CHW Fault Rules

Chilled-water plant fault detection rules (CHW-*). CHW-0001..0006 originate in HVAC FDD Reference v1.0 ch.13 or close its cited approach-rule gaps. CHW-0007..0009 are library-authored control/protection extensions grounded in public plant guidance and verified graph precedents. The family now separates efficiency and reset performance from per-machine tracking, proof, and cycling.

Point dictionary: points/chw.points.json. Supplementary deep-read sources (paraphrase-and-cite only, per the licensing rule): G36 cooling-plant AFDD document, ASHRAE RP-1043 chiller FDD review, and the chiller-plant entries in the project’s internal research triage (licensed sources; not distributed).

Index

IDNameSevMethodStatus
CHW-0001Chiller efficiency (kW/ton) degradation3statisticalverified
CHW-0002CHWST reset not functioning3statisticalverified
CHW-0003CHW loop DP reset not functioning3statisticalverified
CHW-0004Chilled water low delta-T syndrome3ruleverified
CHW-0005Chiller condenser approach high3ruleverified
CHW-0006Chiller evaporator approach high3ruleverified
CHW-0007Chilled-water supply temperature tracking failure3ruleverified
CHW-0008Chiller proof-of-operation failure2ruleverified
CHW-0009Chiller short-cycling2ruleverified

Severity and method per the reference’s ch.13 cards. CHW-0005/CHW-0006 are the approach pair resolving the reference’s dangling CHW-FC-008/009 playbook citations (mentioned there, never defined): condenser side and evaporator side of the same verify step, tube-side discriminators for CHW-0001.

Relationships

  • CHW-0002/CHW-0003 are the plant-side siblings of AHU-0023/AHU-0024 (SAT/DSP reset) — same detector shape (setpoint range flat over a window while the load moves), same RetuningOpps lineage, and the same CLU-02-style “reset never programmed” root cause one system further upstream.
  • CHW-0004 (low delta-T) is the plant-level symptom of coil-side defects the library already detects locally: fouled/leaking coil valves (FCU-0004, AHU-0014), three-way bypass, dirty filters — tied together by cluster CLU-06 (trigger CHW-0001).
  • CHW-0001’s baseline follows the HP-0001 host-fitted pattern — the reference specifies a Ridge regression over load/CWST/CHWST; the graph carries the fitted coefficients as set_param placeholders.
  • CHW-0007 complements CHW-0001/0005/0006: tracking direction is useful evidence during an approach or efficiency finding, so none suppresses it.
  • CHW-0008 stays relationship-only. Its fail-to-start direction makes tracking non-evaluable, but its unexpected-run direction can still be loaded and meaningfully fail tracking. Current metadata cannot encode only one lane.
  • CHW-0009 and CHW-0007 are related because low-load overshoot can produce cycling, but neither implies the other and no graph state is shared.

Per-machine binding boundaries

PointCHW-0007CHW-0008CHW-0009Plant/loop use
chiller_cmdFinal command for this machinePlant enable or cooling demand is invalid
chiller_statusThis machineThis machine, independent proofThis machineA fleet OR hides lag-machine starts
chiller_loadThis machineA documented plant maximum remains valid only for plant-level gates such as CHW-0004
chwst / chwst_spSame controllable leaving-water targetCommon header is conditional, not automatically per-machine

On parallel plants, prefer each chiller’s evaporator outlet plus the final active target delivered to its controller. A mixed-header measurement/setpoint may be used for CHW-0007 only when the deployment proves the staged machine(s) actually control that same point. An OR of statuses or maximum of loads is not a weaker per-machine proxy; it changes the question.

Ontology and cluster decision

The PR 04 point additions pin ASHRAE 223 to the inspected public-review artifact 1.0.0-ppr.2.1 (SHA-256 1f156f9938c0be430d2216e01e31bb183c438ba318d8d4a23d2f074ebcd6f573), replacing the former unverified v1.0.0-2026 label. The migration also replaces legacy Water/Refrigerant and free-text aspect shorthands with artifact-defined local names such as Water-ChilledWater, Fluid-Water, Constituent-Refrigerant, and Aspect-Setpoint. Brick 1.4.4 provides exact generic Start_Stop_Command and Run_Status classes on a Chiller.

CLU-06 is not broadened. Tracking, proof, and cycling improve diagnosis but do not share one trigger/fix with the existing efficiency-reset-approach cluster.