SYS-0005 — Sensor drift via cross-validation (paired sensors)
| Status | verified — engine e2ff2f8, cxf:fnv1a128:0f6dd4de2df9cd68164f18828e25c4b9, 2026-08-17 |
| Severity | 3 |
| Method | rule |
| Phase | 2 |
| Category | COMFORT_ENERGY |
| Confidence | LOW |
| Estimation | QUALITATIVE_ONLY |
| G36 | — |
| Clusters | CLU-09 |
| Suppresses | — |
| Suppressed by | — |
| Related | SYS-0006, SYS-0009, SYS-0010, AHU-0028, RTU-0003 |
| Playbooks | sensor-drift |
| Source | HVAC FDD Reference v1.0 §16, SYS-0005 (pdf pp. 142-144) — equation, both delays, drift_threshold 2°C / 5%, the four diagnoses, and the whole impact profile; The reference’s own provenance line for that card: PNNL-27338 §3; G36 sensor calibration checks; Yang, H., Cho, S., Tae, C.-S., Zaheeruddin, M. (2008). Sequential rule based algorithms for temperature sensor fault detection in air handling units. Energy Conversion and Management 49(8), 2291-2306. doi:10.1016/j.enconman.2008.01.029 — the published grounding for pairwise sensor comparison, and the source of this card’s honesty about isolation; Accepted design: internal sensor-health design note (local-only, not distributed) (§2 stance, §3 ID scheme, §4.4 pair-bias vector strategy, §5 usable pairs); Library precedent: AHU-0028 and RTU-0003 (physical-plausibility rules that already ship), VFD-0001 (two published delays chained), VAV-0001 (per-binding placeholder parameter) |
| Operating states | all, within the binding’s own validity window — the two sensors must be measuring the same physical quantity at the moment of comparison, which for a stream-mixing pair is true only in particular damper or mode states (host-enforced; see preconditions) |
Preconditions (host-enforced): sensor_value_a and sensor_value_b are ROLE points, not canonical names: the host’s instance configuration records which real point each is bound to, and that record is also what resolves this card’s adjudicates target. Both must be bound to the same quantity kind in the same units — the rule subtracts two numbers and converts nothing, so a pair trended in °C against °F reads as a permanent 30-unit divergence and alarms forever. drift_threshold ships as a temperature placeholder and MUST be retuned to the binding (see Deviations); a percent-quantity pair left at the shipped 2.0 gets a band the reference never intended. The pair must genuinely see the same quantity during evaluation, which is a per-binding claim the graph cannot check: erv_oa_entering_temp against oat holds whenever both are in the outdoor air stream, but mat against rat holds only with the outdoor air damper shut and mat against oat only at full economizer, so the host must gate those bindings on damper position and exclude the minutes after a changeover exactly as AHU-0028 does. Delivery quality is resolved before this rule runs, not by it: a value the host held over from twenty minutes ago reads as a divergence, and the rule is right about the number it was given and wrong about the sensor. Per the design doc’s normative constraint, no other card may list SYS-0005 in its suppresses — an equipment fault silencing the sensor rule that invalidates it is a cycle with a wrong answer at both ends.
Points: sensor_value_a, sensor_value_b
Outputs:
yFault— True while the two bound sensors have stayed more than drift_threshold apart, in the bound points’ units, continuously for drift_duration plus alarm_delay. Which member drifted is not determined — see adjudicates.verdict
Parameters:
| Name | Default | Unit | CXF path | Description |
|---|---|---|---|---|
drift_threshold | 2.0 | varies (the bound points’ own units) | driftHigh.t | Maximum divergence the pair’s combined accuracy explains. PER-BINDING SITE CONFIGURATION — the reference’s default is 2°C / 5%, one number per quantity kind, and a single CXF literal cannot be both. The shipped 2.0 is the temperature half; a percent-quantity binding (relative humidity, damper position, valve position) takes 5.0, and any other quantity takes a number nobody has published. Retune at binding. |
drift_duration | 3600.0 | s | sustained.delayTime | Continuous divergence required before it counts as drift rather than one sensor lagging the other through a transient (60 min). The reference’s own drift_duration. |
alarm_delay | 1800.0 | s | persist.delayTime | Further persistence required after drift_duration before the alarm asserts (30 min). The reference’s own separate AlarmDelay; 90 min to alarm at the shipped defaults. |
Description
Two sensors that should be reading the same number are not. A single transmitter has nothing to be checked against and every rule that reads one believes it; put a second in the same air stream, or take a pair the physics already constrains, and the disagreement is evidence no single-sensor rule can produce. The failure it catches is drift — slow, monotone, never still enough for a flatline test and never fast enough for a spike test, which is why it survives for years and why the reference puts its prevalence at 15%. What it costs is rarely its own energy: a biased outdoor-air sensor disables an economizer, a biased supply-air sensor drags a reset schedule with it, and what shows up on the report is some other rule firing for a reason that is not true.
