CXF round-trip: what export guarantees

For an integrator writing or consuming CXF documents against the Open Control Engine. It answers one question: when export returns Ok, what is actually in those bytes — and what is quietly not?

CXF is bidirectional here. oce-cxf imports through the §7.1 resolver (crates/oce-cxf/src/resolve/mod.rs:1, reached via oce_cxf::import_cxf at crates/oce-cxf/src/lib.rs:106) and exports through a separate, deliberately smaller path (oce_cxf::export at crates/oce-cxf/src/lib.rs:200). Import and export do not cover the same ground, and the gap between them is where the surprises live.

The RT-2 contract

Export is specified as a fixpoint, not as source recovery (crates/oce-cxf/src/export.rs:5-9). For a graph G1 that import_cxf produced, re-importing the emitted bytes yields a graph that renders bit-identically to G1 — Reals compared by their IEEE-754 bit patterns, never by an epsilon (crates/oce-cxf/src/lib.rs:124-137; the fixpoint test is crates/oce-cxf/tests/export_roundtrip.rs, which compares through a hand-written renderer using f64::to_bits). Emission order derives from the ModelGraph vectors alone, so repeated exports of the same graph are byte-identical (crates/oce-cxf/src/export.rs:47-52).

The carve-out belongs right here rather than in a footnote: bit-identity holds over the survivor cone, not necessarily over the whole input graph. When nothing is deferred the survivor cone is the whole graph. When deferral fires, it is not, and no re-import can restore what was omitted. The next-but-one section is about exactly that.

That promise is for graphs produced by import_cxf. A hand-built legacy graph may carry external_inputs with an empty boundary_inputs sidecar. Export keeps accepting that shape and emits attribute-free root input declarations; re-import then materializes empty sidecars, so the re-imported graph is not structurally identical to the hand-built input even when no warning was reported (crates/oce-cxf/src/lib.rs:139-143).

What never round-trips at all: cosmetic source content. Labels, layout, and line numbers are not in ModelGraph, so none of them come back. The original root @id is not recorded either — the root composite is emitted under the fixed synthetic IRI urn:open-control:cxf-export:root (crates/oce-cxf/src/export.rs:11-14).

The export subset

Export accepts the flat, ground, single-root, scalar-parameter subset — the shape the resolver produces (crates/oce-cxf/src/lib.rs:114-120). Everything outside it is a typed CxfError::Validation carrying DiagCode::ExportUnsupported error diagnostics whose subject is the offending block, connector owner, or declared boundary node. Never a panic (crates/oce-cxf/src/export.rs:61-64).

Of the §7.4.1 connector attributes, five survive, each emitted as a bare JSON scalar on minted child ports and represented root boundary-input and boundary-output nodes. A boundary input keeps its declaration attrs separate from every child target, including fan-out; export never infers one from the other. Engine::load_cxf joins a declared output and its source in the same §7.10 cluster: conflicting values refuse the load, while a value declared on only one side propagates to the unset peer before export. Boundary-input declaration unification is a separate acceptance change and is not implemented. Low-level callers that compose oce_cxf::import_cxf and export directly must run the graph through oce_validate to apply the current output-side load contract (crates/oce-cxf/src/export.rs:31-45):

AttributeEmitted asApplies to
unit, quantity, displayUnitbare stringReal connectors
min, maxbare number, finite onlyReal (float) and Integer (int) connectors

Attributes are emitted only when Some; an all-default connector emits zero attribute keys, which is byte-identical to an attribute-free port node.

Two attributes are rejected rather than dropped — and the distinction between rejected and dropped is the point. On a surviving block, a connector carrying nominal or unbounded fails the export (crates/oce-cxf/src/export_attrs.rs:42-55), because the importer hardcodes both to None and the value would vanish silently. A non-finite Real min/max bound is rejected for the same reason: serde_json writes it as JSON null, which re-imports as None (crates/oce-cxf/src/export_attrs.rs:56-88).

On a deferred ordinary block, none of that runs. The block is omitted from the document and therefore contributes no error diagnostic of its own — not from its connector attributes, not from its parameters, not from its boundary entries (crates/oce-cxf/src/lib.rs:168-208). A reserved pass-through with hidden state is the exception: the resolver-produced lowering shape is the only valid form in the reserved namespace, so it rejects even when an enum parameter also marks the block deferred. A boundary-input sidecar follows its target owner into that omission; invalid attrs on a declaration whose entire target set is deferred do not abort the partial export. Whole-graph guards behave differently: an empty (zero-block) graph, non-dense ids, and a connection that is not output→input reject either way, because they are attributable to no single block’s presence in the document.

The deferral trap

This is the most important thing on this page.

Ordinary enum-carrying blocks — any ValueType::Enum connector or Value::Enum parameter — are deferred, not rejected. The block and its entire transitive downstream cone are omitted from the emitted document so that the enum-free remainder can still export. Reserved pass-through blocks remain strict: an enum parameter violates the resolver-produced lowering shape, so it rejects despite being selected for deferral. Each omission is reported as a DiagCode::ExportDeferred warning, which is non-aborting (crates/oce-cxf/src/export_defer.rs:1-32). The cone is a least fixpoint: a single enum connector near the front of a chain dooms everything downstream of it.

