The CXF composite-subset import contract

This is the canonical statement of which nested-composite CXF shapes the Open Control Engine import accepts and rejects. It is written for the author of an external CXF-emitting tool who has never read the engine source. The behavior described here is what oce_cxf::import_cxf — and therefore Engine::load_cxf in the oce-api facade — enforces; every rule is pinned by tests against the checked-in conformance corpus (see Testing your emitter).

Scope: this contract covers the composite subset of CXF lowering — how S231:containsBlock hierarchies flatten, which hierarchy shapes reject, and the document-wide rejection of active array-valued connector and block-instance nodes. Other leaf-block semantics, connector typing, and post-lowering validation (unit checks, single-assignment) have their own diagnostics and are out of scope here.

Resource bounds are part of this engine’s accepted subset, not CDL semantics. containsBlock nesting is limited to 64. Boundary lowering is iterative and permits at most 64 non-top boundary hops per path, 65,536 target examinations, and 8 MiB of aggregate target-IRI bytes across boundary walks in the document. Exceeding a boundary limit returns MalformedDocument without constructing a partial flat graph. Ordinary direct leaf wiring does not consume the boundary-work budgets.

How rejections are reported

Every rejection is a diagnostic with three parts:

  • a DiagCode (a stable kebab-case code string, e.g. malformed-document),
  • an optional subject (the @id of the offending node, where one exists),
  • a message.

The rejecting rules below — except Rule 6, whose rejections are generic diagnostics with no tag — are contract rules: their messages begin with a stable machine-readable tag of the form composite/<rule-id>: (note the single trailing space after the colon). Match rejections with message.starts_with("composite/<rule-id>: "); the rest of the message is human prose and may change. The tag-to-code mapping is published twice — in the rule catalog table below and as the machine-readable artifact tools/reference-catalog/oce-cxf.composite-rules.json — and a drift-guard test holds this document, the artifact, and the emitting code to the same catalog identities.

Rules 1 and 3 are non-rejecting classification and ordering rules. They carry no DiagCode, no message tag, and no catalog entry — there is nothing to match, because they never fail. They are stated here because an emitter that misunderstands them produces a model that imports cleanly but means something else.

JSON-LD fragments below are illustrative: they elide @context, connector nodes, and unrelated keys. Complete importable documents live in the conformance corpus.

Active nodes

Source profiles may mark components and connectors conditional (S231:isConditionalComponent: true plus an S231:conditionalExpression guard). At load time the guard is evaluated against the owning composite’s own grounded parameters and constants; a false guard makes the node — and, recursively, its inputs, outputs, parameters, constants, and contained blocks — inactive. Everything else is active.

Rules 3, 4, 5, and 7 do not traverse inactive child components, so their whole subtree drops out of the leaf order. During lowering, an active composite’s own scope excludes parameter or constant declarations marked inactive — an inactive array-valued declaration does not reject. Leaf parameter binding is different: an active leaf grounds its ordinary S231:hasParameter and S231:hasConstant declarations, and its node-bearing classified S231:hasInstance parameter members, without filtering activity. Banned Modelica keys or S231:isReplaceable on an inactive node are tolerated. Root classification (rule 2) does not consult activity. Connections are not exempt: an active connection into or out of an inactive node rejects with the generic inactive-conditional-node diagnostic — prune conditional structure so inactive nodes take their connections with them.

Rule 1 — Composite discriminator (non-rejecting)

A node is a runtime composite if and only if its S231:containsBlock list is non-empty AND its @type does not resolve to a registered leaf block class. A node whose @type resolves to a registered class is a leaf even when it carries S231:containsBlock — the carve-out that keeps protected implementation children out of composite classification. Classification never rejects; rule 1 has no DiagCode.

@type resolution operates on the @context-expanded form: the token is first expanded against the document @context (a CURIE with a declared prefix becomes its absolute IRI; anything else stays as written — a typing token is never refused), then take the fragment after the last # (the whole string when there is no #), strip a leading Buildings.Controls.OBC., and look the remainder up in the native block registry (published as tools/reference-catalog/oce-blocks.registry-manifest.json). So http://example.org#Buildings.Controls.OBC.CDL.Reals.Add — or the compact ex:Buildings.Controls.OBC.CDL.Reals.Add under "ex": "http://example.org#" — resolves to the registered class CDL.Reals.Add and is a leaf; S231:Block (expanded, http://data.ashrae.org/S231P#Block) or a vendor class path resolves to nothing and — with children — is a composite. Note the contrast with rule 7: identities and typing tokens expand; property KEYS match by suffix — the banned-key and array-marker matching below stays on the term after the last :, #, or /, whatever the spelling.