The adjudicates contract. While yFault is active, both bound points are
unfit to be believed: the host must return NO_EVAL for every rule on the same
equipment instance that consumes either one, deriving that set from each card’s
points list rather than from any list written here. The verdict is ambiguous
because |a − b| says the pair disagrees and cannot say which member is wrong.
adjudicates is card metadata; the block graph is unchanged and the engine
never sees it.
That an in-graph rule may judge data at all is the accepted design’s argument: “data quality is the host’s” is about delivery — did a sample arrive, when, and what the field bus said about it — while this rule is about physical plausibility, computable from the signal, and a fault of a piece of equipment, because a sensor is equipment. AHU-0028 and RTU-0003 already ship that argument; this card is the same object with the equipment family taken out.
Detection Logic
yFault = |sensor_value_a − sensor_value_b| > drift_threshold
sustained continuously for drift_duration,
then held a further alarm_delay
Block graph (rule.cxf.jsonld):
Five blocks and no gate. The sign discarded by absDiff is the rule’s defining
property rather than an implementation detail: swap the two inputs and the
output is identical on every tick, which is verdict: ambiguous written as
arithmetic.
driftHigh is a strict Reals.GreaterThreshold — CDL Reals has no
GreaterEqual — so a pair sitting exactly drift_threshold apart reads
healthy. The threshold literal is in the bound points’ units, because the graph
has none: bound to an ERV as erv_oa_entering_temp against oat (two
thermometers in the same outdoor air stream, both °C, no host derivation and no
mode gating), 2.0 means 2.0 K; bound to a pair of humidity transmitters the
same literal means two points of relative humidity, which is not the reference’s
number. Retune at binding.
sustained and persist are the reference’s two published delays chained
rather than added, so 90 minutes to alarm at the defaults. Both assert at
exactly T + delayTime, and continuous means continuous in both: a
reconvergence discards the elapsed time rather than pausing it. delayOnInit = true on both (CDL default false) makes a pair already diverged at controller
restart wait out the full 90 minutes.
Possible Diagnoses
The reference’s four, in its order:
- Sensor calibration drift — the intended target, fixed by the playbook’s Step 3 recalibration
- Sensor wiring fault — a long run picking up an offset, a loose terminal, or a 3-wire RTD lead-resistance error reading as a fixed bias
- Sensor placement — the two are not in the same air stream after all (a spare outdoor sensor on a sunlit wall, a probe downstream of a leak, a pair split across a mixing plane), which is a binding correction, not a work order
- Sensor failure — a transmitter drifting toward a rail, on its way to the flatline SYS-0009 will catch when it arrives
Every one of the four names a single sensor and this rule cannot say which of the two it is; the playbook’s Step 3.4 settles it by taking a reference instrument to both members.
Energy Impact
COMFORT_ENERGY, LOW confidence, QUALITATIVE_ONLY — the reference’s profile.
There is no runtime waste term and this card does not invent one: a drifted
sensor spends nothing by drifting. savings_range is EEM-01’s recalibration
figure, 0-5% of site energy where the drift is causing downstream faults, and
the conditional does the work — the amount belongs to the economizer or reset
rule being misled, not to this one. Confidence is LOW for a specific reason: the
rule is confident about the pair and silent about either member, and its
false-positive rate is governed by whether the binding is sound. Diagnosis 3 is
the standing false positive, and no threshold distinguishes it from real drift.
Emissions Impact
Scope 1 or 2 depending on what the mis-measurement drives, QUALITATIVE_EMISSIONS,
LOW confidence, avoided-emissions basis N/A — the reference’s assignment. The
ambiguity in scope is real: a drifted sensor biasing a boiler is Scope 1, the
same sensor biasing a chiller or economizer is Scope 2, and the sensor itself
emits nothing. The quantity is entirely cascade, which is why
runtime_estimation is empty.
