Playbook: Zone Heating in Warm Weather
| Applies to | SYS-0007, CLU-05 |
| Fix complexity | Remote fix (85%) · On-site (15%) |
| Typical time | 15–30 min remote |
| Typical cost | $0 remote / $200–$600 on-site (stuck valve) |
| Energy impact | Found in ~20% of buildings per PNNL 151-building study. 100% of reheat energy consumed during warm weather is pure waste — the building is paying to heat air that was just mechanically cooled. In perimeter zones with solar gain, this is especially wasteful. A single reheat coil running at 50% during summer can waste $500–$2,000/yr. |
Adapted from HVAC FDD Reference v1.0, Remediation Playbooks (pp. 172–173).
Step 1 — Verify the fault
- Confirm the reheat valve command is above 10% when outdoor air temperature is above 21°C (70°F).
- Check whether this is a single zone or building-wide:
- A single zone: likely a stuck valve or a zone-level control issue.
- Multiple zones: likely a missing seasonal lockout or the AHU SAT is set too low (driving reheat across many zones).
- Check the zone temperature: if the zone is already at or above setpoint and the reheat valve is open, the valve is operating wastefully.
- In perimeter zones, check for solar gain overcooling the space — the reheat may be fighting solar-driven overcooling. If so, the root cause is lack of solar-responsive control rather than a hardware fault.
Step 2 — Remote fix
- Program an outdoor air temperature lockout for zone reheat:
- When OAT > 21°C (70°F) and the zone is satisfied, disable the reheat valve.
- Use hysteresis: re-enable at OAT < 18°C (65°F).
- Check the zone’s minimum airflow setpoint — if it’s too high, excess cool air is being delivered and then reheated. Reducing the minimum (see the VAV Minimum Flow / Reheat Waste playbook) eliminates the root cause.
- For building-wide issues, check the AHU SAT setpoint:
- If SAT is locked at 55°F (13°C) year-round, raise it during mild weather via SAT reset (see the Missing Reset playbook).
- A 2°F increase in SAT during part-load conditions can eliminate reheat in 30–50% of zones.
- For perimeter zones with solar gain: consider a demand-based reheat enable that allows reheat only when zone temperature drops below the heating setpoint minus 1°F.
Step 3 — On-site service (if the reheat valve is stuck open)
- Command the reheat valve to 0% and physically verify it closes.
- If the valve does not close, see the Stuck Actuator playbook for repair procedures.
- For perimeter heating systems not controlled by the BAS (e.g., standalone baseboard heaters with local thermostats): lower the thermostat setpoint for summer or add a manual seasonal shutoff.
Step 4 — Confirm resolution
- Monitor reheat valve commands during warm weather for 7 days.
- Reheat valves should remain at 0% when OAT is above the lockout threshold and zones are satisfied.
- The fault should clear within 24 hours.