Server Mode

bac-py can act as a full BACnet server, exposing local objects, responding to client requests, and running engines for scheduling, trend logging, events, and auditing. This guide covers everything from basic setup to advanced customization.

Basic Server Setup

Every bac-py server follows the same four-step pattern regardless of transport:

  1. Create a DeviceConfig (transport selection happens here)

  2. Start a BACnetApplication

  3. Populate the ObjectDatabase with a DeviceObject and application objects

  4. Register DefaultServerHandlers for APDU dispatch

The transport is determined entirely by DeviceConfig — the object creation, handler registration, and lifecycle management are identical across BACnet/IP, IPv6, SC, and Ethernet.

BACnet/IP server (default)

The default transport. Uses UDP on port 47808 with broadcast discovery:

import asyncio
from bac_py import BACnetApplication, DefaultServerHandlers, DeviceConfig, DeviceObject
from bac_py.objects.analog import AnalogInputObject
from bac_py.types.enums import EngineeringUnits

async def serve():
    config = DeviceConfig(
        instance_number=100,
        name="My-Device",
        vendor_name="ACME",
        vendor_id=999,
        interface="0.0.0.0",          # bind address (all interfaces)
        port=0xBAC0,                   # UDP 47808
        broadcast_address="255.255.255.255",  # or subnet-directed, e.g. "192.168.1.255"
    )

    async with BACnetApplication(config) as app:
        device = DeviceObject(
            instance_number=100,
            object_name="My-Device",
            vendor_name="ACME",
            vendor_identifier=999,
        )
        app.object_db.add(device)

        app.object_db.add(AnalogInputObject(
            instance_number=1,
            object_name="Temperature",
            units=EngineeringUnits.DEGREES_CELSIUS,
            present_value=22.5,
        ))

        handlers = DefaultServerHandlers(app, app.object_db, device)
        handlers.register()

        # Server now responds to Who-Is, ReadProperty,
        # ReadPropertyMultiple, WriteProperty, COV subscriptions,
        # and other standard services.
        await app.run()

asyncio.run(serve())

BACnet/IPv6 server

BACnet/IPv6 (Annex U) uses UDP over IPv6 with multicast discovery and 3-byte VMAC addressing. Set ipv6=True on DeviceConfig — everything else is identical to BACnet/IP:

async def serve_ipv6():
    config = DeviceConfig(
        instance_number=100,
        name="My-IPv6-Device",
        vendor_name="ACME",
        vendor_id=999,
        ipv6=True,
        # interface="::" is the default when ipv6=True (all interfaces)
        # port=0xBAC0 is the default (47808)
        # multicast_address="ff02::bac0" is the default (link-local)
        # vmac=None auto-generates a 3-byte VMAC
    )

    async with BACnetApplication(config) as app:
        device = DeviceObject(
            instance_number=100,
            object_name="My-IPv6-Device",
            vendor_name="ACME",
            vendor_identifier=999,
        )
        app.object_db.add(device)
        # ... add objects ...

        handlers = DefaultServerHandlers(app, app.object_db, device)
        handlers.register()
        await app.run()

asyncio.run(serve_ipv6())

Use multicast_address="ff05::bac0" for site-local scope (reaches beyond the link). Provide an explicit vmac (3 bytes) if you need a stable address across restarts.

See examples/ipv6_server.py for a complete example.

BACnet/SC server

BACnet Secure Connect (Annex AB) uses TLS-secured WebSockets in a hub-and-spoke topology. An SC server typically runs the hub function so that SC nodes can connect to it. Pass an SCTransportConfig with a hub_function_config to DeviceConfig:

from bac_py.transport.sc import SCTransportConfig
from bac_py.transport.sc.hub_function import SCHubConfig
from bac_py.transport.sc.tls import SCTLSConfig

async def serve_sc():
    tls = SCTLSConfig(
        ca_certificates_path="/path/to/ca.pem",
        certificate_path="/path/to/hub.pem",
        private_key_path="/path/to/hub.key",
    )

    config = DeviceConfig(
        instance_number=100,
        name="My-SC-Hub",
        vendor_name="ACME",
        vendor_id=999,
        sc_config=SCTransportConfig(
            hub_function_config=SCHubConfig(
                bind_address="0.0.0.0",
                bind_port=8443,
                tls_config=tls,
            ),
            tls_config=tls,
        ),
    )

    async with BACnetApplication(config) as app:
        device = DeviceObject(
            instance_number=100,
            object_name="My-SC-Hub",
            vendor_name="ACME",
            vendor_identifier=999,
        )
        app.object_db.add(device)
        # ... add objects ...

        handlers = DefaultServerHandlers(app, app.object_db, device)
        handlers.register()
        await app.run()

asyncio.run(serve_sc())

Key SCTransportConfig fields for server mode:

  • hub_function_config — required for a server that accepts node connections. Omit this (and set primary_hub_uri) for a node that connects to an existing hub.

  • tls_config — TLS 1.3 certificate configuration. Use SCTLSConfig(allow_plaintext=True) only for testing.

