BACnet mirror
mm-bacnet serves live runs as one BACnet/IP device. It uses rusty-bacnet (pre-existing,
pinned, used unmodified) for the protocol; the point map, the updates and the wiring are ours.
What it serves
Section titled “What it serves”Device 599, name MECHANICAL-MUSE, 55 objects:
| Points | Object type | Example names |
|---|---|---|
| 24 BOPTEST readings (plant and air handler values, duct static pressures, supply fan power) | Analog Input | reaChiWatSys_TCHWSup_y, floor2_reaAHU_PFanSup_y |
| 26 sequence outputs | Analog Value, read-only | chw.TSupSet, zone2eas.yPreReq, sp1.dpSet |
| 5 setpoints the runtime sent | Analog Value, read-only | oveChiWatSys_TWSet_u, floor1_dpSet_u |
- Instance numbers derive from the sorted names, so the same specs always give the same objects.
- Values are
f64in the engine andf32in BACnet, converted in exactly one place. - A point with nothing to report (before a run, after it, a setpoint handed back to BOPTEST, a
blank test fault) reads reliability
NO_SENSOR. - Only live runs update it; replays of recorded runs do not.
What it refuses
Section titled “What it refuses”Every request that would change an object is refused: property writes, object creation and deletion, list changes, and COV subscriptions (so peers poll). A peer sees the sequences’ decisions; it cannot change them. Tests send writes over UDP with rusty-bacnet’s own client and fail if the policy is ever switched back to permissive. No conformance or certification is claimed.
Run it
Section titled “Run it”MM_BOPTEST_URL=http://127.0.0.1:80 MM_BACNET_ADDR=0.0.0.0:47808 make serverAny BACnet/IP client on the same network can discover device 599 (Who-Is) and read it. BACnet/IP relies on UDP broadcast, which Docker’s default network does not carry to the LAN, so run the server natively for the mirror.