AHU-0008 — SAT ≠ MAT in economizer mode
| Status | verified — engine e2ff2f8, cxf:fnv1a128:9a1a1d3f2efeeaa385ba4336b64530a2, 2026-08-17 |
| Severity | 3 |
| Method | rule |
| Phase | 1 |
| Category | COMFORT_ENERGY |
| Confidence | LOW |
| Estimation | QUALITATIVE_ONLY |
| G36 | §5.16.14 FC#8 |
| Clusters | — |
| Suppresses | — |
| Suppressed by | AHU-0028 |
| Related | AHU-0002, AHU-0003, AHU-0010, AHU-0028 |
| Playbooks | sensor-drift |
| Source | HVAC FDD Reference v1.0 §5.8.1 (index; card abbreviated); G36 §5.16.14 FC#8 (text per Addendum u public review); NISTIR 7365 (defaults provenance); PNNL-25985 (EEM-01, sensor recalibration) |
| Operating states | OS#2 (free cooling, modulating OA) — host-gated |
Preconditions (host-enforced): The unit must have a MAT sensor; G36 omits FC#8 where there is none. Evaluate only in OS#2, which G36 Table 5.16.14.2 defines by actuator signature: heating coil = 0, cooling coil = 0, minimum OA position < OA damper < 100%. Outside that state a coil is legitimately working and SAT is supposed to differ from MAT, so the equation means nothing. Supply fan running, since neither temperature describes a stream that is not moving. Per §5.16.14.11 the host suspends evaluation while the AHU is off and for ModeDelay (30 min) after a mode change in any zone group the AHU serves, while the coils and damper are still stroking. Silence this rule while AHU-0028 is active: MAT is an input here and FC-062 is its integrity gate. When any gate is unmet the verdict is NO_EVAL, not healthy.
Outputs:
yFault— True while |sat − fan_rise − mat| has stayed above combined_error for at least alarm_delay
Parameters:
| Name | Default | Unit | CXF path | Description |
|---|---|---|---|---|
fan_rise | 1.0 | °C | fanConst.k | Temperature rise across the supply fan (G36 dTSF). Subtracted from the raw SAT − MAT difference so the comparison is about coil and sensor behavior rather than shaft work. A site that measures its own fan rise — a high-static or direct-drive plenum fan can be well off 1 °C — sets this to the measured value; the threshold is unaffected, since fan rise centers the band and sensor error sizes it. |
combined_error | 3.1623 | °C | devBig.t | Half-width of the band the fan-heat-corrected difference may occupy, composed as the root-sum-square of the two sensor error bands: sqrt(eSAT² + eMAT²) = sqrt(1² + 3²) = sqrt(10) = 3.1623 °C with the G36 Table 5.16.14.5 defaults. Errors add in quadrature rather than linearly because two independent sensors are unlikely to be wrong in the same direction at once. A site with a different MAT accuracy recomputes the root-sum-square: eMAT = 4 °C gives sqrt(1 + 16) = sqrt(17) = 4.1231 °C. |
alarm_delay | 1800.0 | s | persist.delayTime | Continuous fault persistence required before the alarm asserts (G36 AlarmDelay, 30 min) |
Description
In OS#2 the air handler runs as a modulating economizer: both coils are commanded shut, so the only thing between the mixed-air sensor and the supply-air sensor doing any work is the supply fan. Air should leave at the temperature it arrived plus the degree or so the fan puts in. A disagreement larger than the two sensors’ combined error after that fan rise is taken out means something in between is adding or removing heat, or a sensor is not reporting the stream it is mounted in.
This is the one state where the two sensors can be audited against each other at no cost — everywhere else a coil is doing work and SAT is supposed to differ from MAT. The fault is deliberately non-committal about direction: air leaving too warm points at hot water leaking through a seated heating valve, too cold at chilled water doing the same. Either way the plant is serving a coil nobody commanded, which no command-following check can see.
Detection Logic
G36 §5.16.14 FC#8, applies to OS#2 (omitted if the unit has no MAT sensor):
| SAT_AVG − dTSF − MAT_AVG | > sqrt(eSAT² + eMAT²)
with the Table 5.16.14.5 defaults:
| sat − 1.0 − mat | > sqrt(1² + 3²) = 3.1623 °C
yFault = (|sat − fan_rise − mat| > combined_error), sustained for alarm_delay
Block graph (rule.cxf.jsonld):
Fan rise and sensor error do different jobs, which is why they are separate
parameters: fan_rise positions the center of the acceptance band —
the difference the unit is expected to show — and combined_error sets its
half-width. Retuning one does not imply retuning the other. The fan-heat term
is a constant source into a Subtract rather than an AddParameter with a
negative parameter, so fanConst.k holds the physical quantity with its
physical sign and a host that measures a 1.4 °C rise can set 1.4 (precedent:
AHU-0021’s designConst).