{ "@id": "…#M.sub", "@type": "http://…#Vendor.Sequences.ScaleAndForward",
  "S231:containsBlock": { "@id": "…#M.sub.gain" } }

is a runtime composite, while

{ "@id": "…#M.con", "@type": "http://…#Buildings.Controls.OBC.CDL.Reals.Sources.Constant",
  "S231:containsBlock": { "@id": "…#M.con.protected" } }

stays a leaf: it imports as a normal CDL.Reals.Sources.Constant block and the protected child is elided (corpus fixture accepted/registered_leaf_carveout.jsonld).

Rule 2 — Single top root (rejects: composite/root-count)

After classification, exactly one runtime composite must be unreferenced by any other runtime composite’s S231:containsBlock. Zero candidates, or two or more, reject with composite/root-count (DiagCode malformed-document). With two or more candidates the message enumerates every candidate in @graph order and the first candidate is the subject. With zero candidates the diagnostic carries no subject — there is no candidate to name.

Normative consequence: a pure composite containsBlock cycle (every composite referenced, no root at all) classifies as zero roots and is reported as composite/root-count, never as composite/contains-cycle (corpus fixture rejected/pure_cycle.jsonld). The cycle detector of rule 4 only runs below a valid single root.

{ "@id": "…#M",  "@type": "S231:Block", "S231:containsBlock": [ … ] },
{ "@id": "…#M2", "@type": "S231:Block", "S231:containsBlock": [ … ] }

rejects with subject …#M and a message ending found 2 candidate roots: …#M, …#M2 (corpus fixture rejected/multi_root.jsonld).

Rule 3 — Nesting traversal order (non-rejecting)

Active composite children lower depth-first in S231:containsBlock array order; inactive children are skipped along with their entire subtrees. This flat leaf order assigns BlockId and block decl_order, not authored connector IDs. Authored connectors are numbered by their own @graph positions. Non-rejecting; no DiagCode.

"S231:containsBlock": [ { "@id": "…#M.sub" }, { "@id": "…#M.post" } ]

lowers …#M.sub’s leaves (depth-first) before …#M.post.

Ordering and identity contract

This table is the OCE executable profile, not a general JSON-LD ordering guarantee. OBC CXF §8.2 defines containsBlock as a relation between blocks; it does not define the executable array-order semantics below. The OBC code-generation example (§11.3) shows authored arrays and describes modelica-json recursively flattening composites to elementary blocks. Neither that example nor its displayed order establishes a general producer-order guarantee.

Order-bearing means a permutation can change the resolved vectors, port meaning, diagnostics, export bytes or executable compatibility; it need not change numerical outputs. Normalized means the stated permutation does not change the specified result. Derived storage is a dense position inside one resolved executable, not a durable external identity. Authored identity is an expanded IRI/name maintained by the producer and used by the host, not an array offset.