  • primary_hub_uri — leave empty ("") when this node is the hub. Set it to connect to another hub as a client simultaneously (hub chaining).

For testing without TLS certificates:

config = DeviceConfig(
    instance_number=100,
    name="SC-Test-Hub",
    sc_config=SCTransportConfig(
        hub_function_config=SCHubConfig(
            bind_address="0.0.0.0",
            bind_port=4443,
            tls_config=SCTLSConfig(allow_plaintext=True),
        ),
        tls_config=SCTLSConfig(allow_plaintext=True),
    ),
)

See examples/sc_server.py for a complete example and BACnet Secure Connect for TLS certificate generation, failover, and VMAC addressing.

BACnet Ethernet server

BACnet Ethernet (Clause 7) sends BACnet packets directly over IEEE 802.3 frames with 802.2 LLC headers, bypassing IP entirely. Set ethernet_interface on DeviceConfig:

async def serve_ethernet():
    config = DeviceConfig(
        instance_number=100,
        name="My-Ethernet-Device",
        vendor_name="ACME",
        vendor_id=999,
        ethernet_interface="eth0",
        # ethernet_mac=b"\x02\x42\xAC\x11\x00\x02",  # required on macOS
    )

    async with BACnetApplication(config) as app:
        device = DeviceObject(
            instance_number=100,
            object_name="My-Ethernet-Device",
            vendor_name="ACME",
            vendor_identifier=999,
        )
        app.object_db.add(device)
        # ... add objects ...

        handlers = DefaultServerHandlers(app, app.object_db, device)
        handlers.register()
        await app.run()

asyncio.run(serve_ethernet())

Platform requirements:

  • Linux — raw sockets require CAP_NET_RAW or root. The MAC address is auto-detected from the interface.

  • macOS — requires a BPF device (/dev/bpf*), typically root. You must provide an explicit ethernet_mac because BPF does not expose the interface MAC address directly.

See examples/ethernet_server.py for a complete example.

Transport-independent wiring

Because transport selection is isolated in DeviceConfig, the rest of your server code — object creation, handler registration, engines, custom handlers — is identical across all four transports. You can switch transports by changing only the DeviceConfig, which makes it straightforward to support multiple deployment environments from a single codebase.

DefaultServerHandlers.register() installs handlers for all standard BACnet server services. The server will respond to Who-Is with I-Am, ReadProperty and ReadPropertyMultiple with values from the object database, and WriteProperty/WritePropertyMultiple to update writable objects. See Object Model for the full list of supported object types.

DeviceConfig Options

DeviceConfig controls device identity, network parameters, and security:

from bac_py import DeviceConfig
from bac_py.app.application import RouterConfig, RouterPortConfig

config = DeviceConfig(
    instance_number=100,           # BACnet device instance (0-4194302)
    name="My-Device",              # Device name
    vendor_name="ACME",            # Vendor string
    vendor_id=999,                 # ASHRAE vendor ID
    model_name="Controller-1",     # Model name
    firmware_revision="2.0.0",     # Firmware version (default: bac-py version)
    application_software_version="1.0.0",  # Software version (default: bac-py version)
    interface="0.0.0.0",           # IP address to bind
    port=0xBAC0,                   # UDP port (47808)
    max_apdu_length=1476,          # Max APDU size (bytes)
    max_segments=None,             # Max segments (None = unlimited)
    apdu_timeout=6000,             # Request timeout (ms)
    apdu_segment_timeout=2000,     # Segment timeout (ms)
    apdu_retries=3,                # Retry count
    broadcast_address="255.255.255.255",  # Directed broadcast address
    password="secret123",          # Optional password for DCC/ReinitializeDevice
    router_config=None,            # Multi-network router (see below)
    ipv6=False,                    # Use BACnet/IPv6 (Annex U) transport
    sc_config=None,                # BACnet/SC transport config (Annex AB)
    ethernet_interface=None,       # Ethernet interface, e.g. "eth0" (Clause 7)
    ethernet_mac=None,             # Explicit 6-byte MAC (auto-detected on Linux)
)

Transport selection – ipv6, sc_config, and ethernet_interface are mutually exclusive. When none are set, the default BACnet/IP (UDP) transport is used. See Transport Setup for transport configuration details and examples for each transport type.

The password field (1–20 characters) is used by the DeviceCommunicationControl and ReinitializeDevice handlers. When set, incoming requests must include a matching password or the server responds with a PASSWORD_FAILURE error. The comparison uses hmac.compare_digest() for constant-time security.

The broadcast_address defaults to "255.255.255.255" (global broadcast). Override it for subnet-directed broadcasts in Docker or segmented networks (e.g. "192.168.1.255").

See Multi-Network Routing for router_config details.

Object Database

The ObjectDatabase is the runtime registry for all BACnet objects hosted by the server.

