Execution profile

The generated authority summary distinguishes compiled state revisions from the review-only profile name and semantics; it does not define a new profile identity.

Open Control Engine currently has one execution profile: HostTick v1. It is fixed, not selected through an API option. A future profile with different state-transition semantics would require a separate compatibility and snapshot contract.

The complete-frame contract implements read-only preparation and one native atomic transition with an immutable output/diagnostic result around this same profile, not a second evaluator or profile selector. Preparation does not execute; consuming execute_frame is the only public state-advancing execution surface. Legacy execution profiles were removed.

The frame path enters one private infallible evaluation/refresh core after preflight and staging. The core closes durable-restore readiness, evaluates once, updates the previous time and refreshes latest outputs. It selects no diagnostic policy and performs no Store IO, restart, frame-sequence update or projection. Host loops select cadence and capture traces from completed receipts or explicitly labelled latest-state inspections.

HostTick v1

Each successful Engine::execute_frame(prepared) call is one state transition:

  1. Preparation snapshots every required typed boundary input and finite nondecreasing model time in seconds. Execution rechecks readiness, incarnation, time and sequence capacity before staging.
  2. The engine evaluates the frozen schedule once. Algebraic blocks compute from current inputs; stateful blocks compute from call-entry state and any feedthrough inputs their contracts use.
  3. After all emissions, every stateful block updates once from current-call inputs.
  4. The engine refreshes latest-state inspection and returns immutable CompletedFrame boundary outputs and warnings, correlated by an engine-lifetime accepted-frame sequence.

Repeating a timestamp does not repeat an observation of the same transition. Every successful call advances state again. Time-dependent blocks see zero elapsed time, but call-based state still changes. The engine performs no hidden same-time evaluation, event queue processing, rollback, or fixed-point search.

Ordinary refusal preserves the full execution image, including connector values, clocks, words, restore readiness and sequence. Previously retained completed diagnostics are unchanged. There is no sparse staging prefix, Store determinant or post-write error path.

CDL.Logical.Pre

The upstream Buildings Pre block defines y = pre(u) as a delay of one Modelica event iteration without advancing time. Event iteration continues until u == pre(u). HostTick v1 deliberately uses a different projection:

BoundaryHostTick v1 behavior
State allocationOne Boolean memory word is seeded from pre_u_start.
Before the first tickThe output connector has its Boolean connector seed, false; allocating state does not execute the block.
First successful tickPre emits pre_u_start, then latches current u.
Later successful ticksPre emits the u latched by the preceding call, then latches current u.
Repeated t_nowEach call advances the memory once, even though model time is unchanged.
Feedthrough graphPre reports no direct feedthrough and cuts a scheduling cycle.

Schedule acceptance is based on direct-feedthrough shape, not event convergence. A Boolean loop such as Pre -> Not -> Pre is accepted and alternates once per tick call. That network has no same-time Boolean fixed point, but HostTick v1 neither rejects it nor emits a non-convergence diagnostic.

Host observation

get_output and watch are latest-state, non-receipt inspections. Load, restore and parameter resume can replace their state without a frame. They may read internal connector points that are not boundary outputs. There are no intermediate event-iteration rows or raw output-arena accessor.

CompletedFrame retains accepted inputs and executable root boundary outputs in lexical identity order, plus the Warning diagnostics emitted by that native transition. It is independent of the mutable latest view. Its engine-lifetime sequence increases only on accepted frames, never on refusal, and survives reload/resume/restore without rewinding. The private context fence is not serialized and is not host deployment authority. See the frame contract for preflight precedence.

The separate canonical replay record captures this receipt without reevaluation. Exact replay compares raw values and diagnostic fields, not tolerances. Hosts authenticate order, build/executable context and optional state sidecars, then drive the same prepare/execute surface. No sequence container, embedded snapshot, profile selector or second evaluator is introduced.

Do not drive event iteration by repeatedly executing frames with the same timestamp unless repeated HostTick state transitions are the intended behavior. Those calls also update every other stateful block, not only Pre.

Snapshots

A state snapshot stores both sides of the call boundary: connector values contain the currently visible Pre output, and the block’s Boolean state word contains the value to emit on the next successful call. Capture and restore do not evaluate the model. After restore, a call at the restored timestamp is a new HostTick transition.

HostTick v1 is part of execution-state ABI revision 2 even though the profile name is not a separate wire field. A future same-time event-iteration profile must use a distinct execution-state ABI revision or a newly revised manifest and codec with profile identity. It must not consume HostTick v1 snapshots as semantically equivalent state.

ABI revision 2 preserves HostTick v1 and adds the exact executable IO acceptance domain to the state manifest, alongside format revision 2. See the state compatibility contract. Build/deployment authentication is a mandatory host-envelope precondition before byte decoding; OCE carries no build token. State compatibility does not authenticate a build or authorize actuation.

Conformance boundary

Open Control Engine supports the CDL.Logical.Pre interface and the HostTick v1 behavior above. It does not claim exact Modelica or OpenModelica same-time event-iteration equivalence for Pre, or for a network whose result depends on that iteration. Pre is therefore excluded from expected-green OpenModelica differential claims under this profile.

The boundary is pinned through the public facade in crates/oce-api/src/tests/pre_execution_profile_tests.rs. The tests cover initialization, repeated equal-time calls, all host output views, a non-convergent Boolean feedback loop, and snapshot/restore continuation.

The Tier-A references for Generic.TimeSuppression, CoolingOnly.Controller, and ReliefFanGroup likewise check HostTick v1. Their 20 signal records are independent of oce-blocks, but they do not claim Modelica Pre event-iteration equivalence.