How large does that get in practice? The G36 corpus pins two cases as tripwires (crates/oce-cxf/tests/export_g36_roundtrip.rs:678-698):

FixtureBlocks in graphBlocks deferredShare
cooling_only_controller213 (crates/oce-api/tests/g36_cooling_only_controller.rs:252)8339 %
multizone_vav_relief_fan_group226 (crates/oce-api/tests/g36_relief_fan_group.rs:105)6328 %

Rejection fires only on total deferral — a graph with no emitted runtime block left after deferred and reserved lowering-only blocks are removed, which would be an unloadable root-only shell (crates/oce-cxf/src/export.rs:112-116). In principle, then, all but one block can vanish from an export that returns Ok.

And export() discards the warnings (crates/oce-cxf/src/lib.rs:210-212 — it destructures them into _warnings). A caller using export() alone cannot distinguish a complete export from one that dropped 39 % of the graph. Both return Ok(Vec<u8>).

Use export_with_report (crates/oce-cxf/src/lib.rs:254). It returns an ExportReport with bytes and warnings (crates/oce-cxf/src/lib.rs:215-240); the bytes are identical to what export() returns for the same graph. An empty warnings list is what certifies that the round trip covered the whole resolver-produced input. The legacy empty-sidecar exception above still applies to hand-built graphs. Treat a non-empty list as “this document is a subset of the model I asked you to write.”

Through the facade, Engine::export_cxf() (crates/oce-api/src/export.rs:98) always goes through export_with_report and keeps the warnings, so the facade route does not expose the trap. It is oce_cxf::export() specifically that drops them.

Pass-through elision is not deferral

CDL allows a boundary input wired straight to a boundary output. Import lowers each such connect to a reserved internal identity block — urn:oce:lowering#PassThrough.Real, .Integer, or .Boolean (crates/oce-blocks/src/lowering.rs:66-78) — and export elides those blocks back to the bare boundary edge (crates/oce-cxf/src/export.rs:743-812, :827-842). Re-import re-synthesizes them, so RT-2 holds by render identity.

The visible consequence: the emitted document lists fewer containsBlock entries than the graph holds blocks, and a canonical imported pass-through produces no warning at all (crates/oce-cxf/src/lib.rs:144-148). Reserved connectors have no emitted child-port node, so a host-built boundary alias or connection involving a surviving reserved block is rejected rather than silently omitted. If cascade deferral omits the reserved owner, well-directed relationships follow the ordinary survivor-cone rule: they are omitted with ExportDeferred warnings. Structural direction errors still reject before survivor filtering. An authored instance identity, parameter, connector attribute, or class/type mismatch on the reserved block rejects because elision has no wire representation for that internal state. Declaration-side attrs remain representable on the emitted boundary input and output. If cascade deferral omits the reserved block, those declarations leave with it rather than appearing without a target. An empty warning list means nothing was deferred; it does not mean the document explicitly lists every internal lowering block. If you are reconciling counts between a ModelGraph and an emitted document, that is the difference to expect.

Two ways an Ok export produces bytes that fail re-import

Both are documented, and both are reachable only from a hand-built ModelGraph — never from one the resolver produced.

  1. Port arity contradicting the class. Export takes no registry dependency, so it does not check a block’s declared port count against the class its class_path names. A hand-built block naming a registered class while declaring fewer ports than that class requires exports Ok; the bytes then fail re-import with MalformedDocument (crates/oce-cxf/src/lib.rs:150-156).
  2. An unregistered class path. Same root cause, different symptom: the bytes export fine and fail re-import loudly with ClassNotFound — never silently (crates/oce-cxf/src/lib.rs:158-160).

Every graph the resolver produces is correct by construction on both axes.

content_id_complete: a checked integrity tag, not a digest

ExportReport::content_id_complete() returns cxf:fnv1a128:<32 hex chars> computed over exactly the emitted bytes when the export is complete. If any content was deferred, it returns the typed ContentIdError::Incomplete { warning_count, .. } instead of minting an identity. Its rustdoc carries a runnable reproduction of the tag computation so a host can verify a returned tag independently. Three properties worth internalizing:

  • It is explicitly non-cryptographic and not a security boundary. A host needing a cryptographic digest must hash the same bytes itself.
  • It is not LoadReport::model_id. model_id preserves the authored top-composite @id; export uses a synthetic root, and resumed parameter edits change exported bytes without recomputing model_id.
  • When warnings is non-empty, the unchecked tag would name only the partial survivor document; content_id_complete() refuses that case and reports the exact warning count. The older content_id() method remains only as deprecated compatibility behavior and should not be used to mint version identities. The checked behavior is pinned by crates/oce-api/tests/export_cxf.rs.

The import side

This page is about export. The normative contract for what nested-composite shapes import accepts and rejects — how S231:containsBlock hierarchies flatten, which shapes reject, and the machine-readable composite/<rule-id>: message tags an emitter can match on — is cxf-composite-subset.md in this directory. Read that one if you are writing a CXF generator.

Composite nesting is bounded at 64. Boundary lowering is iterative and separately rejects paths beyond 64 non-top isConnectedTo hops or documents beyond 65,536 target examinations or 8 MiB of aggregate target-IRI bytes within boundary walks. These are engine acceptance bounds, not CDL semantics. Hosts must still bound input bytes before JSON deserialization when accepting untrusted documents.

For which CDL classes and G36 sequences exist on the other end of that pipe, see cdl-coverage.md.