Source code for bac_py.objects.notification_forwarder
"""BACnet Notification Forwarder object per ASHRAE 135-2020 Clause 12.51."""
from __future__ import annotations
from typing import Any, ClassVar
from bac_py.objects.base import (
BACnetObject,
PropertyAccess,
PropertyDefinition,
register_object_type,
standard_properties,
status_properties,
)
from bac_py.types.enums import (
ObjectType,
PropertyIdentifier,
)
[docs]
@register_object_type
class NotificationForwarderObject(BACnetObject):
"""BACnet Notification Forwarder object (Clause 12.51).
Filters and routes event notifications to subscribed recipients.
"""
OBJECT_TYPE: ClassVar[ObjectType] = ObjectType.NOTIFICATION_FORWARDER
PROPERTY_DEFINITIONS: ClassVar[dict[PropertyIdentifier, PropertyDefinition]] = {
**standard_properties(),
**status_properties(include_out_of_service=False),
PropertyIdentifier.PROCESS_IDENTIFIER_FILTER: PropertyDefinition(
PropertyIdentifier.PROCESS_IDENTIFIER_FILTER,
object,
PropertyAccess.READ_WRITE,
required=True,
),
PropertyIdentifier.SUBSCRIBED_RECIPIENTS: PropertyDefinition(
PropertyIdentifier.SUBSCRIBED_RECIPIENTS,
list,
PropertyAccess.READ_WRITE,
required=True,
default=[],
),
PropertyIdentifier.PORT_FILTER: PropertyDefinition(
PropertyIdentifier.PORT_FILTER,
list,
PropertyAccess.READ_WRITE,
required=False,
),
PropertyIdentifier.LOCAL_FORWARDING_ONLY: PropertyDefinition(
PropertyIdentifier.LOCAL_FORWARDING_ONLY,
bool,
PropertyAccess.READ_WRITE,
required=True,
default=True,
),
}
def __init__(self, instance_number: int, **initial_properties: Any) -> None:
super().__init__(instance_number, **initial_properties)
self._init_status_flags()