Deviations
- First card in the library carrying
adjudicates(contract above). No rule list appears on this card and none should: a hand-written list is correct the day it is written and silently incomplete the first time someone authors a rule reading the same point. AHU-0028’s hand-written thirteen-entrysuppressesis the counter-example, and two of those thirteen do not exist yet. - The fan-out is larger than it looks. Bound to an ERV as
erv_oa_entering_temp/oat, the closure is ERV-0001 and ERV-0002 — every rule the ERV family currently has, so the unit goes dark on one finding. Whether a host should then go silent or report at reduced confidence is an open question for the library owner; what this card owes is an honest declaration of scope, which is both points. verdict: ambiguousrather than picking a victim in prose. The alternative was to declaresensor_value_bthe reference (the reference’s required-points table calls it that) and adjudicate onlysensor_value_a. Nothing in the graph distinguishes the two inputs andabsDiffguarantees identical output under a swap, so naming the members primary and reference is a binding convention, not a property this rule can exploit.sensor_value_a/sensor_value_bare role points, the documented exception to the canonical-name convention. The same graph deploys against many real points and the reference’s own required-points table says “varies by application” in the units column. The cost is named rather than hidden: the host’s instance configuration must record each binding — the same artifactadjudicatesresolves against, so the design needs it either way.drift_thresholdships as one number where the reference publishes two. The reference’s2°C / 5%is it acknowledging that the threshold is per-quantity; a CXFS231:valueis one double. The shipped 2.0 is the temperature half, the same value AHU-0028 uses forsensor_tolerance, and the 5% alternative is documented inparams. Precedent for an explicitly per-binding placeholder: VAV-0001’sventilation_requirement.- Two delays in series, not one. The reference lists
drift_duration(60 min) andAlarmDelay(30 min) as separate tunables for one condition, so both are kept and chained, the VFD-0001 shape. A single 5400 s delay behaves identically as shipped; the chain is what lets a site keep a 30-minute drift window and a two-hour alarm hold, or the reverse, without re-authoring. - No activity gate, deliberately. SYS-0009 needs
equip_activebecause a signal that is not moving on idle equipment is not evidence of anything; a bias test needs no such permission, since two thermometers in the same air disagree when one is wrong whether or not a fan runs. What this rule does need — that the pair is seeing the same quantity right now — is a per-binding claim about dampers and modes that no boolean expresses, so it is host-enforced preconditions, the call AHU-0028 made for its post-changeover exclusion. - No discrete blocks, so no startup artifact to mask.
SubtractandAbsare combinational, and so isGreaterThresholdat the shippedh = 0— it takes a state word only when hysteresis is enabled — so tick one compares two live readings and means it.Discrete.UnitDelay’s tick-one artifact and the ban onReals.Derivativebelong to SYS-0010; this card’s only state is the two timers. TrueDelayasserts at exactlyT + delayTime, verified against the engine at the pin rather than assumed: withdelayOnInitthe timer is zero on the first tick and accumulatesdtfrom the second, so the realized test is “diverged for strictly more thandrift_duration + alarm_delay”.- Common-mode drift is invisible. Two sensors from one calibration batch, on one supply voltage, with one wrong scaling constant drift together and the subtraction cancels it. The rules that could see it are SYS-0006 (a virtual sensor built from other points) and a fleet-comparison form that is not written.
- Kept the reference’s number instead of taking a new one. At authoring
time a consecutive
SYS-FC-102was offered; the reference’s ownSYS-FC-054won (decided 2026-08-17) because the reference’s card is this rule and the cluster and playbook files already used that ID. The 2026-08-18 renumbering into the general namespace made it SYS-0005; legacy IDs live infaults/registry.json. clusters: [CLU-09]is a declaration, not an edit. CLU-09 already carries SYS-0005 as a member. That CLU-09’s trigger should arguably become one of the sensor rules, with AHU-0028 demoted to member, is a single-writer file and someone else’s edit — flagged here, not made.suppresses: [], and it must stay that way in both directions. The NO_EVAL fan-out isadjudicates’ job, derived per instance. The stronger constraint belongs to whoever writes the next card: a card carryingadjudicatesMUST NOT appear in any other card’ssuppresses, because an equipment fault silencing the sensor rule that invalidates it is a cycle. The linter does not check this today.category: COMFORT_ENERGYtranscribed, not argued.PROTECTIVEis arguably more honest for an adjudicating rule, whose delivered value is avoided false alarms and preserved diagnostic coverage rather than energy, but the reference says COMFORT_ENERGY and so do AHU-0028 and RTU-0003; a category convention for sensor faults is library-wide. Severity 3 likewise.- Operating states and preconditions are declared in frontmatter for host enforcement rather than encoded in the block graph, per the library’s design stance.
