TOWER Fault Rules
Cooling tower rules (TOWER-*) are fully library-authored: no HVAC FDD
Reference chapter covers towers. BEE, DOE/PNNL, NREL, ASHRAE, SPX, and EVAPCO
sources corroborate the mechanisms and safety constraints, but they do not
publish portable executable limits for approach/range degradation, loaded-fan
overcooling, proof timing, or basin thermal response. Each card therefore
labels adopted values and site/OEM adoption blockers explicitly.
The first batch’s quantitative grounding remains the committed 4-climate
simulation study (tools/simharness README, “Tower groundwork”): healthy
approach spans 1.6–13.3 °C un-gated purely on VFD fan modulation, which is why
TOWER-0001 is fan-at-capacity gated, while range holds a stable healthy band.
TOWER-0003’s 4–5 starts/hour mechanism is literature-backed. TOWER-0004..0006
add per-fan proof, loaded-fan overcooling, and an explicitly site/OEM-governed
wet-basin freeze watchdog.
Point dictionary: points/tower.points.json
— note the loop-side semantics (tower-leaving = cold = entering condenser
water), the oa_wetbulb host psychrometric obligation, and provisional 223
topology for basin points.
Index
| ID | Name | Sev | Method | Status |
|---|---|---|---|---|
| TOWER-0001 | Tower approach high at fan capacity | 3 | rule | verified |
| TOWER-0002 | Tower range collapse | 3 | rule | verified |
| TOWER-0003 | Tower fan short-cycling | 3 | rule | verified |
| TOWER-0004 | Tower fan proof-of-operation failure | 2 | rule | verified |
| TOWER-0005 | Condenser water overcooling with fan energy | 3 | rule | verified |
| TOWER-0006 | Cooling-tower basin freeze-protection failure | 2 | rule | verified |
Relationships
- CLU-10 (Condenser-Side Degradation): TOWER-0001 is the trigger,
TOWER-0002 and CHW-0005 (chiller condenser approach) the members;
playbooks/cooling-tower-performance.mdis the family playbook. CHW-0005 is the tube-side vs fill-side discriminator: tower approach normal + condenser approach high → clean the tubes, not the fill. - TOWER-0003 stays outside CLU-10 — a drive/control fault, not the degradation syndrome; it shares the playbook’s control-side steps.
- TOWER-0004 and TOWER-0005 stay outside CLU-10. Proof disagreement and overcooling control waste do not share the cluster’s degradation repair contract. TOWER-0004 is direction-sensitive proof context for TOWER-0005; no static whole-rule suppression is safe.
- TOWER-0006 stays independent and synthetic-only. It applies only to a wet, filled basin with monitored heater/equivalent protection and configured site/OEM limits. A basin heater is not protection for external piping.
- The pending primary sources when they are acquired: a CTI/ASHRAE tower chapter for approach/range fault bands, ASHRAE RP-1043 for the chiller condenser-approach threshold.