CDL coverage: what “supported” means

For anyone asking “does this run my sequence?” This page states which CDL classes the engine implements, what the 46 conformance fixtures actually are, and — the part that matters most — what the word “supported” is doing in each of those sentences.

The elementary-block registry

The engine registers 136 block classes: 133 CDL elementary classes plus 3 reserved internal lowering identities.

FamilyClasses
CDL.Reals52
CDL.Logical26
CDL.Integers24
CDL.Routing15
CDL.Discrete7
CDL.Conversions4
CDL.Psychrometrics3
CDL.Utilities2
CDL total133
Reserved lowering identities3
Registry total136

Every number in that table is checkable against the checked-in tools/reference-catalog/oce-blocks.registry-manifest.json, a 136-entry ordered JSON array generated from the registry itself and held byte-identical to it by registry::manifest_tests::checked_in_manifest_matches_regenerated_bytes in oce-blocks. The total is separately pinned at crates/oce-blocks/src/catalog_tests.rs:27.

The three reserved identities are urn:oce:lowering#PassThrough.Real, .Integer, and .Boolean (crates/oce-blocks/src/lowering.rs:66-78). They are what CXF import synthesizes for CDL’s direct boundary input→output connect. They are not authorable CDL — a hand-written CXF document cannot spell them — and each carries reserved: true in the catalog so a palette-building host can filter them out (crates/oce-blocks/src/catalog.rs:98-100).

Introspecting the registry at runtime

oce_blocks::catalog() (crates/oce-blocks/src/catalog.rs:155) returns the registered classes in deterministic registry order. Each CatalogEntry (crates/oce-blocks/src/catalog.rs:74-101) carries resolved input and output ports in declaration order, the port-naming policy, the static parameter rules, the authored parameter defaults, a width_driven flag, a conservative stateful hint, and the reserved flag.

The defaults are honest. DefaultSource (crates/oce-blocks/src/catalog.rs:47-57) has three variants — Literal, Derived { formula }, and Required. A parameter the caller must supply reports Required, not an internal fallback value dressed up as a default. That distinction is the whole reason the type exists.

The caveat that will cost you ten minutes: catalog() lives in oce-blocks, and oce-api does not re-export it. Reading crates/oce-api/src/lib.rs, the string catalog does not appear anywhere in crates/oce-api/src/ — the pub use block at crates/oce-api/src/lib.rs:50-77 re-exports Engine, the error types, ExportReport, IO and sim types, LoadReport, the parameter table, the topology view (Topology, TopologyBlock, TopologyConnection, DeclaredOutput, PassThroughPair), oce_diag::Diagnostic, oce_model::{ConnectorId, Value, ValueType}, and oce_store (including SemanticQuery) — and nothing from oce_blocks. oce-api depends on oce-blocks (crates/oce-api/Cargo.toml:29) and uses it internally, but a consumer depending only on oce-api must add oce-blocks as its own dependency to call catalog().

What “supported” means for a G36 sequence

The repo’s own catalog is explicit, and it under-claims on purpose. The support_policy block in tools/reference-catalog/Buildings.Controls.OBC.ASHRAE.G36.catalog.json records runtime_sequence_status: "selected-explicit-cxf-variants-supported" and states that supported rows “are limited to the listed checked-in explicit-CXF variants and do not imply arbitrary ASHRAE G36 composite support.”

Concretely, what exists today is:

  • 43 pre-specialized runtime variants (runtime_sequences, all status supported-runtime-sequence) over 31 distinct canonical class paths.
  • 3 hand-authored fixture-only fragments (fixture_only_sequences, status supported-fixture-only): ahu_supply_air_temp_reset, ahu_economizer, and vav_single_zone. Each carries canonical_g36_class_path_status: "fragment-of-canonical-source-not-runtime-sequence" — they are pre-flattened CXF graphs built from supported CDL elementary blocks, with source-reviewed-fragment evidence, and they make no canonical runtime-sequence claim.

All of them are pre-flattened CXF at specific parameterizations. A variant is a fixture at a fixed set of parameter values, not a general instantiation of the class.

The support vocabulary itself is defined at tools/reference-catalog/README.md:77-86. Note that one of its three terms, supported-import-fixture, currently labels zero rows — grepping the G36 catalog for that string returns no hits. It is defined vocabulary, not present state.

The promotion bar

A canonical class path is promoted to supported-runtime-sequence only once all six of these exist (tools/reference-catalog/README.md:77-80), and each runtime row carries the corresponding field:

RequirementField on the catalog row
Canonical Buildings.Controls.OBC.ASHRAE.G36.* class pathclass_path
Source provenancesource
Supported parameter variantssupported_variant
Fixturefixture
Deterministic golden tracegolden_trace, determinism_provenance
Independent oracle evidenceoracle_reference, oracle_test

A missing element is a missing promotion. That is the bar, and it is why the supported set is small.

The engine does not read Modelica

The engine executes the block graph that CXF hands it. It does not parse or flatten Modelica .mo sources. oce-flatten is a reserved seam and an identity passthrough today: CXF arrives already flattened and monomorphic, the oce-cxf resolver owns lowering, and full Modelica elaboration — parameter propagation, expression folding, conditional-instance removal, replaceable/redeclare/extends — is explicitly deferred (crates/oce-flatten/src/lib.rs:2-20). If your sequence exists only as .mo, something upstream has to produce CXF first.

47 fixture documents is not 47 sequences

crates/oce-conformance/tests/fixtures/golden/g36_traces/ holds 46 .csv traces and 46 matching .prov.json provenance records — 92 files. EXPECTED_G36_FIXTURES at crates/oce-cxf/tests/export_g36_roundtrip.rs:46 pins 47 CXF documents: those 46 catalog fixtures plus member_list_interface.jsonld, a resolver contract fixture with no conformance trace or G36 catalog claim.

The 46 catalog fixtures are configurations, not 46 distinct G36 sequences. Across the 43 runtime variants, the 31 distinct canonical class paths distribute like this:

  • 29 class paths appear once;
  • …Economizers.Subsequences.Modulations.ReturnFan appears twice;
  • Buildings.Controls.OBC.ASHRAE.G36.Generic.AirEconomizerHighLimits appears 12 times.

Those 12 are the air-economizer high-limit family: 4 ASHRAE 90.1 variants (differential, and fixed dry-bulb at 18 / 21 / 24) and 8 Title 24 variants (4 differential offsets and fixed dry-bulb at 21 / 22 / 23 / 24). Twelve fixtures, one class, twelve parameterizations.

So the honest reading is: 47 checked-in CXF documents comprise 46 catalog configurations covering 31 canonical G36 class paths plus 3 non-canonical fragments, and one resolver contract fixture. Any count of distinct sequences is smaller, and a public-facing number must say which set it means.

What the coverage is evidence of

Breadth of fixtures is not the same as correctness against the standard, and this repo separates the two deliberately. The evidence layers — engine-self-output determinism goldens, the per-PR structural diff against vendored modelica-json translations, and the oracle layer generated behind a code-dependency firewall — are described in ../README.md and ../TESTING.md.

The load-bearing limitation, stated plainly: no sequence here has been executed against an external Modelica / Buildings toolchain. Scoped OpenModelica evidence covers one exhaustive CDL.Logical.Nand Boolean case and one stateful CDL.Logical.Toggle event schedule, but no numeric tolerance or broader sequence behavior. The global Tier-3 report remains skipped, and no number on this page stands in for that deferred coverage.

For what happens when you export a loaded sequence back out to CXF, see cxf-round-trip.md.