SurfaceClassificationExecutable rule and identity consequence
JSON objects and context spellingNormalizedObject-key/map iteration order carries no executable meaning. Equivalent supported compact/expanded identity and typing tokens, singleton relation spellings, and equivalent context maps resolve alike. Context redefinition order and unsupported JSON-LD features are not covered by this equivalence. Structural property names must still use the supported spelling; this is not arbitrary JSON-LD canonicalization.
@graph node arrayOrder-bearingAuthored instance connector nodes receive ConnectorId and connector decl_order in surviving node order. Boundary definitions follow boundary node order; synthesized connector groups use owner node position. Moving only a leaf’s node does not replace containsBlock as the source of block order. Root-count candidates also follow node order.
containsBlockOrder-bearingActive leaves lower depth-first in child array order, assigning BlockId and block decl_order. Permuting siblings can change schedule tie-breaks, export, state compatibility and replay content. Authored connector node positions do not move merely because containment order changes, but their block owners can receive different IDs.
Named leaf hasInput / hasOutputNormalizedWhen all ports on a side name the class’s declared ports, they bind in class-signature order, regardless of member-array order. Dense connector IDs still follow @graph. Partial name matches refuse rather than guessing.
Positional/unnamed leaf portsOrder-bearingWhen no declared names match, ports bind positionally; classes without declared names also bind positionally. A same-kind swap can change meaning without changing arity or types.
Composite own hasParameter + hasConstantNormalized for accepted scopesOne mutual dependency-ordered scope, including forward references across the two lists. Permutations preserve the accepted graph and guard decisions. Rejected cycles/duplicates retain rule IDs and participant sets, not necessarily subjects or message order; see Rule 5.
Leaf values and dimensionsOrder-bearing where Rule 5 specifiesLeaf declaration chains are not composite mutual scopes. Values use enclosing-first lookup, earlier sibling fallback and no forward sibling grounding; dimensions use nearest-wins lookup. Do not generalize composite declaration-order independence to leaf chains.
isConnectedToOrder-bearing, with orientation normalizationAuthored connection sources follow @graph; targets follow each source’s array. Re-anchored relations follow the orientation rules in Rule 6; node-less derived sources follow authored sources in derived connector order. Direct target permutations can alter export content while leaving executable compatibility unchanged because the state manifest canonicalizes the edge set.
Boundary loweringNormalized fanout; order-bearing node positionsexternal_inputs re-key by (boundary input node position, ConnectorId); fanout target-array permutation does not reorder them. Pass-through pairs re-key by (input boundary node position, output boundary node position). Declared input/output definitions follow boundary @graph order. Boundary hops and composite nodes disappear, while declared boundary IRIs retain their public IO role.
hasInstance member arrayNormalizedArray order is load-bearing for nothing: derived ports use names/class signature, classified parameters append in class-signature order, and synthesized connectors append after authored connectors ordered by (owner @graph position, class-signature position). This does not make owner node order or authored connector node order inert.
Inactive conditionalsPrunedInactive children and entire subtrees contribute no leaf or connector positions. Moving an inactive child among active siblings does not move the active order. Active connections referencing inactive nodes still refuse; pruning is not permission to leave dangling wiring. See Active nodes for declaration/guard exceptions.
Resolver diagnosticsDeterministically finalizedSort by numeric connector dense ID first (including recognized connector#N subjects), then subject, code string and message. Non-connector subjects use the final ID bucket: no subject before named subjects, then lexical subject/code/message order. Early failures with no connector index use that non-connector handling. Severity is not a sort key. Export warnings retain their separate block/cascade order, not this resolver sort.
ExportDerived from ModelGraph vectorsEmit the synthetic root, surviving blocks and their parameters, surviving connectors, then boundary nodes in their vector-derived order. Deferral filters the survivor cone without lexically sorting it. Export is flat, not source recovery; a partial export tag is not whole-model identity. See the round-trip contract.
Dense IDs versus authored identityDerived storage versus stable authored identityBlockId, ConnectorId, decl_order, schedule/vector positions and synthetic positional port names are never stable external identities. Hosts key by authored expanded IRI/name, preserving that identity across producer revisions deliberately. Authored identity does not imply executable compatibility: unchanged names can accompany incompatible storage/order. Export content identity, state compatibility and replay identity remain distinct.

Emitter guidance and qualification limits

Emit deterministic @graph, containsBlock, positional ports, leaf declaration chains and connection arrays; preserve those orders across exports of the same source. Do not run a generic RDF/set sort over them and assume it is executable-neutral. Prefer declared port names over positional binding. Compare both authored-name inventories and the order-sensitive executable contract; identical names alone do not qualify a state restore or replay. Boundary fanout and named-port normalization are specific rules, not permission to reorder every array.

The executable oracle here is OCE-only. Studio producer order is unqualified: no Studio source or producer run is accepted as evidence by these tests. The OCL routine compiler does not emit CXF and is not a qualified producer for this contract. Downstream qualification must run the actual producer against these cases; neither is a prerequisite for freezing the OCE contract. For issue #249 accounting, this establishes ordering/identity evidence only. It introduces no parameter-shadowing policy, option or diagnostic, and does not close that separate policy question.

Rule 4 — Acyclicity (rejects: composite/contains-cycle)

The containsBlock graph reachable from the root through active children must be acyclic. A cycle rejects with composite/contains-cycle (DiagCode malformed-document); the message names all participants in traversal path order, ending at the re-entered id, and the re-entered id is the subject.

Normative consequence: one diagnostic per re-entry. A cycle reachable via k distinct paths yields k truthful path-ordered diagnostics; a consumer must not assume one diagnostic per structural cycle (corpus fixture rejected/diamond_cycle.jsonld: one cycle, two paths, two diagnostics). The degenerate self-loop (A contains A) reports the two-entry list …#A -> …#A (corpus fixture rejected/self_loop.jsonld).