Notes
Read the finding as a work order for two sensors, not one — Step 3.4 of the sensor-drift playbook says so, and it is the only procedure two points justify. A technician sent to a guessed member has a 50% chance of recalibrating a correct sensor against a drifted reference, which makes the pair agree and the building wrong.
Rule out diagnosis 3 from a trend first, because it is free and it is the most common false positive. Real drift opens slowly and does not close; a placement mismatch opens and closes with the weather, the schedule, or the damper, and the repair is a bracket rather than a calibration.
The family’s three members answer different questions: SYS-0009 catches the transmitter that has stopped moving, SYS-0010 the one that jumps further than the process can, and this one the one that is quietly wrong. A sensor that trips this rule and later trips SYS-0009 has finished failing.
Test Vectors
14 scenarios, clock step 60 s over 10800 s.
| Scenario | Description |
|---|---|
pair_agrees | Both members of the pair read the same air within their combined accuracy: 15.0 against 14.6 is a 0.4-unit spread, well inside drift_threshold. Silent for three hours. |
member_a_reads_high | sensor_value_a sits 4.0 units above sensor_value_b. The divergence clears the threshold on the first tick, sustained matures at 3600 s and persist at 5400 s. |
member_b_reads_high | The mirror of member_a_reads_high, and the vector-level statement of verdict: ambiguous. sensor_value_b is now the high one and every output tick is byte-identical to the previous scenario — Abs discards the sign, so the rule cannot name which member drifted and does not pretend to. |
divergence_exactly_at_the_threshold | Boundary: 17.0 against 15.0 is a divergence of exactly drift_threshold (2.0). Reals.GreaterThreshold is strict and CDL Reals has no GreaterEqual, so exactly on the line reads healthy. |
divergence_just_below_the_threshold | The same line from below: 1.9 units apart, never reported. |
divergence_just_above_the_threshold | The same line from above: 2.1 units apart, alarm at 5400 s. |
both_members_drift_together | The blind spot, pinned rather than left to be discovered on site: both sensors read 25.0 while the air they share is at 15. A common-mode error — one calibration batch, one supply voltage, one wrong scaling constant — cancels in the subtraction and this rule is silent through all of it. |
slow_drift_crosses_the_threshold | The reason the shape exists. sensor_value_a walks away from its partner over 90 minutes — 15.0, 16.0, 17.5, 19.0 — and crosses drift_threshold at t=3600 s, so the alarm lands at 9000 s. Neither a flatline test nor a spike test can see this: the signal is never still and never fast. |
divergence_shorter_than_both_delays | A 75-minute divergence: long enough to mature sustained (60 min) and 15 of the further 30 minutes persist needs. No alarm. With the reference’s drift_duration alone — one combined delay instead of the chain — this fires at 3600 s, which is what makes it the regression test for the two-delay structure. |
divergence_clears_on_the_maturity_tick | The delay edge from below: the pair reconverges at exactly 5400 s. TrueDelay asserts at T + delayTime and the falling edge passes through both delays with no lag, so the two land on the same tick and the fault is never reported. |
divergence_clears_one_tick_later | The same edge from above: reconvergence one tick later leaves exactly one tick of alarm at 5400 s. The realized test is therefore ‘diverged for strictly more than drift_duration + alarm_delay’ at tick resolution. |
divergence_dips_and_restarts_the_clock | Continuous means continuous. The pair converges for ten minutes at t=1800 s, which discards the elapsed time rather than pausing it, and the alarm lands a full 5400 s after the second crossing at 2400 s. |
