is scored by replaying the library’s 1,760 test vectors through the pinned engine. Before scoring, all 1,760 scenarios were replayed with the reference rules and all pass.

Run of 2026-10-27: muse-spark-1.3-contributor (the library is public), medium effort, up to 3 attempts, validator-only repair feedback (no vector results reach the model), zero-shot, tier A (prose only), 3 runs, engine fa5cb19.

Run First try (of 137) After repair (of 137) Scenarios passed (of 1,760)
2026-10-26, engine 4063202, before the loop rule 125, 121, 124 131, 132, 133 1,750, 1,744, 1,749
2026-10-27, engine fa5cb19, with the loop rule 122, 125, 124 132, 130, 131 1,747, 1,737, 1,743

Baselines: a constant-false graph passes 0 rules and 720 of 1,760 scenarios; constant-true passes 0 rules and 30 scenarios. The run-to-run spread (3 to 4 rules) is as large as the difference between the two batches.

Where it fails (2026-10-27 run, rule-runs):

Group Rule-runs First try After repair
Statistical rules (CUSUM, baselines, rolling statistics) 69 71% 87%
Plain threshold/timing rules 339 94% 97%
17+ blocks 24 75% 75%
10-16 blocks 90 74% 91%
5-9 blocks 222 95% 98%
4 or fewer blocks 75 100% 100%
Rules using Discrete.Sampler 21 48% 71%

Typical misses are statistical baselines, evaluation gating and sampled signals.

Runs of 2026-10-26 on engine 4063202; re-checked on fa5cb19 with every verdict unchanged.

Subset Tier Rules First try After repair Scenarios (best attempt) Constant-false
test_clean A 37 33, 32, 32 35, 35, 36 475, 475, 477 of 478 0 rules; 204 of 478
test_clean B 29 29, 29, 29 29, 29, 29 381 of 381 0 rules; 157 of 381

Tier B adds the card’s pseudo-code, which is close to a direct specification, and skips 8 rules whose pseudo-code names a block class or id; it is not comparable with tier A. The held-out set is small (37 rules, only one over 16 blocks), which is why the whole-library run leads this page.

Unpublished specs, muse-spark-1.3 (standard tier), repair feedback that names failing scenarios. A pass after that kind of repair is “repaired against the scoring vectors”, not a blind score.

Spec Setup First try After repair Constant baselines
Chilled-water plant reset, v2 task high effort, up to 5 attempts, 3 runs (2026-10-27) 0 of 3 2 of 3 0 of 10 scenarios
Chilled-water plant reset, live sessions with the loop rule high effort, up to 5 attempts, 3 sessions (2026-10-27) 3 of 3; 0 of 9 drafts looped
Air handler chilled-water requests medium effort, 3 runs (2026-10-26) 3 of 3 3 of 3 1 of 15 scenarios
Zone static pressure requests, v2 high effort, up to 5 attempts, 3 runs (2026-10-27) 0 of 3 3 of 3 1 of 9 scenarios
Duct static pressure reset high effort, up to 5 attempts, 3 runs (2026-10-27) 3 of 3 3 of 3 0 of 6 scenarios
Home price response high effort, up to 5 attempts, 3 runs (2026-10-28) 3 of 3 3 of 3 0 of 17 scenarios
  • The plant reset is the hard one. Most first drafts had an algebraic loop until the repair message named the loop as a block chain and the prompt named the two classes that break one. With validator-only feedback (no vector results), only 1 of 12 runs produced a passing graph.
  • The air handler requests and home price response are easy specs for the model: their tasks state every edge or formula.