PMP Fault Rules
Hydronic pump fault detection rules (PMP-*). PMP-0001/PMP-0002 originate in
the HVAC FDD Reference v1.0 ch.15; the later proof, cycling, stopped-flow, and
expected-power rules are library-authored extensions grounded in verified graph
precedents and public pump-system guidance. The family covers direct proof,
hydraulic delivery, protective cycling, and baseline electrical performance
without claiming a universal pump curve.
Point dictionary: points/pmp.points.json.
Loop-agnostic: the same rules bind to CHW, HW, or condenser-water pumps.
Index
| ID | Name | Sev | Method | Status |
|---|---|---|---|---|
| PMP-0001 | Pump commanded on, no flow detected | 2 | rule | verified |
| PMP-0002 | Pump deadheading (high DP, low/no flow) | 2 | rule | verified |
| PMP-0003 | Pump proof-of-operation failure | 2 | rule | verified |
| PMP-0004 | Pump short-cycling | 3 | rule | verified |
| PMP-0005 | Flow through stopped pump | 2 | rule | verified |
| PMP-0006 | Pump input-power degradation | 3 | statistical | verified |
All six are Phase 2. Thresholds that depend on pump size, branch design flow, sensor uncertainty, or a fitted model are explicitly site-configured on their cards.
Relationships
- PMP-0001 vs -051 differ in what they can see: -050 needs only cmd/status/flow and catches the broad “no useful work” condition; -051 adds the DP signature that distinguishes true deadheading (valves closed against a running pump) from impeller/coupling failure (DP low). Diagnosis order in the shared vfd-pump-faults playbook follows that split.
- VFD-0001/VFD-0002 watch the same drive from the electrical side; a deadheading pump at fixed speed shows normal VFD tracking — the families are complementary, not redundant.
- PMP-0003 suppresses PMP-0005 on the same pump because unreliable run proof invalidates the stopped/running premise. The stopped-flow graph remains raw and the host scopes suppression by equipment instance.
- PMP-0004 complements VFD-0004: pump starts and analog speed hunting are different signatures. Neither suppresses the other.
- PMP-0006 relates to VFD-0001/VFD-0005 but is not globally suppressed by them. A drive finding invalidates expected power only when the deployment’s model actually consumes the disputed drive state/speed and the host can prove both rules belong to the same pump/drive.
Ontology and cluster decisions
The PR 03 point additions pin ASHRAE 223 to the inspected public-review
artifact 1.0.0-ppr.2.1 (SHA-256
1f156f9938c0be430d2216e01e31bb183c438ba318d8d4a23d2f074ebcd6f573),
matching the ERV/VFD expansion precedent. This is an explicit migration from
the former unverified v1.0.0-2026 label, not a claim of a final release.
No Pump Delivery Failure cluster is added. Running with no flow, deadheading, proof disagreement, and flow through a stopped branch have mutually different premises and no single trigger whose correction should clear the set within the cluster contract’s 24–48 hour window.