{ "@id": "…#R", "@type": "S231:Block", "S231:containsBlock": { "@id": "…#A" } },
{ "@id": "…#A", "@type": "S231:Block", "S231:containsBlock": { "@id": "…#B" } },
{ "@id": "…#B", "@type": "S231:Block", "S231:containsBlock": { "@id": "…#C" } },
{ "@id": "…#C", "@type": "S231:Block", "S231:containsBlock": { "@id": "…#A" } }

rejects with subject …#A and message tail …#A -> …#B -> …#C -> …#A (corpus fixture rejected/reachable_cycle.jsonld).

Rule 5 — Parameter-scope inheritance (rejects: composite/array-parameter, composite/declaration-cycle, composite/duplicate-declaration)

A composite’s active S231:hasParameter and S231:hasConstant bindings form one mutual scope: every binding’s value may reference any sibling of either kind, declared earlier or later — declaration array order carries no meaning for the composite’s own scope. A document that loads does so with a byte-identical imported model and an identical diagnostic vector under any permutation of the two arrays; a document these rules refuse refuses under every permutation with the same rule ids and the same participant sets — only a diagnostic’s subject may relocate, because subjects follow the chained declaration order that permutation changes. Inside an own binding’s value, an own local name always denotes the own sibling, shadowing a same-named binding of an enclosing composite; only names with no own binding fall through to the enclosing scope chain (innermost composite first). The grounded scope is inherited by every child composite and leaf. Identifier-shaped text inside an expression String literal is data, not a sibling reference: S231:value: "\"b\"" creates no dependency on an own declaration named b. Three shapes reject:

  • A reference cycle among a composite’s own bindings — including the length-1 self-reference x = "x * 2", which is never an enclosing read — rejects with composite/declaration-cycle (DiagCode malformed-document): one diagnostic per distinct cycle per chain evaluation. Like contains-cycle, a composite reachable via multiple containsBlock paths is evaluated once per path (enclosing scopes can differ per path), so the same cycle can surface once per visit — consumers must not assume one diagnostic per structural cycle document-wide. Subject = the participant earliest in the params-then-constants chained declaration order; the message’s arrow list is the participant ring in chained declaration order closing on the first (…#M.a -> …#M.b -> …#M.a) — not the discovered edge path. Bindings outside the cycle still ground (maximal progress); cycle members keep their own binding’s name — masking a same-named enclosing binding — but are absent from the scope, so a reference to one fails with a generic grounding-failed.
  • One local name declared twice in one composite’s own chain rejects with composite/duplicate-declaration (DiagCode malformed-document): one diagnostic per occurrence beyond the first in chained order (three declarations of one name emit two), subject = that later occurrence, message naming it and the first occurrence’s @id. The first occurrence stays a normal binding.
  • An array-valued (S231:isArray: true) active parameter or constant on a composite rejects with composite/array-parameter (DiagCode non-subset-construct); the subject is the parameter node.

Leaf members are a different level and keep their order-sensitive contract: a leaf member’s value reference resolves enclosing-first — when the name is bound both in the enclosing scope chain and by an earlier sibling member, the enclosing binding wins, and within each region the most recently grounded binding shadows earlier ones (issue #239) — so a leaf member’s forward reference to a sibling member still fails grounding. A leaf dimension reference (S231:sizeOfDimensions) still resolves nearest-wins over the undivided scope, so there a sibling binding shadows a same-named enclosing one — when the sibling is grounded earlier; member array order still decides the dimension reading (for an enclosing-bound name, values are order-invariant under member order, dimensions are not). When the two readings of one name disagree on an array’s shape, the element-count divergence refuses with grounding-failed (both counts in the message); a value divergence with a matching count is silent, exactly like the scalar path.

Conditional-guard specialization evaluates guards against the same own-scope semantics through the same mechanism, so guard decisions are equally order-independent. The specialization pass also grounds leaf declaration chains that carry conditional members; on that pass, generic grounding machinery is non-emitting, and the two tagged rules above apply to composite chains only — a leaf chain’s bindings are member modifications (the leaf level described above), so a cycle or duplicate among them produces no tagged finding there: the participants simply fail to ground in the guard scope. A composite-chain defect visible to both passes is reported once, from the lowering view; a composite chain only the specialization pass grounds (for example one pruned by a false guard) still surfaces through the two tagged rules; and a guard that genuinely cannot evaluate refuses through the guard’s own diagnostics — never as a bare grounding-failed. A leaf with a legal array parameter plus a conditional member therefore loads (corpus fixture accepted/leaf_array_parameter_conditional_member.jsonld), and so does the leaf identity-modification idiom — a leaf parameter samplePeriod = "samplePeriod" reading the same-named enclosing composite parameter, beside a conditional member (corpus fixture accepted/leaf_identity_parameter_modification.jsonld, the member value grounding enclosing-first per the leaf rules above); the specialization model itself — what a guard means and how pruning propagates — is unchanged.

