Playbook: Sensor Drift / Calibration
| Applies to | SYS-0005, SYS-0006, AHU-0002, AHU-0003, AHU-0008, AHU-0010, AHU-0028, AHU-0032, RTU-0003, CLU-09; SYS-0009 (flatline), SYS-0010 (spike) — library-authored additions, the reference’s row predates them |
| Fix complexity | On-site service required |
| Typical time | 1–2 h per sensor |
| Typical cost | $50–$200 per sensor (recalibrate or replace) |
| Energy impact | EEM-01: 0–5% site energy from sensor recalibration; ~15% prevalence. The direct energy impact of one drifted sensor is small, but the cascade is not — a single biased OAT sensor can disable the economizer (0–7% waste), trigger false alarms across multiple rules, and mask real faults. |
Adapted from HVAC FDD Reference v1.0, Remediation Playbooks (pp. 165–166).
Step 1 — Verify the fault
- Compare the suspect sensor to a portable reference instrument: temperature → NIST-traceable digital thermometer; pressure → calibrated manometer; CO₂ → fresh-air baseline (outdoor CO₂ ≈ 420 ppm); humidity → sling psychrometer or calibrated RH probe (humidity sensors are the most drift-prone, typical lifespan 1–2 years between recalibrations).
- If the FDD system’s virtual sensor model (SYS-0006) shows bias greater than 1.5 °C, drift is confirmed (virtual sensors demonstrate RMSE ≈ 0.30 °C — Koo & Yoon 2022 — so 1.5 °C is well outside normal error).
- A drifted sensor may be triggering false alarms on other rules: if multiple faults fire on the same equipment, this sensor may be the root cause (the CLU-09 suppression rationale).
Step 2 — Remote fix (temporary)
- Apply a sensor offset / calibration correction in the BAS to compensate; document the offset value and date. This is a stopgap — the physical sensor still needs service.
- If the drifted sensor is an OAT sensor disabling the economizer, the offset provides immediate energy savings while waiting for on-site work.
Step 3 — On-site service
- Recalibrate per the manufacturer’s procedure.
- If the sensor cannot hold calibration, replace it: temperature $30–$80; pressure transducers $80–$200; humidity $50–$150 (most frequent); CO₂ $100–$300 (calibrate with a known gas standard or fresh outdoor air).
- Verify the reading against the reference instrument before leaving.
- For paired installations (SYS-0005 cross-validation), recalibrate both sensors in the pair.
Step 4 — Confirm resolution
- The sensor drift fault should clear within 1–2 evaluation windows.
- Downstream false alarms caused by the drifted sensor should also clear.
- If the Sensor Integrity cluster (CLU-09) was active, the entire cluster should resolve.