pair_reconverges_after_alarm | Recovery: the alarm asserts at 5400 s and someone applies a BAS offset at 7200 s, bringing the members within 0.2 units. Both delays drop on that tick — TrueDelay delays the rising edge only. |
percent_binding_at_the_shipped_default | The units warning made executable. Two humidity transmitters bound as the pair, 44.0 %RH against 40.0 %RH: the graph has no units, so the shipped 2.0 temperature placeholder alarms on a 4-point spread the reference’s own 5% default would have cleared. A binding that does not retune drift_threshold gets a rule it did not ask for. |
vectors.json
{
"schema": "cxf-library/vectors/v1",
"clock": {
"step_s": 60,
"horizon_s": 10800
},
"scenarios": [
{
"name": "pair_agrees",
"description": "Both members of the pair read the same air within their combined accuracy: 15.0 against 14.6 is a 0.4-unit spread, well inside drift_threshold. Silent for three hours.",
"inputs": {
"sensor_value_a": 15.0,
"sensor_value_b": 14.6
},
"expect": [
{
"output": "yFault",
"from_s": 0,
"to_s": 10800,
"equals": false
}
]
},
{
"name": "member_a_reads_high",
"description": "sensor_value_a sits 4.0 units above sensor_value_b. The divergence clears the threshold on the first tick, sustained matures at 3600 s and persist at 5400 s.",
"inputs": {
"sensor_value_a": 19.0,
"sensor_value_b": 15.0
},
"expect": [
{
"output": "yFault",
"from_s": 0,
"to_s": 5340,
"equals": false
},
{
"output": "yFault",
"from_s": 5400,
"to_s": 10800,
"equals": true
}
]
},
{
"name": "member_b_reads_high",
"description": "The mirror of member_a_reads_high, and the vector-level statement of verdict: ambiguous. sensor_value_b is now the high one and every output tick is byte-identical to the previous scenario \u2014 Abs discards the sign, so the rule cannot name which member drifted and does not pretend to.",
"inputs": {
"sensor_value_a": 15.0,
"sensor_value_b": 19.0
},
"expect": [
{
"output": "yFault",
"from_s": 0,
"to_s": 5340,
"equals": false
},
{
"output": "yFault",
"from_s": 5400,
"to_s": 10800,
"equals": true
}
]
},
{
"name": "divergence_exactly_at_the_threshold",
"description": "Boundary: 17.0 against 15.0 is a divergence of exactly drift_threshold (2.0). Reals.GreaterThreshold is strict and CDL Reals has no GreaterEqual, so exactly on the line reads healthy.",
"inputs": {
"sensor_value_a": 17.0,
"sensor_value_b": 15.0
},
"expect": [
{
"output": "yFault",
"from_s": 0,
"to_s": 10800,
"equals": false
}
]
},
{
"name": "divergence_just_below_the_threshold",
"description": "The same line from below: 1.9 units apart, never reported.",
"inputs": {
"sensor_value_a": 16.9,
"sensor_value_b": 15.0
},
"expect": [
{
"output": "yFault",
"from_s": 0,
"to_s": 10800,
"equals": false
}
]
},
{
"name": "divergence_just_above_the_threshold",
"description": "The same line from above: 2.1 units apart, alarm at 5400 s.",
"inputs": {
"sensor_value_a": 17.1,
"sensor_value_b": 15.0
},
"expect": [
{
"output": "yFault",
"from_s": 0,
"to_s": 5340,
"equals": false
},
{
"output": "yFault",
"from_s": 5400,
"to_s": 10800,
"equals": true
}
]
},
{
"name": "both_members_drift_together",
"description": "The blind spot, pinned rather than left to be discovered on site: both sensors read 25.0 while the air they share is at 15. A common-mode error \u2014 one calibration batch, one supply voltage, one wrong scaling constant \u2014 cancels in the subtraction and this rule is silent through all of it.",
"inputs": {
"sensor_value_a": 25.0,
"sensor_value_b": 25.0
},
"expect": [
{
"output": "yFault",
"from_s": 0,
"to_s": 10800,
"equals": false
}
]
},
{
"name": "slow_drift_crosses_the_threshold",
"description": "The reason the shape exists. sensor_value_a walks away from its partner over 90 minutes \u2014 15.0, 16.0, 17.5, 19.0 \u2014 and crosses drift_threshold at t=3600 s, so the alarm lands at 9000 s. Neither a flatline test nor a spike test can see this: the signal is never still and never fast.",
