Playbook: VFD and Pump Faults
| Applies to | VFD-0001 through VFD-0005, PMP-0001 through PMP-0006, AHU-0039 |
| Fix complexity | On-site service required |
| Typical time | 2–4 h |
| Typical cost | $200–$2,000 |
| Energy impact | Pump energy follows the cube law: reducing pump speed by 20% reduces pump power by 49%. A pump deadheading (running against closed valves) wastes 100% of its energy as heat and risks mechanical damage. Differential pressure reset (EEM-10/11) saves 0.5–2% of site energy by allowing pumps to run slower. |
Adapted from HVAC FDD Reference v1.0, Remediation Playbooks (pp. 167–168).
Pump family index: faults/pmp.
Decision tree
Follow control authority before component replacement:
- Confirm remote/auto/bypass state.
- Compare speed command and feedback.
- Determine whether the loop is pinned at minimum or maximum and read the process-error direction.
- Check current, torque, safety, demand, and application limits plus mechanical restrictions.
- Review tuning, process-sensor quality, and setpoint-reset behavior.
- Inspect current/kW trends only after control-state findings are resolved.
Do not manually energize, transfer, or bypass a drive outside the site’s approved operating and electrical-safety procedure.
Step 1 — Confirm control authority (VFD-0005)
- Verify the final drive enable is actually commanded, not merely an upstream system request.
- Read the HOA/keypad selector and configured command source. “Auto” must mean the commissioned remote BAS source, not local PID auto or terminal control.
- Confirm bypass from authoritative drive mode or contactor/power-path proof. Bypass available, ready, or commanded is not active bypass.
- Check whether maintenance, emergency, fire/smoke, commissioning, or a functional test explains the state. If approved, suppress the diagnostic rather than defeating the safety sequence.
- Restore authority only through approved procedures, then allow the loop and setpoint to settle before evaluating downstream faults.
Step 2 — Compare speed command and feedback (VFD-0001)
- Verify command and feedback are both normalized to percent of rated speed; do not compare percent with Hz.
- Check command-source configuration and fieldbus communication.
- Check the drive display for current, torque, thermal derating, and fault codes such as overcurrent, overvoltage, or ground fault.
- Check the cooling fan and heatsink — overheating can cause quiet derating before the drive trips.
- Compare drive-reported speed with a tachometer only after confirming what each point measures.
Step 3 — Inspect loop saturation (VFD-0002, VFD-0003)
- Confirm process value and setpoint are from the same loop, share units, and use a commissioned site-specific error threshold.
- At minimum speed, use the error direction to distinguish overdelivery/a minimum set too high from underdelivery, obstruction, or bad sensing.
- At maximum speed, verify the configured maximum and inspect current, torque, safety, demand, and application limits before calling the equipment undersized.
- Inspect filters, coils, strainers, dampers, valves, belts, couplings, impellers, and the distribution path for restrictions or degradation.
- Confirm the setpoint was settled long enough for the application’s time constant; a real reset/load step is not a capacity fault.
Step 4 — Inspect hunting (VFD-0004)
- Acquire speed, process value, and setpoint together at 60 seconds or faster; resample faster acquisition to the rule’s legal fixed evaluator interval (14.3–150 seconds at the defaults, 60 seconds recommended). Change-of-value logs can hide crossings.
- If only speed hunts, inspect command, feedback, drive limits, and mechanical backlash. If only the process hunts, inspect its sensor and external load.
- If both hunt, compare phase before retuning: process movement leading speed suggests a real disturbance or sensor problem; speed leading process suggests aggressive tuning or actuator/drive behavior.
- Exclude startup, staging, setpoint reset, smoke/purge, and manual tuning tests.
- Change one tuning parameter at a time and preserve protective/current/torque limits. Observe for at least two evaluation windows after each change.
Step 5 — Electrical and drive service
- Check VFD input and output power and calculate drive efficiency only after mode, scaling, and control-state findings are resolved.
- Check harmonic distortion where symptoms or site requirements justify it.
- Follow the manufacturer’s diagnostics for the exact drive and motor.
- If the VFD is failing, replacement is typically $500–$2,000 depending on motor horsepower; confirm the diagnosis before replacement.
Step 6 — Separate pump delivery signatures (PMP-0001, PMP-0002, PMP-0003, PMP-0005)
- Validate command and independent run proof first. An active PMP-0003 makes a stopped/running inference unreliable; resolve that before replacing a hydraulic component.
- Confirm flow and DP belong to this individual pump branch. A common-header flow point cannot distinguish a failed lag branch or a passing check valve.
- Running with no flow is PMP-0001. Running with high pump DP and low flow is the more specific deadhead signature PMP-0002. A stopped branch with flow is PMP-0005; do not treat these mutually different premises as one alarm.
- For PMP-0005, verify meter sign and zero, then compare flow with other-pump status and header pressure. Inspect the discharge check valve, isolation valves, bypass paths, and approved gravity/free-cooling arrangements.
- Remote fix: check the differential pressure setpoint — it may be set too high, forcing the active pump to work against closed valves.
- Remote fix: implement a differential pressure reset sequence if one doesn’t exist — the same trim-and-respond logic as air-handler duct static pressure reset (see the missing-reset playbook). EEM-10: 0.5–2% site energy savings.
- On-site: check for closed isolation valves and a blocked strainer.
- On-site: verify the pump impeller and coupling — damage can produce no flow despite the motor running.
- For variable-primary CHW systems, verify the minimum-flow bypass valve is functioning. Without it, the lead pump may deadhead when all AHU valves close.
Step 7 — Review starts and staging (PMP-0004)
- Use per-pump proof and a fixed evaluator tick that can resolve the shortest
cycle. At the defaults, acquire at 60 seconds and set
count_scale=evaluation_window/tick; COV loss can hide starts. - Compare each start with plant enable, lead/lag transfer, DP/temperature demand, minimum on/off timers, and any approved exercise sequence.
- Check whether VFD speed/process hunting (VFD-0004) is repeatedly crossing a run threshold. Fix the unstable loop before changing motor protection.
- Inspect overload, safety, and drive fault histories for trip/auto-reset cycling. A chattering proof device can create the same count.
- Apply the pump/motor manufacturer’s starts-per-hour limit; the library’s default is only a commissioning placeholder.
Step 8 — Compare actual and expected power (PMP-0006)
- Confirm actual and expected kW cover the same pump motor/drive circuit and the expected model is ready, fresh, in-domain, and fitted on known-good data.
- Compare power with speed, individual-branch flow, differential pressure, staging, and fluid condition. A model indexed on a different pump configuration is not a degradation finding.
- Resolve same-drive VFD tracking or mode/bypass findings before trusting a baseline that uses those signals. Scope any suppression to this pump/drive.
- Check power-sensor scaling and phase coverage before mechanical work.
- After control and sensor checks, inspect strainers, impeller, coupling, alignment, bearings, seals, motor, and drive. Refit the baseline only after the equipment is known clean; never train the fault into normal.
Step 9 — Confirm resolution
- Verify the drive remains in the commissioned remote-auto state with bypass inactive whenever normal operation is expected.
- Verify output tracks command within the commissioned tolerance.
- Verify the process returns within its allowance band without sustained minimum/maximum saturation or material hunting.
- For pumps, verify expected branch flow/DP, zero stopped-branch flow, and a compliant per-pump start count over at least one full evaluation window.
- Where PMP-0006 applies, verify actual power returns inside the commissioned residual band without refitting on the faulty interval.
- Confirm suppressions release on the same equipment instance and observe for at least two hunting/baseline windows before closing an instability or degradation finding.