References use the local name — the segment after the last . of the binding’s @id — so two same-named bindings at different nesting levels shadow (own-scope-wins for the composite’s own bindings, enclosing-first for leaf member values, nearest-wins for dimensions), while two same-named bindings in one composite’s own chain reject under composite/duplicate-declaration. Give bindings distinct local names unless shadowing is intended; the corpus does. Element names minted by leaf array expansion (k[2] → k_1, k_2) shadow like any sibling binding: a later member’s value reference to k_1 reads a same-named enclosing binding when one exists, not the minted element, while a same-named sibling parameter collides and refuses (ArrayFlattenCollision). Because grounded values feed block construction, own-scope resolution can change what a document means, so a constructed document that imported under the older order-sensitive reading can refuse under this rule (a cycle or a duplicate) or ground differently (a forward or shadowed sibling reference). Measured against the pre-change base (43d8a13, which held 147 checked-in CXF documents: 103 crate fixtures plus 44 vendored modelica-json translations), all 103 crate documents are byte-identical in import outcome under the rule; 12 vendored documents — every one still refusing on unrelated grounds — shed 48 grounding-failed diagnostics in exactly the two ruled classes (forward sibling references now grounding, and specialization-pass generic machinery going non-emitting), with zero new diagnostics anywhere. The tree now holds 205 documents (161 crate plus 44 vendored). The wider reach exists off-corpus.

{ "@id": "…#M", "@type": "S231:Block",
  "S231:hasParameter": [ { "@id": "…#M.kBase" }, { "@id": "…#M.kTop" } ], … },
{ "@id": "…#M.kBase",      "S231:value": { "@value": "0.25", "@type": "…#double" } },
{ "@id": "…#M.kTop",       "S231:value": "kBase + 0.25" },
{ "@id": "…#M.sub.kInner", "S231:value": "kTop" }

grounds the sibling reference kTop to 0.5; the child composite’s constant kInner (declared under …#M.sub via S231:hasConstant) inherits it through the parent scope, and the leaf parameter "S231:value": "kInner" grounds the chain’s end — the kBase → kTop → kInner → gain.k chain of corpus fixture accepted/minimal_nested.jsonld.

Rule 6 — Boundary elision (rejects: generic diagnostics)

Composite boundary connectors are lowered away. A boundary input rewires to the child connectors it drives; the top composite’s boundary inputs surface as the imported model’s external inputs. A boundary output of a non-top composite is followed through to its final targets. A boundary output of the top composite is elided outright: its @id appears on no connector in the flat model, and a leaf output whose only target is a top boundary output ends with no connection at all — the driving leaf connector remains, carrying no source @id. The composite node itself never becomes a runtime block. Boundary elision rejects invalid direction (DirectionMismatch), mismatched value types (TypeMismatch), unresolved endpoints or missing boundary nodes (UnresolvedReference), and boundary datatype declarations that cannot be derived (MalformedDocument).

CXF §8.2 permits either endpoint of a connection to carry S231:isConnectedTo; subject position does not encode signal direction. Before boundary elision, the importer therefore derives each endpoint’s source/sink role from its owning block, its port direction, and the peer’s location inside or outside that owning composite, then re-anchors reverse-spelled edges on their canonical driver. This is an orientation rule over the existing connector and containment data, not a new runtime model. Edges whose roles cannot be derived — a dangling or non-connector peer, a port claimed by two owners, non-tree containment — as well as same-polarity (contradictory) pairs and reverse spellings whose canonical driver has neither a node nor a synthesized connector identity, are left exactly as authored and reject under the existing Rule 6 diagnostics when the relation survives lowering. If boundary elision would erase an active relation that cannot be kept or swapped, the importer defers a direction diagnostic until the bounded boundary walk succeeds. This applies whether the boundary is the authored source or target. An active elided boundary source targeting an inactive node similarly retains the ordinary inactive-node refusal. A node-less output listed by hasInstance, or padded from an omitted declared output, can be a canonical driver; its lowered edges follow authored sources in derived connector order. Re-anchoring never invents or silently removes a relation: an input driven twice still rejects. Authoring the same relation from both endpoints collapses when either spelling required re-anchoring. In particular, both directions between one composite’s input and output denote one pass-through relation, not a boundary cycle.

