FCU Fault Rules

Fan coil unit fault detection rules (FCU-*). Source grounding: HVAC FDD Reference v1.0 ch.12 and ASHRAE Guideline 36 §5.22.6 for the 001-range (the FCU analog of the AHU §5.16.14 set). FCUs are two-coil air handlers in miniature, distributed by the dozens; faults persist because nobody is watching any single unit.

Point dictionary: points/fcu.points.json.

Index

IDNameSevMethodStatus
FCU-0001Excessive operating state changes3ruleverified
FCU-0002SAT too low in full heating3ruleverified
FCU-0003SAT too high in full cooling3ruleverified
FCU-0004Inactive cooling coil temperature drop (leak)3ruleverified
FCU-0005Inactive heating coil temperature rise (leak)3ruleverified
FCU-0006FCU fan proof-of-operation failure2ruleverified
FCU-0007Simultaneous heating and cooling commands2ruleverified

Severity and method for FCU-0001..005 follow the reference’s ch.12 cards (its §5.8.5 index carries no severity column); FCU-0006 is a severity-2 library proof-of-operation adaptation and FCU-0007 is the command-level FCU adaptation of the simultaneous-conditioning signature. The first five rules are siblings of verified AHU patterns: FC-001 mirrors AHU-0004’s rolling transition counter, FC-002/003 mirror the AHU-0007/AHU-0013 saturated-coil pair, FC-004/005 mirror the AHU-0014/AHU-0015 inactive-coil signatures with rat/sat as the entering/leaving proxies.

Relationships

  • FCU-0001..007 share the fcu-faults playbook.
  • FCU-0006 compares the final fan command with independent proof. Its fail-to-start direction contests the airflow premise of FCU-0002..005; the unexpected-run direction can leave those temperature signatures meaningful, so the relationship is informational rather than a whole-rule suppression.
  • Passive/convection terminal units do not instantiate FCU-0006.
  • FCU-0007 detects a control-command conflict; FCU-0004/0005 detect thermal evidence while the corresponding command is closed. They are related and do not suppress one another. Intentional cooling-plus-reheat is host-excluded.
  • FCU-0007 shares the simultaneous-hc workflow but remains outside CLU-01: the cluster’s AHU-0016 trigger cannot causally clear a local FCU conflict.
  • FC-004/005 are the zone-scale members of the simultaneous-conditioning family (AHU-0016’s world): a leaking valve conditions air nobody asked to condition.