G36’s comparison is already strict, so GreaterThreshold reproduces it exactly
and a deviation of exactly 3.1623 °C reads healthy in both. persist requires
30 minutes of continuous violation and any interruption restarts the timer.
Possible Diagnoses
Per G36 §5.16.14 Table 5.16.14.8, FC#8:
- SAT sensor error — cheapest to rule out with a hand-held reference in the supply duct
- MAT sensor error — harder, since a mixed-air sensor can be in calibration and still read a stratified slice of the plenum instead of the mixture (AHU-0028 catches the gross version)
- Cooling coil valve leaking or stuck open — chilled water through a valve commanded to 0 shows up here and nowhere in the command stream
- Heating coil valve leaking or stuck open — the mirror case, and the more expensive one in this state: the unit chose free cooling because outdoor air was useful, and boiler energy is being spent to undo it
Energy Impact
COMFORT_ENERGY, LOW confidence, QUALITATIVE_ONLY — the grades in the reference’s §5.8.1 index row, which maps the fault to PNNL-25985 EEM-01 (sensor recalibration) and publishes savings as sensor-dependent. Nothing is estimated from the rule’s inputs: two temperatures and no airflow give no power term, and the difference is ambiguous between a lying sensor and a leaking valve. Those have very different costs — a drifted sensor burns nothing directly, while a valve leaking through in free cooling burns plant energy continuously, and worse than the same leak elsewhere because the unit entered OS#2 on the finding that outdoor air could do the job unaided. Climate-neutral.
Emissions Impact
QUALITATIVE_EMISSIONS, LOW confidence; the block is library-assigned, as the
§5.8.1 index carries no emissions column. Scope 1|2 because the equation
cannot tell which coil is leaking: a hot water valve passing flow lands in
Scope 1 (Scope 2 for electric resistance or heat pump heat), a chilled water
valve or stuck DX circuit in Scope 2. The sensor-error diagnoses have no direct
emissions. Avoided-emissions basis: N/A — no quantity is estimated.
Deviations
- The reference card is an index row, so this card is built from G36. §5.8.1 gives the code, the name, and the energy grades, with no equation, vectors, or severity. The equation, OS#2 applicability, four diagnoses, and internal-variable defaults are transcribed from ASHRAE Guideline 36 §5.16.14 as it appears in Addendum u to Guideline 36-2018 (first public review, 2021).
- Severity 3 is library-assigned. The index has no severity column, and G36’s Level 3 alarm grading (§5.16.14.16) is a reporting priority rather than a ranking. The value matches every other G36 001-range card here.
- Energy profile follows the §5.8.1 index row (COMFORT_ENERGY / LOW / QUAL, EEM-01, savings “sensor-dependent”); the emissions block is library-assigned.
- Root-sum-square threshold shipped as one number. G36 writes the bound as
sqrt(eSAT² + eMAT²); the graph carries the evaluated 3.1623 °C indevBig.t, so a host retunes one parameter and no square root runs at runtime. The composition is spelled out in the parameter description because the arithmetic is not linear: a 4 °C mixed-air sensor gives sqrt(1 + 16) = 4.1231 °C, not 1 + 4. - No boundary deviation for this fault. FC#8’s comparison is already strict
(
>), unlike the≥/≤forms elsewhere in Table 5.16.14.8 (FC#5, FC#12, FC#14, FC#15), so no measure-zero rewrite is involved. Same finding as AHU-0009 and AHU-0011. - Fan heat enters as a constant signal, not a negative parameter. An
AddParameterwithp = −1.0computes the same deviation but stores the fan rise with an inverted sign, so a host setting a measured value throughset_paramwould double the error instead of correcting it. - Instantaneous samples instead of averaged signals. G36 compares 5-minute
rolling averages sampled at 1-minute intervals; this rule compares raw
samples and leans on the 30-minute
persistdelay. Not equivalent — persistence resets on every compliant tick, so an oscillating difference can hide indefinitely, while a drifted sensor and a leaking valve are steady offsets and read the same either way. (Honesty note carried from AHU-0002.) - Suppression is declared, not encoded. AHU-0028 gates MAT integrity and
silences this rule while active; the engine is status-blind, so the
relationship lives in
suppressed_byfor the host to enforce. - Operating-state gating and NO_EVAL are frontmatter, not graph. G36 scopes FC#8 to OS#2 (§5.16.14.9b), suspends evaluation for ModeDelay after a mode change, and suspends it entirely when the AHU is off (§5.16.14.11). A host that evaluates in OS#1 or OS#4 will see this rule assert continuously — correctly by the equation and meaninglessly in fact, because a working coil is exactly what the difference is measuring.
persist.delayOnInit = true(Modelica/CDL default isfalse): a deviation already present at load waits out the full 30 minutes rather than alarming on the first tick after a controller restart. Library-wide choice, per AHU-0016.