The boundary walk preserves canonical target order and duplicate multiplicity below its resource limits. It checks an active-path cycle or missing boundary node before the hop limit, so those shapes retain their UnresolvedReference outcome at the boundary. The target-examination budget counts inactive, terminal, dangling, and cycle-revisit targets before classification; it prevents a shallow branching graph from expanding without bound even when every path is short. The aggregate byte budget also charges an authored target that orientation turns into a synthesized canonical driver, before the completed target lists are cloned. Resource-limit diagnostics omit the attempted target subject to avoid an additional untrusted IRI copy at refusal. Deferred diagnostics, including the inactive-target variant, also omit their subject. If bounded expansion repeats one missing endpoint through ordinary or boundary-specific orientation, the importer emits one unresolved-reference diagnostic for that endpoint rather than copying its subject once per edge.

What an emitter must NOT expect to survive import: composite nodes as blocks, boundary connector hops, nesting depth, or the authored bytes. The import-parity boundary is flat by contract: re-importing an exported document reproduces the flat ModelGraph — never the original nested/authored bytes. Round-tripping a nested document through the engine and comparing bytes will always “fail”; compare imported models instead.

{ "@id": "…#M.u",     "@type": "S231:RealInput",
  "S231:isConnectedTo": { "@id": "…#M.sub.u" } },
{ "@id": "…#M.sub.u", "@type": "S231:RealInput",
  "S231:isConnectedTo": { "@id": "…#M.sub.gain.u" } }

imports as one external input feeding …#M.sub.gain.u directly; …#M.sub.u is gone.

Rule 7 — Rejected constructs (rejects: composite/banned-modelica-key, composite/replaceable, composite/array-connector, composite/array-instance, composite/vector-port-instance, composite/unsupported-instance-member, composite/colliding-member-identity)

Six Modelica construct keys are banned on any active node: redeclare, constrainedby, extends, extendsFrom, moSource, modelicaSource. Matching is on the term after the last :, #, or / in the key, so the bare (extends), prefixed (S231:extends), and absolute-IRI (http://data.ashrae.org/S231P#extends) spellings all reject. A banned key rejects with composite/banned-modelica-key (DiagCode non-subset-construct); the subject is the owning node and the message names the key exactly as authored.

S231:isReplaceable: true on any active node rejects with composite/replaceable (DiagCode unresolved-polymorphism). The subject is the replaceable node. Replaceable components must be resolved to concrete classes before export.

An active connector — any node referenced by an active node’s S231:hasInput or S231:hasOutput list, anywhere in the document, whether or not the referencing node is reachable from the top-level root, or any member of an active derivation-shaped node’s S231:hasInstance list (a containsBlock referent that is not a runtime composite, declares neither port list, and carries a member list) — rejects when it carries an array marker. The member source matches the existing sources on reachability and is narrower only in shape: an orphan node’s list and a runtime composite’s list contribute nothing, where the existing sources take any active node’s list at all; the scan stays reference-based and class-independent on both. The markers: S231:isArray: true or any S231:sizeOfDimensions. Marker keys match on the term after the last :, #, or /, like the banned-key matching above, so absolute-IRI spellings reject too. The rejection is composite/array-connector (DiagCode non-subset-construct) with the connector node as subject. Flatten connector arrays to one connector per element.

An active block instance — any node referenced by an active node’s S231:containsBlock — rejects under the same array markers as composite/array-instance (DiagCode non-subset-construct) with the instance node as subject. Flatten block arrays to one instance per element. A node referenced as both connector and instance receives both rejections, and a S231:hasParameter listing does not exempt it. Array-valued parameters on a composite are governed by Rule 5; an array-valued parameter on a leaf block is preserved and expanded, not rejected. Inactive conditional subtrees are invisible to these checks.

