open-control-library

Executable, engine-verified HVAC fault detection rules. Every rule is a CDL block graph, shipped as CXF JSON-LD that the open-control engine loads directly — no code generation, no black box.

📖 Browse the library — every rule, playbook, and point dictionary, published as a book.

Status: early access. Shared for review ahead of a broader release; content and contracts may still change.

Why

Most FDD libraries are papers, spreadsheets, or vendor black boxes. This one runs — and you can audit every step, from the plain-language fault card down to the exact logic the engine verified.

How a rule ships

Each rule is one folder of four files that travel together:

FileWhat it is
card.mdthe fault card — what the rule detects, the points and parameters it needs, likely diagnoses, energy impact, and every judgment call written down
rule.cxf.jsonldthe detection logic itself, as elementary CDL blocks
vectors.jsonexecutable test scenarios that pin the rule’s behavior from both sides of every threshold
diagram.svgthe block graph, drawn

A rule is marked verified only when the engine at a pinned revision replays every vector green. The engine’s content_id is stamped on the card, so the verified logic stays identifiable forever.

Here’s a real one — AHU-0016, simultaneous heating and cooling:

AHU-0016 block graph

What’s inside

  • 137 verified fault rules across fourteen equipment families — air handlers, VAV boxes, fan-powered terminals, rooftop units, heat pumps, chillers, cooling towers, hot-water plants, hydronic heat exchangers, fan coils, energy recovery ventilators, pumps, VFDs, and cross-equipment sensor-health rules. The Fault Code Map lists them all.
  • Point dictionaries (points/) — every canonical point name grounded in Brick 1.4.4 and ASHRAE 223P, so binding a rule to a real building is mechanical.
  • Remediation playbooks (playbooks/) — verify → remote fix → on-site service → confirm, with typical costs and times.
  • Fault clusters (clusters/) — faults that share a root cause, with a trigger rule and a fix order.
  • CI verification (tools/verify) — every push replays every rule against the pinned engine.

Every card cites its sources — standards, research reports, and this library’s own simulation studies — and records each place the rule departs from them. The detail lives on the cards; start with any rule in the book.

Design stance

The graph computes fault-given-valid-data, and only that. Data quality, operating-state gating, and suppression are host concerns, declared on the card for the host to enforce — never buried in the logic. Rules stay portable, and every judgment call is written down where a reviewer can disagree with it.

Quick start

# read the contracts
$EDITOR SCHEMA.md

# run one rule's vectors against the engine (sibling checkout of open-control required)
cargo run --manifest-path tools/verify/Cargo.toml -- faults/ahu/AHU-0016

# run everything
cargo run --manifest-path tools/verify/Cargo.toml -- --all

# build the book locally
python3 tools/book/generate.py && mdbook serve book --open

Layout

  • SCHEMA.md — the normative contracts. Read this first.
  • faults/<equip>/<FAULT-ID>/ — one folder per rule; faults/registry.json maps them all.
  • points/ — canonical point dictionaries.
  • playbooks/, clusters/ — remediation workflows and fault syndromes.
  • tools/ — the verifier, lints, and book generator.

License

Licensed under either of

at your option. Unless you explicitly state otherwise, any contribution intentionally submitted for inclusion in the work by you, as defined in the Apache-2.0 license, shall be dual licensed as above, without any additional terms or conditions.


This book is generated from the repository by tools/book/generate.py; the files above are the source of truth.