Playbook: Simultaneous Heating & Cooling
| Applies to | AHU-0004, AHU-0005, AHU-0012, AHU-0016, AHU-0025, AHU-0029, AHU-0032, FCU-0007, CLU-01 |
| Fix complexity | Remote fix (70%) · On-site service (30%) |
| Typical time | 30 min remote / 2–4 h on-site |
| Typical cost | $0 remote / $200–$1,500 on-site (actuator replacement) |
| Energy impact | EEM-38: 10–30% of AHU thermal energy. Simultaneous heating and cooling is pure waste with no occupant benefit; common across all building types with heating and cooling coils. |
Adapted from HVAC FDD Reference v1.0, Remediation Playbooks (pp. 153–154).
Step 1 — Verify the fault
- Pull a 24-hour trend of the heating valve command and cooling valve command for the same AHU or FCU on one chart.
- Confirm both commands are above the rule’s configured material thresholds for its configured duration. AHU-0016 and FCU-0007 intentionally use different library defaults; verify the deployed parameters before triage.
- Check data quality flags — rule out bad sensor readings before acting.
- Check for intentional cooling-plus-reheat/dehumidification, freeze protection, valve exercise, commissioning, or mode transition. These states are NO_EVAL for FCU-0007 unless the deployed sequence explicitly says otherwise.
- If position feedback sensors exist, compare command vs. actual position to determine whether the problem is the control sequence (software) or a physical issue (stuck valve).
- Do not price command overlap alone. Quantify only from verified valve position/flow and delivered heating/cooling energy during the overlap.
Step 2 — Remote fix (BAS changes, no site visit)
- First confirm the unit is not designed for intentional cooling-plus-reheat; do not add an interlock that defeats humidity, freeze, or equipment protection.
- Check the ordinary control sequence for a heating/cooling interlock:
- The heating valve should close to 0% before the cooling valve may open, and vice versa. If no interlock exists, add one — the most common fix.
- G36 §5.16 specifies a minimum deadband of 2.8 °C (5 °F) between heating and cooling loops.
- Check for a deadband between the heating and cooling PID loops:
- At least 1 °C (2 °F) between where heating stops and cooling starts; if the loops overlap, insert a deadband.
- For single-duct VAV systems, verify the SAT setpoint is above the reheat lockout temperature before investigating individual zone interlocks.
- Check for stuck manual overrides on either valve command (BACnet priority array). Release any override holding a valve open — among the most common retro-commissioning findings (PNNL-27338).
- Check whether the heating coil has an OAT lockout; if outdoor temps are warm enough that heating shouldn’t run, enable one (typical: disable heating when OAT > 16 °C with 2 °C hysteresis).
- If the AHU serves mixed interior/perimeter zones, verify perimeter reheat is not fighting the central cooling coil — SAT reset (see missing-reset) often resolves this.
Step 3 — On-site service (if remote fix doesn’t resolve)
Only qualified personnel may open panels or work on hydronic valves. Follow the site’s lockout/tagout procedure and never bypass freeze, condensate, pressure, or electrical safeties to clear an FDD finding.
- Inspect the heating valve actuator: command to 0% from the BAS and physically verify full closure; check the mechanical linkage (disconnected linkages are common on older systems); verify normally-open vs. normally-closed — an NO valve opens whenever the actuator loses its signal.
- Inspect the cooling valve actuator with the same checks.
- On pneumatic-to-digital conversions: normally-open pneumatic valves need spring-return actuators; check for air leaks in the tubing — small leaks can prevent full closure.
- If a valve cannot close mechanically, replace the actuator ($200–$800) or valve body ($500–$1,500).
- Check for coil bypass: on older AHUs a face-and-bypass damper can mix hot and cold decks — inspect the bypass damper actuator and linkage.
Step 4 — Confirm resolution
- Monitor both valve commands for 48 hours after the fix.
- Verify both commands do not overlap above their configured thresholds during applicable modes; separately confirm intentional dehumidification still works.
- The fault should clear automatically. FCU-0004/0005 may remain if physical valve leakage persists after the command conflict is fixed.
- Recalculate impact from measured thermal input/output, not command percentage.