Three rules govern the hasInstance interface derivation (an instance declaring neither hasInput nor hasOutput and carrying a S231:hasInstance list derives its interface from the list; a node declaring either port list keeps its own interface). Each refusal skips the instance’s derivation whole — the tagged rejection replaces the generic arity mismatch rather than doubling it:

  • composite/vector-port-instance (DiagCode non-subset-construct, subject the instance node, one per instance): the resolved class publishes no declared port names — its port count is a function of a parameter, so one member stands for N scalar connectors and this subset derives scalar interfaces only. A document declaring the same class’s ports explicitly through hasInput/hasOutput is untouched.
  • composite/unsupported-instance-member (DiagCode non-subset-construct, subject the member IRI, one per offending member): a member outside its owner’s namespace (not <owner>.<oneSegment>), a member that is itself a block instance, or a member whose local name is neither a declared port nor a declared parameter of the class.
  • composite/colliding-member-identity (DiagCode non-subset-construct, subject the colliding IRI, one per collision): a synthesized connector identity that is already an @graph node or is minted twice for one owner, or a parameter name declared twice for one instance — across its classified members or against its own hasParameter/hasConstant list.
{ "@id": "…#M.c2", "@type": "…MultiplyByParameter",
  "S231:isReplaceable": true,
  "redeclare": "…#SomeBase", … }

rejects twice: once under composite/banned-modelica-key naming `redeclare`, once under composite/replaceable (corpus fixtures rejected/banned_key_*.jsonld, rejected/replaceable.jsonld).

Rule catalog

The contract identities, mirroring tools/reference-catalog/oce-cxf.composite-rules.json (catalog order). Rules 1 and 3 do not appear here because they are non-rejecting. Rule 6 has no composite/ rule identity; its rejections are generic diagnostics.

RuleRule idDiagCodeMessage prefix
2root-countmalformed-documentcomposite/root-count:
4contains-cyclemalformed-documentcomposite/contains-cycle:
7replaceableunresolved-polymorphismcomposite/replaceable:
7banned-modelica-keynon-subset-constructcomposite/banned-modelica-key:
5array-parameternon-subset-constructcomposite/array-parameter:
7array-connectornon-subset-constructcomposite/array-connector:
7array-instancenon-subset-constructcomposite/array-instance:
5declaration-cyclemalformed-documentcomposite/declaration-cycle:
5duplicate-declarationmalformed-documentcomposite/duplicate-declaration:
7vector-port-instancenon-subset-constructcomposite/vector-port-instance:
7unsupported-instance-membernon-subset-constructcomposite/unsupported-instance-member:
7colliding-member-identitynon-subset-constructcomposite/colliding-member-identity:

Every message prefix is composite/<rule-id>: — colon, then one trailing space (U+0020), which markdown table cells cannot render unambiguously. Match with starts_with("composite/<rule-id>: "), trailing space included. The drift-guard test (crates/oce-cxf/tests/composite_contract_doc.rs) checks the Rule id and DiagCode columns of this table against the catalog artifact and derives the prefix from the rule id; the prefix column above is display-only.

Generic diagnostics

Three diagnostics that can accompany or replace a contract rejection are shared import machinery, deliberately untagged (no composite/ prefix, no catalog entry):

  • unresolved-reference — a containsBlock child, parameter node, composite @id, or a connection/boundary reference naming a hasInstance member of an instance whose interface was not derived (an unregistered class, or a composite/vector-port-instance refusal), referenced but not resolvable. A classifiable member itself is never reported under this code: a node-less port member becomes a synthesized connector and a node-less parameter member refuses as grounding-failed at derivation.
  • grounding-failed — a parameter value that cannot ground: a missing S231:value (values are required — Ground mode, on the hasParameter/hasConstant route and the hasInstance member route alike), an unknown identifier (including a reference to a cycle-refused sibling, or a leaf member’s forward reference to a later sibling member), or an expression error.
  • conflicting-interface-declaration — an instance declaring hasInput/hasOutput beside a hasInstance list whose class-declared names its own routes do not carry (a warning; compared one-directional, list minus own), or one parameter name valued differently on the two routes (an error — two values for one name state a contradiction).

They are not contract rules because they do not describe a composite shape; they fire anywhere in the import pipeline. Match them by DiagCode, not by message. The conditional-pruning rejection inactive-conditional-node (see Active nodes) is generic machinery in the same sense — untagged, no catalog entry.

