RTU Fault Rules

Packaged rooftop unit fault detection rules (RTU-*). Source grounding: HVAC FDD Reference v1.0 ch.11 (adapted authority — see each card’s Deviations section). RTUs are the most common commercial HVAC system type, and the chapter’s emphasis follows the field data: economizer problems affect 54% of units (Cowan 2004), and compressor short-cycling and coil fouling dominate the mechanical failures.

Point dictionary: points/rtu.points.json.

Index

IDNameSevMethodStatus
RTU-0001Compressor short-cycling2ruleverified
RTU-0002Evaporator coil fouling3statisticalverified
RTU-0003SAT/MAT inconsistency (AFDD0)3ruleverified
RTU-0004Economizer not modulating3ruleverified
RTU-0005Excess outdoor air3ruleverified
RTU-0006Insufficient ventilation2ruleverified
RTU-0007Condenser airflow restriction3statisticalverified
RTU-0008Refrigerant undercharge — superheat/subcooling divergence3ruleverified
RTU-0009Refrigerant overcharge — high liquid subcooling3ruleverified
RTU-0010RTU supply-fan proof-of-operation failure2ruleverified
RTU-0011RTU supply-air temperature tracking failure3ruleverified

Severity and method for RTU-0001..009 follow the reference’s ch.11 cards (its §5.8.3 index carries no severity column); RTU-0010 is a severity-2 library proof-of-operation adaptation and RTU-0011 is a library tracking adaptation. RTU-0007 shipped once the host-fitted-baseline convention resolved its two-variable (stage AND outdoor temperature) curve as the derived point cond_split_baseline; its remaining constraint is the condenser leaving-air temperature sensor most packaged units lack, declared on the card as a retrofit gate rather than a deferral.

Relationships

  • RTU-0003 is PNNL’s AFDD0 — the sensor-consistency prerequisite for the chapter. While active it suppresses RTU-0002 and RTU-0004 (declared in its frontmatter).
  • RTU-0005/RTU-0006 are the excess/deficit halves of the outdoor-air-fraction measurement; the reference gates both behind the AHU-0028 mixing-box envelope check, instantiated against the RTU’s own mat/oat/rat points (the 062 graph is equipment-agnostic).
  • RTU-0004 is a CLU-03 member (economizer failure, trigger AHU-0017’s cluster) and shares the economizer-failure playbook.
  • RTU-0010 compares the final supply-fan command with independent proof. Read its direction before RTU-0001..006 and RTU-0008/0009: fail-to-start contests their running/airflow premise or evidence quality, while unexpected operation does not make their physical evidence invalid by itself.
  • RTU-0011 compares discharge temperature with the final active mode-specific target while fan and mechanical delivery are proven. Its warm/cold direction leads investigation across capacity, airflow, economizer, refrigerant, and control findings; proof rules remain related rather than unconditional suppressors.