ERV Fault Rules
Energy recovery ventilator fault detection rules (ERV-*). Source
grounding: HVAC FDD Reference v1.0 ch.15 (Energy Recovery — adapted
authority; see each card’s Deviations section) plus clearly labeled
library-authored operating, proof, and airflow-balance extensions.
Point dictionary: points/erv.points.json.
Index
| ID | Name | Sev | Method | Status |
|---|---|---|---|---|
| ERV-0001 | Sensible effectiveness degradation | 3 | statistical | verified |
| ERV-0002 | Frost protection not engaging | 2 | rule | verified |
| ERV-0003 | Frost protection active above release conditions | 3 | rule | verified |
| ERV-0004 | Recovery device proof-of-operation failure | 2 | rule | verified |
| ERV-0005 | Supply/exhaust airflow imbalance | 3 | rule | verified |
ERV-0001/0002 adapt the reference chapter. ERV-0003..0005 are library-authored: the cards classify every threshold and name their reusable graph precedents.
Applicability and point availability
- Passive plate cores: ERV-0001, ERV-0002/0003 where a frost-state point exists, and ERV-0005 where both device-local flow measurements exist. ERV-0004 is not applicable because the core has no commanded active device.
- Rotary wheels: all five rules may apply. ERV-0004 needs a final wheel-run command and independent rotation/speed proof; command echo is not proof.
- Runaround loops: all five rules may apply where a frost sequence/state exists and temperatures/flows map to both air streams. ERV-0004 binds the loop pump’s final command and independent pump work/rotation proof.
- Point scarcity: enabled/frost flags and three temperatures do not imply command/status proof or two comparable airflow measurements. Omit a rule rather than substitute a high-level enable or an unrelated AHU flow meter.
Relationships
- All rules share the
erv-effectivenessinvestigation order. ERV-0004 also usesproof-of-operationfor command/status diagnosis. - ERV-0003 relates to both existing frost/effectiveness rules but suppresses neither: excessive frost protection can be the real cause of lost recovery.
- ERV-0005’s direction flags identify the air path to inspect;
yFlowOk=falsemeans NO_EVAL, not balanced operation.