Acceptance preconditions

A document that satisfies rules 1–7 must also meet the general import preconditions before it loads warning-free:

  1. Exactly one top composite, and its @type must be unregistered (S231:Block works). A registered leaf standing alone — even one with containsBlock — classifies as zero composites and rejects under rule 2 with zero candidates.
  2. Every parameter and constant carries a S231:value (missing values are grounding-failed). A parameter declared through a S231:hasInstance member is covered too: a valueless or node-less member named after a declared parameter refuses the same way.
  3. Every leaf @type resolves to a registered block class (else class-not-found).
  4. Accepted means warning-free: the corpus drivers assert an empty diagnostic report, not merely a non-error one.

Testing your emitter

The engine tests itself against a checked-in conformance corpus; point your emitter’s output at the same files and drivers.

  • Corpus: crates/oce-cxf/tests/fixtures/composite_contract/{accepted,warned,rejected}/*.jsonld, one fixture per contract behavior, indexed in the corpus README.md. The warned/ category holds documents that load successfully with a pinned advisory vector — untagged import machinery such as undriven-boundary-output, not a composite-shape rule.
  • Accepted-fixture goldens (byte-exact ModelGraph renders): crates/oce-cxf/tests/fixtures/golden/composite_contract_*.modelgraph.txt.
  • Resolver-layer drivers: cargo nextest run -p oce-cxf --test composite_contract_corpus
  • Full-pipeline (Engine::load_cxf) drivers: cargo nextest run -p oce-api --test conformance composite_contract
  • Doc/catalog drift guard: cargo nextest run -p oce-cxf --test composite_contract_doc
  • Ordering oracle: resolve_ordering.rs, with independently authored compact/expanded documents, hand-listed block/connector/edge and export survivor orders, object-key reversal, declaration/member permutations, and exact ordered diagnostic vectors. These are OCE profile expectations, not an external numerical oracle.
  • Public identity: composition_identity.rs checks complete export content tags and public state-restore compatibility. It distinguishes normalized permutations, incompatible containment/connector/positional-port changes, and direct fanout permutations that change content but preserve executable compatibility. It neither exposes private fingerprints nor changes format revisions.
  • Complementary contract evidence: resolve_external_input_order, resolve_declaration_scope, resolve_param_precedence, and resolve_composite_orientation retain boundary, leaf-scope and orientation cases. fixture_structural_oracle independently checks the vendored corpus’s structure, not these OCE array-order semantics; fixture_port_order and vendored_corpus_delta retain their input-hygiene and diagnostic-delta roles.

To check a document your tool produced:

  • Rejected: drop it under rejected/, add a README index row, and add its expected (DiagCode, subject, message) triples to the pin tables in both drivers (expected_rejections() in composite_contract_corpus.rs, COMPOSITE_REJECTIONS in crates/oce-api/tests/conformance.rs).
  • Warned: drop it under warned/, add a README index row, add its exact complete warning vector to expected_warnings() in composite_contract_corpus.rs, and add its ordered warning triples to the composite_warnings() table in crates/oce-api/tests/conformance.rs — the end-to-end warned driver is table-driven and its on-disk listing pin is taken over that table, so a warned fixture cannot land half-wired.
  • Accepted: drop it under accepted/, add a README index row, add the pair to the ACCEPTED table in composite_contract_corpus.rs — the golden filename convention is tests/fixtures/golden/composite_contract_<fixture-stem>.modelgraph.txt — then bless the golden with OCE_BLESS=1 cargo test -p oce-cxf --test composite_contract_corpus accepted_fixtures_match_their_blessed_modelgraph_goldens_byte_exactly and review the blessed bytes before committing. The oce-api driver picks the new file up automatically and requires the warning-free load.

The corpus completeness tests fail on any unindexed or unpinned fixture, so a fixture cannot land half-wired.

The 44 vendored modelica-json translations under third_party/modelica-buildings-cdl/cxf/ are additionally held to a per-document characterization capture (crates/oce-cxf/tests/vendored_corpus_delta.rs): per-DiagCode counts, severities, and duplicate diagnostic triples, re-blessed only deliberately. The hasInstance interface derivation moved that capture in both directions, every increase declared: 904 arity mismatches and 2,579 unresolved references removed, 30 arity mismatches replaced by composite/vector-port-instance, single-assignment arriving at 57 (31 undriven and 8 multiply-driven derived inputs, plus 18 multiply-driven declared boundary outputs assessed for this dialect for the first time), grounding-failed rising 62 → 204 as member values and member connector bounds ground for the first time on class-translation documents, and inactive-conditional-node rising 11 → 44 because pruning now reaches a conditional instance’s listed members as well as its @graph nodes (32 members still carrying active connections, 12 connection targets).