"inputs": {
"sensor_value_a": [
{
"t": 0,
"value": 15.0
},
{
"t": 1800,
"value": 16.0
},
{
"t": 3600,
"value": 17.5
},
{
"t": 5400,
"value": 19.0
}
],
"sensor_value_b": 15.0
},
"expect": [
{
"output": "yFault",
"from_s": 0,
"to_s": 8940,
"equals": false
},
{
"output": "yFault",
"from_s": 9000,
"to_s": 10800,
"equals": true
}
]
},
{
"name": "divergence_shorter_than_both_delays",
"description": "A 75-minute divergence: long enough to mature sustained (60 min) and 15 of the further 30 minutes persist needs. No alarm. With the reference's drift_duration alone \u2014 one combined delay instead of the chain \u2014 this fires at 3600 s, which is what makes it the regression test for the two-delay structure.",
"inputs": {
"sensor_value_a": [
{
"t": 0,
"value": 19.0
},
{
"t": 4500,
"value": 15.0
}
],
"sensor_value_b": 15.0
},
"expect": [
{
"output": "yFault",
"from_s": 0,
"to_s": 10800,
"equals": false
}
]
},
{
"name": "divergence_clears_on_the_maturity_tick",
"description": "The delay edge from below: the pair reconverges at exactly 5400 s. TrueDelay asserts at T + delayTime and the falling edge passes through both delays with no lag, so the two land on the same tick and the fault is never reported.",
"inputs": {
"sensor_value_a": [
{
"t": 0,
"value": 19.0
},
{
"t": 5400,
"value": 15.0
}
],
"sensor_value_b": 15.0
},
"expect": [
{
"output": "yFault",
"from_s": 0,
"to_s": 10800,
"equals": false
}
]
},
{
"name": "divergence_clears_one_tick_later",
"description": "The same edge from above: reconvergence one tick later leaves exactly one tick of alarm at 5400 s. The realized test is therefore 'diverged for strictly more than drift_duration + alarm_delay' at tick resolution.",
"inputs": {
"sensor_value_a": [
{
"t": 0,
"value": 19.0
},
{
"t": 5460,
"value": 15.0
}
],
"sensor_value_b": 15.0
},
"expect": [
{
"output": "yFault",
"from_s": 0,
"to_s": 5340,
"equals": false
},
{
"output": "yFault",
"from_s": 5400,
"to_s": 5400,
"equals": true
},
{
"output": "yFault",
"from_s": 5460,
"to_s": 10800,
"equals": false
}
]
},
{
"name": "divergence_dips_and_restarts_the_clock",
"description": "Continuous means continuous. The pair converges for ten minutes at t=1800 s, which discards the elapsed time rather than pausing it, and the alarm lands a full 5400 s after the second crossing at 2400 s.",
"inputs": {
"sensor_value_a": [
{
"t": 0,
"value": 19.0
},
{
"t": 1800,
"value": 15.0
},
{
"t": 2400,
"value": 19.0
}
],
"sensor_value_b": 15.0
},
"expect": [
{
"output": "yFault",
"from_s": 0,
"to_s": 7740,
"equals": false
},
{
"output": "yFault",
"from_s": 7800,
"to_s": 10800,
"equals": true
}
]
},
{
"name": "pair_reconverges_after_alarm",
"description": "Recovery: the alarm asserts at 5400 s and someone applies a BAS offset at 7200 s, bringing the members within 0.2 units. Both delays drop on that tick \u2014 TrueDelay delays the rising edge only.",
"inputs": {
"sensor_value_a": [
{
"t": 0,
"value": 19.0
},
{
"t": 7200,
"value": 15.2
}
],
"sensor_value_b": 15.0
},
"expect": [
{
"output": "yFault",
"from_s": 0,
"to_s": 5340,
"equals": false
},
{
"output": "yFault",
"from_s": 5400,
"to_s": 7140,
"equals": true
},
{
"output": "yFault",
"from_s": 7200,
"to_s": 10800,
"equals": false
}
]
},
{
"name": "percent_binding_at_the_shipped_default",
"description": "The units warning made executable. Two humidity transmitters bound as the pair, 44.0 %RH against 40.0 %RH: the graph has no units, so the shipped 2.0 temperature placeholder alarms on a 4-point spread the reference's own 5% default would have cleared. A binding that does not retune drift_threshold gets a rule it did not ask for.",
"inputs": {
"sensor_value_a": 44.0,
"sensor_value_b": 40.0
},
"expect": [
{
"output": "yFault",
"from_s": 0,
"to_s": 5340,
"equals": false
},
{
"output": "yFault",
"from_s": 5400,
"to_s": 10800,
"equals": true
}
]
}
]
}