Notes
This rule and AHU-0010 are the G36 pair testing whether two temperatures that ought to be equal actually are, and both are close cousins of AHU-0028. FC-062 tests containment — MAT inside the OAT–RAT envelope — a law that holds in every operating state; these two test equality, which holds in one state each, and size their bands as the root-sum-square of two specific sensors’ error. The pair also splits the AHU at the fan: FC-010 compares MAT against OAT, both upstream, and carries no fan-heat term. Run the sensor-drift playbook before touching a valve — a hand-held reference settles the SAT question in minutes, and a sensor runs $30–$80.
Test Vectors
10 scenarios, clock step 300 s over 7200 s.
| Scenario | Description |
|---|---|
sat_is_mat_plus_fan_rise | Textbook OS#2: 13.0 °C mixed air arrives at the supply sensor as 14.0 °C, the whole difference being the 1 °C the supply fan puts in. dev = sat − mat − dTSF = 0 exactly, which is what the fanConst term exists to produce. No coil is doing anything and neither sensor is lying. |
sat_equals_mat_no_fan_rise | SAT and MAT read identically, so dev = −1.0 °C: the fan heat G36 expects is missing. That is well inside the 3.1623 °C root-sum-square band — a fan that adds less than its nameplate rise, or a pair of sensors each off by half a degree, is not a fault. |
heating_valve_leaking_sat_too_warm | 13.0 °C mixed air leaves at 18.0 °C: dev = +4.0 °C, past the threshold. In OS#2 the heating coil is commanded shut, so the only ways air gains four degrees more than fan heat are hot water leaking through a closed valve or a sensor reading wrong. Alarms once the 30 min delay expires. |
cooling_valve_leaking_sat_too_cold | 14.0 °C mixed air leaves at 10.0 °C: dev = −5.0 °C. Negative disagreement pins the Abs — without it the rule would only see air that got too warm. Physically this is chilled water leaking through a closed valve, cooling nobody asked for and nobody is paying attention to, since the valve command reads 0. |
edge_positive_dev_equals_threshold | Strict boundary, clear side: sat − mat − 1.0 = 3.1623 °C exactly, the full root-sum-square of eSAT and eMAT. GreaterThreshold is u > t, so a unit sitting precisely on its combined sensor budget reads healthy. |
edge_positive_dev_just_over_threshold | Strict boundary, fault side: the same mixed air with SAT 0.04 °C warmer puts dev at 3.2 °C, which clears u > t and alarms after the delay. Pins the edge from the other direction. |
edge_negative_dev_equals_threshold | Same boundary on the cold side: dev = −3.1623 °C exactly, |
edge_negative_dev_just_over_threshold | Cold side, fault: dev = −3.2 °C. |
transient_disagreement_never_alarms | SAT jumps to 18 °C for 1200 s — shorter than the 1800 s alarm delay — then returns. A damper stroke or a load step moves the mixed-air stream past the SAT sensor before the MAT sensor settles, and the timer resets on the first compliant tick, so nothing is reported. |
fault_clears_when_valve_seats | A leaking heating valve holds SAT at 18 °C, the alarm asserts at 1800 s, and at 3600 s the valve seats and SAT falls back to 14 °C. The alarm drops on that tick: assertion waits out the delay, recovery does not. |
vectors.json
{
"schema": "cxf-library/vectors/v1",
"clock": {
"step_s": 300,
"horizon_s": 7200
},
"scenarios": [
{
"name": "sat_is_mat_plus_fan_rise",
"description": "Textbook OS#2: 13.0 \u00b0C mixed air arrives at the supply sensor as 14.0 \u00b0C, the whole difference being the 1 \u00b0C the supply fan puts in. dev = sat \u2212 mat \u2212 dTSF = 0 exactly, which is what the fanConst term exists to produce. No coil is doing anything and neither sensor is lying.",
"inputs": {
"sat": 14.0,
"mat": 13.0
},
"expect": [
{
"output": "yFault",
"from_s": 0,
"to_s": 7200,
"equals": false
}
]
},
{
"name": "sat_equals_mat_no_fan_rise",
"description": "SAT and MAT read identically, so dev = \u22121.0 \u00b0C: the fan heat G36 expects is missing. That is well inside the 3.1623 \u00b0C root-sum-square band \u2014 a fan that adds less than its nameplate rise, or a pair of sensors each off by half a degree, is not a fault.",
