Canonical accepted-frame replay record — revision 1

Scope and authority

This is the execution-maintainer detail of PC-039 in the product contract. It defines one accepted-frame record, not a sequence, historian, state snapshot, deployment receipt, network protocol or second evaluator. OCE remains synchronous, in-process, database-free and file-I/O-free. Nothing is published or qualified for cross-release migration by this format. The release-candidate matrix and fallback guide retain current/current evidence only; the historical v0.1.0 source pin has no replay producer. Cross-build envelopes refuse outside OCE before decoding, not through an invented historical replay decoder.

CompletedFrame::inputs() retains the canonical accepted boundary inputs independently of caller buffers and later engine mutation. CompletedFrame::replay_record() encodes those inputs, that transition’s outputs/warnings/time and its captured placement, without executing again. It records the public CompatibilityDescriptor::current(None) facts: export is explicitly absent, not silently claimed complete. The public descriptor is constant for that compiled process; it is not the loaded executable. No export, state capture, private fingerprint or Store operation is involved.

The record contains no sequence number. CompletedFrame::sequence() remains Engine-lifetime correlation only, never durable replay position. Hosts own the authenticated order, gap detection, duplicate policy and optional start/end EngineStateSnapshot sidecars. Even identical record bytes can represent two distinct accepted transitions. Equal timestamps are not idempotence keys.

Host workflow and trust boundary

  1. Bound transport/envelope buffering. Authenticate an envelope binding the exact record bytes, ordered position, compatible executable/parameters, approved same-build/deployment qualification, and any snapshot sidecars. Check freshness/generation and missing/duplicate policy outside OCE. Build qualification can include source/dependency lock, compiler, features, target and codegen. Package version, catalog/export tags and replay content identity are not build authority.
  2. Decode an approved record with ReplayRecord::from_bytes. This checks canonical representation, corruption and bounds, not host trust. Do not patch bytes or relabel placement to make them pass.
  3. Call record.check_compatible(&CompatibilityDescriptor::current(None)?) before preparation. It checks exact public facts in canonical order, then foreign target placement. V1 only decodes exact-bits policy. It never accesses an engine, performs execution or implements a tolerance.
  4. Use an isolated engine loaded with the host-approved compatible executable/parameters. If supplied, decode and restore the separately authenticated compatible start snapshot under the existing startup window and manifest checks. A per-frame record intentionally does not prove prior state or complete executable identity. Without a snapshot the host qualifies the exact cold-start or preceding continuation state.
  5. Borrow record.inputs() into Vec<(&str, Value)>, call existing prepare_frame(record.time(), …), then consuming execute_frame once. Preparation still checks completeness, types, domains, time and current executable; ordinary refusal preserves all state and restore readiness.
  6. Call record.verify(&completed) to compare exact time, accepted inputs, outputs and diagnostics. Comparison also rechecks current public facts (export:none) and receipt placement. A mismatch happens after that transition and does not roll it back. Stop the isolated host replay loop; do not blindly retry or use comparison failure as equipment fail-safe policy.
  7. Drop that record before reading the next unless host retention is intended. Compare optional end-state snapshot bytes exactly. OCE keeps no last record or whole-sequence buffer. Persisting bytes, sidecars and authenticated order, recovery and any equipment command remain host work.

The public-only host prototype executes this workflow through oce_api alone. It is a deterministic integration fixture, not authentication implementation, external downstream adoption or host/equipment qualification. The rustdoc workflow is compiled too.

Wire grammar

All integers are unsigned little-endian unless specified. str is a u32 byte length followed by exact UTF-8 bytes, with no terminator, normalization or padding. Counts are u32. There are no optional extensions, reserved flags, alignment gaps, compression, serde encodings or trailing bytes.

Position/orderEncoding
0..8ASCII OCERPLY then one NUL byte
8..12u32 format revision, exactly 1
12..20u64 body byte length, excluding this header and the trailer
Body firstu8 exactness: 0 = ExactBits; every other tag refuses
Placementu8: 0 = Portable; 1 = TargetBound, followed by str arch, str os; other tags refuse
Public factsstr canonical descriptor, grammar below
Model timeu64 raw binary64 bits, finite seconds; signed zero is retained
Inputsu32 count; each row is str canonical_path, native value
Outputsu32 count; each row is str canonical_path, native value
Diagnosticsu32 count; each row is str block, str message, u64 raw time bits, u8 severity (0 = Warning only)
Traileru128 FNV-1a-128 over all preceding header/body bytes

Input/output paths are nonempty and strictly increasing lexical UTF-8 bytes, separately in each section. Duplicate keys refuse even if values agree. Diagnostic order is emission order; identical repeated diagnostics are allowed. Source/message strings can be empty and include NUL or LF; diagnostic times preserve all bits, without adding a new producer-time restriction. Native frame model time remains finite. Severity is closed Warning-only: never Error, escalation or interlock.

Target labels contain 1..64 ASCII lowercase letters, digits or underscores; capture uses Rust std::env::consts::ARCH and OS. Structurally valid foreign labels can decode for inspection but refuse eligibility. Placement uses the exact same conservative 15-class predicate as state capture; any participating target-bound class binds the record. Portable removes only that target check, not other compatibility or host qualification requirements. The finite Linux strict-bit corpus does not imply universal mathematics or relax the state placement policy.

Native value encoding

u8 tagPayload
0 — Realu64 raw IEEE-754 binary64 bits, including subnormals, infinities, both zeros and every NaN payload/sign
1 — Integeri64 two’s-complement bits; no f64 conversion or codec-level i32 narrowing
2 — Booleanu8 exactly 0 or 1
3 — Stringstr exact UTF-8, including empty, NUL and LF
4 — Enumstr canonical registered enum class path, then u32 1-based ordinal in that class’s domain

Other tags refuse. Enum aliases, unknown classes and illegal ordinals refuse; no process-local EnumClassId is serialized. The currently registered CDL/G36 enum paths/members are the existing value/catalog contract, not a new extension registry. The codec covers every closed Value variant; detached full-domain probes do not add String/enum signal ports to the live CXF profile. Playback preparation retains its executable-specific input-domain checks, including CDL Integer bounds.

Public descriptor grammar

The descriptor is at most 1024 UTF-8 bytes, with the ten existing labeled LF-terminated lines in exact order: oce-compatibility, catalog-schema, catalog, io-schema, value-schema, parameter-schema, execution-profile, execution-profile-schema, oce-api-version, export. No missing/extra lines, CR/BOM, whitespace or escaping is accepted. Revision fields are positive u32 decimal with no leading zeros. Catalog text is catalog:1:fnv1a128: plus 32 lowercase hex digits; export is none or cxf:fnv1a128: plus 32 lowercase hex digits. The profile is HostTick-v plus a positive u32 decimal. Package version uses SemVer syntax: three canonical u64 decimal components, optional dot-separated ASCII alphanumeric/hyphen prerelease (numeric identifiers have no leading zeros), and optional build identifiers. Empty identifiers refuse.

Structurally valid differing facts can decode, then fail check_compatible with the existing CompatibilityMismatch cause. Descriptor revision other than 1 always refuses eligibility. Native capture/verification use export:none; a decoded present export never matches absence. Inspection/comparison of externally carried export facts does not make OCE attest their provenance. No standalone public descriptor parser or arbitrary serde-stability promise is added.

Integrity, identity and exactness

The trailer uses offset 0x6c62272e07bb014262b821756295c58d, XOR each byte then multiply by 0x0000000001000000000000000000013b modulo 2^128. ReplayContentId applies the same FNV-1a-128 algorithm to all canonical bytes including the trailer; Display is replay:1:fnv1a128:<32 lowercase hex digits>. Its private typed representation cannot be confused with catalog/export identity. Both hashes are noncryptographic, collision-prone accidental-content checks. An attacker can recompute them. Only exact host-authenticated bytes are the trust boundary.

Exact means Value::bit_eq and exact diagnostic source/message, severity and time bits, in order. Time uses to_bits, not numeric equality: +0 and -0 differ; matching NaN payloads agree as signal values. No epsilon, funnel, tolerance class or conformance comparison is reused. A record result is computation evidence, never sensor quality, freshness, actuator delivery or security authority.