"inputs": {
"sat": 13.0,
"mat": 13.0
},
"expect": [
{
"output": "yFault",
"from_s": 0,
"to_s": 7200,
"equals": false
}
]
},
{
"name": "heating_valve_leaking_sat_too_warm",
"description": "13.0 \u00b0C mixed air leaves at 18.0 \u00b0C: dev = +4.0 \u00b0C, past the threshold. In OS#2 the heating coil is commanded shut, so the only ways air gains four degrees more than fan heat are hot water leaking through a closed valve or a sensor reading wrong. Alarms once the 30 min delay expires.",
"inputs": {
"sat": 18.0,
"mat": 13.0
},
"expect": [
{
"output": "yFault",
"from_s": 0,
"to_s": 1500,
"equals": false
},
{
"output": "yFault",
"from_s": 2100,
"to_s": 7200,
"equals": true
}
]
},
{
"name": "cooling_valve_leaking_sat_too_cold",
"description": "14.0 \u00b0C mixed air leaves at 10.0 \u00b0C: dev = \u22125.0 \u00b0C. Negative disagreement pins the Abs \u2014 without it the rule would only see air that got too warm. Physically this is chilled water leaking through a closed valve, cooling nobody asked for and nobody is paying attention to, since the valve command reads 0.",
"inputs": {
"sat": 10.0,
"mat": 14.0
},
"expect": [
{
"output": "yFault",
"from_s": 0,
"to_s": 1500,
"equals": false
},
{
"output": "yFault",
"from_s": 2100,
"to_s": 7200,
"equals": true
}
]
},
{
"name": "edge_positive_dev_equals_threshold",
"description": "Strict boundary, clear side: sat \u2212 mat \u2212 1.0 = 3.1623 \u00b0C exactly, the full root-sum-square of eSAT and eMAT. GreaterThreshold is u > t, so a unit sitting precisely on its combined sensor budget reads healthy.",
"inputs": {
"sat": 17.2623,
"mat": 13.1
},
"expect": [
{
"output": "yFault",
"from_s": 0,
"to_s": 7200,
"equals": false
}
]
},
{
"name": "edge_positive_dev_just_over_threshold",
"description": "Strict boundary, fault side: the same mixed air with SAT 0.04 \u00b0C warmer puts dev at 3.2 \u00b0C, which clears u > t and alarms after the delay. Pins the edge from the other direction.",
"inputs": {
"sat": 17.3,
"mat": 13.1
},
"expect": [
{
"output": "yFault",
"from_s": 0,
"to_s": 1500,
"equals": false
},
{
"output": "yFault",
"from_s": 2100,
"to_s": 7200,
"equals": true
}
]
},
{
"name": "edge_negative_dev_equals_threshold",
"description": "Same boundary on the cold side: dev = \u22123.1623 \u00b0C exactly, |dev| = t, clear. Together with the positive edge this shows the band is symmetric about the fan-heat-corrected zero rather than about zero itself.",
"inputs": {
"sat": 10.8377,
"mat": 13.0
},
"expect": [
{
"output": "yFault",
"from_s": 0,
"to_s": 7200,
"equals": false
}
]
},
{
"name": "edge_negative_dev_just_over_threshold",
"description": "Cold side, fault: dev = \u22123.2 \u00b0C. |dev| clears the threshold and the alarm asserts after 30 min, at the same magnitude the positive case does.",
"inputs": {
"sat": 10.8,
"mat": 13.0
},
"expect": [
{
"output": "yFault",
"from_s": 0,
"to_s": 1500,
"equals": false
},
{
"output": "yFault",
"from_s": 2100,
"to_s": 7200,
"equals": true
}
]
},
{
"name": "transient_disagreement_never_alarms",
"description": "SAT jumps to 18 \u00b0C for 1200 s \u2014 shorter than the 1800 s alarm delay \u2014 then returns. A damper stroke or a load step moves the mixed-air stream past the SAT sensor before the MAT sensor settles, and the timer resets on the first compliant tick, so nothing is reported.",
"inputs": {
"sat": [
{
"t": 0,
"value": 14.0
},
{
"t": 600,
"value": 18.0
},
{
"t": 1800,
"value": 14.0
}
],
"mat": 13.0
},
"expect": [
{
"output": "yFault",
"from_s": 0,
"to_s": 7200,
"equals": false
}
]
},
{
"name": "fault_clears_when_valve_seats",
"description": "A leaking heating valve holds SAT at 18 \u00b0C, the alarm asserts at 1800 s, and at 3600 s the valve seats and SAT falls back to 14 \u00b0C. The alarm drops on that tick: assertion waits out the delay, recovery does not.",
"inputs": {
"sat": [
{
"t": 0,
"value": 18.0
},
{
"t": 3600,
"value": 14.0
}
],
"mat": 13.0
},
"expect": [
{
"output": "yFault",
"from_s": 0,
"to_s": 1500,
"equals": false
},
{
"output": "yFault",
"from_s": 2100,
"to_s": 3300,
"equals": true
},
{
"output": "yFault",
"from_s": 3900,
"to_s": 7200,
"equals": false
}
]
}
]
}