Bounds and deterministic first cause

MAX_REPLAY_BYTES is 67,108,864 inclusive, counting header, body and trailer. Above-limit input refuses before header inspection and allocation. In addition, canonical decoded-work charge is at most 134,217,728 inclusive: 64 bytes per input/output/diagnostic row, every encoded string’s UTF-8 length (including enum paths), plus 24 bytes per String value for Arc metadata/alignment. These charges are fixed across architectures; compile-time layout guards ensure the Rust row/Arc representation does not outgrow them. Counts also have to fit the remaining raw minimum row bytes. All sums/products and slice boundaries are checked.

The decoder scans/checks every field and charges the entire workspace without allocation, then materializes exact-capacity vectors, owned strings and a copy of canonical bytes. It never trusts a count to allocate before admission. Work is linear in byte/row counts with no recursive structure. Canonical bytes plus charged decoded storage bound the owned record, not total process RSS: caller buffers, allocator overhead, clones, expected-descriptor capture and engine state are separate. Encoding sizes before allocating its bounded byte vector and validates through this decoder; capture temporarily holds that encoding as well as the decoded record. Allocation failure/panic/process death remain outside ordinary returned-error guarantees. This is not a CPU deadline promise.

Decode precedence is size; short/wrong header; format; total length; integrity; then body fields in wire order (exactness, placement, descriptor, finite model time, inputs, outputs, diagnostics, exact end). ReplayError distinguishes those causes, UTF-8, native/placement/severity tags, enum domain, noncanonical keys/Boolean/labels/suffix and workspace limit. Offsets are in the complete record. Eligibility compares descriptor fields in their existing canonical order, then target architecture/OS. Verification checks current eligibility and receipt placement, time, input rows, output rows, then diagnostic rows. The first differing row is reported; on pure count mismatch the index is the common length. Helpers never mutate engine or Store. They do not replace preparation preflight or restore manifest validation. A post-execution mismatch does not undo a prior accepted transition.

Evidence and remaining qualification

  • tests/fixtures/replay_{add,values,warning}.hex are hand-authored expected payload bytes, not blessed engine output. The existing hand-authored descriptor golden and independent tests/replay_oracle/mod.rs compose complete header/body/trailer bytes. Its two-word multiplication implements the specified checksum independently of the product’s u128 hashing. Add’s 3.75 output and warning fields are analytical expectations. No external Modelica oracle exists for this OCE-specific record grammar.
  • tests/replay_codec.rs covers complete-domain decoding, every truncation boundary, rechecksummed hostility, descriptor fields, key ordering/duplicates, target labels, all unknown value tags, other closed tags, native bits, enum bounds, UTF-8, counts/lengths/trailing bytes, integrity, inclusive cap/one-past, workspace amplification and repeated allocation-free refusal.
  • src/replay_capture_tests.rs checks exact independent encoding of every value domain on inputs and outputs, numeric bit classes, diagnostic fields/order/duplicates/counts, enum identity, empty records, oversized capture and unchanged sequence-independent bytes.
  • tests/replay.rs exercises actual accepted receipt ownership, Store noninterference, retained capture, wrong-descriptor/target pre-execution refusal and restore-window preservation, warning goldens, equal-time stateful replay from separately decoded start snapshots, exact end-state bytes, and a 16,384-record public-only host stream. Each iteration has identical bounded allocation peak/total and zero retained allocations; an explicit larger allocation is the positive control. This fixture is not a whole-program performance or all-model memory claim.
  • tests/replay_matrix.rs supplies repeat-exact portable and target-bound local vectors via optional OCE_PORTABLE_REPLAY_OUT / OCE_TARGET_REPLAY_OUT paths and foreign-placement inspection via OCE_FOREIGN_TARGET_REPLAY_IN. The existing debug/release oce-api matrix runs these tests, but cross-architecture replay artifact comparison is pending. Its artifact plumbing was not extended because ci.yml is itself pinned in the accepted strict-bit 35-file source boundary; changing that workflow would require separate requalification rather than silently reblessing evidence. Local artifact equality never fabricates hosted results or macOS qualification.

No state format/ABI, HostTick, catalog facts, conformance tolerance, dependencies, supported feature selections, downstream repository pins or release claims change. The new facade items are additive stable candidates; the exact public baseline and classification ledger record them.