Adding and removing objects

from bac_py.objects.analog import AnalogInputObject, AnalogOutputObject
from bac_py.objects.binary import BinaryInputObject
from bac_py.types.enums import EngineeringUnits, ObjectType
from bac_py.types.primitives import ObjectIdentifier

# Add objects
ai = AnalogInputObject(
    instance_number=1,
    object_name="Zone-Temp",
    units=EngineeringUnits.DEGREES_CELSIUS,
    present_value=22.5,
)
app.object_db.add(ai)

# Object names must be unique (Clause 12.1.5)
# Duplicate names or IDs raise BACnetError

# Remove an object
app.object_db.remove(ObjectIdentifier(ObjectType.ANALOG_INPUT, 1))
# Note: Device objects cannot be removed

Querying objects

# Look up by identifier
obj = app.object_db.get(ObjectIdentifier(ObjectType.ANALOG_INPUT, 1))

# All objects of a type
all_ai = app.object_db.get_objects_of_type(ObjectType.ANALOG_INPUT)

# Full object list (auto-computed)
obj_list = app.object_db.object_list

# Iterate all objects
for obj in app.object_db:
    print(obj.object_identifier, obj.read_property(PropertyIdentifier.OBJECT_NAME))

# Count and membership
count = len(app.object_db)
exists = ObjectIdentifier(ObjectType.ANALOG_INPUT, 1) in app.object_db

The Object_List property on the Device object is automatically computed from the database contents. Adding or removing objects increments the Database_Revision property.

Change callbacks

Register callbacks to be notified when a property value is written:

from bac_py.types.enums import PropertyIdentifier

def on_temp_change(prop_id, old_value, new_value):
    print(f"Temperature changed: {old_value} -> {new_value}")

app.object_db.register_change_callback(
    ObjectIdentifier(ObjectType.ANALOG_INPUT, 1),
    PropertyIdentifier.PRESENT_VALUE,
    on_temp_change,
)

# Later, to stop receiving callbacks:
app.object_db.unregister_change_callback(
    ObjectIdentifier(ObjectType.ANALOG_INPUT, 1),
    PropertyIdentifier.PRESENT_VALUE,
    on_temp_change,
)

Change callbacks power both COV-based trend logging and the event engine’s intrinsic reporting.

Supported Object Types

bac-py includes 62 object types covering the full BACnet standard:

Sensing: AnalogInput, BinaryInput, MultiStateInput

Control (commandable): AnalogOutput, BinaryOutput, MultiStateOutput

Values: AnalogValue, BinaryValue, MultiStateValue

Extended values: IntegerValue, PositiveIntegerValue, LargeAnalogValue, CharacterStringValue, OctetStringValue, BitStringValue, DateValue, TimeValue, DateTimeValue, DatePatternValue, TimePatternValue, DateTimePatternValue

Infrastructure: Device, File, NetworkPort, Channel

Scheduling: Schedule, Calendar

Trending: TrendLog, TrendLogMultiple

Events: EventEnrollment, NotificationClass, EventLog, AlertEnrollment, NotificationForwarder

Safety: LifeSafetyPoint, LifeSafetyZone

Auditing: AuditReporter, AuditLog

Access control: AccessDoor, AccessPoint, AccessZone, AccessUser, AccessRights, AccessCredential, CredentialDataInput

Advanced control: Command, Timer, Staging, LoadControl, Loop, PulseConverter, Accumulator

Lighting: LightingOutput, BinaryLightingOutput

Transportation: ElevatorGroup, Lift, Escalator

Other: Program, Averaging, Group, GlobalGroup, StructuredView

All objects are created as frozen dataclasses with validated property definitions and read/write access control.

Commandable Objects and Priority Arrays

BACnet commandable objects support a 16-level command priority array (Clause 19.2). When multiple sources write to the same object, the highest priority (lowest number) wins.

Always-commandable objects

AnalogOutput, BinaryOutput, and MultiStateOutput are always commandable:

from bac_py.objects.analog import AnalogOutputObject
from bac_py.types.enums import EngineeringUnits

ao = AnalogOutputObject(
    instance_number=1,
    object_name="Damper-Position",
    units=EngineeringUnits.PERCENT,
    relinquish_default=0.0,
)
app.object_db.add(ao)

# Write at priority 8 (manual operator)
ao.write_property(PropertyIdentifier.PRESENT_VALUE, 75.0, priority=8)

# The present value is now 75.0 (priority 8 is the highest active slot)

# Write at priority 1 (life safety -- overrides priority 8)
ao.write_property(PropertyIdentifier.PRESENT_VALUE, 100.0, priority=1)
# Present value is now 100.0

# Relinquish priority 1
ao.write_property(PropertyIdentifier.PRESENT_VALUE, None, priority=1)
# Present value falls back to 75.0 (priority 8)

# Relinquish priority 8
ao.write_property(PropertyIdentifier.PRESENT_VALUE, None, priority=8)
# All slots empty -- present value falls back to relinquish_default (0.0)

Optionally-commandable objects

IntegerValue and PositiveIntegerValue support an optional commandable flag:

from bac_py.objects.value_types import IntegerValueObject

iv = IntegerValueObject(
    instance_number=1,
    object_name="Setpoint-Mode",
    commandable=True,
    relinquish_default=0,
)

When commandable=True, the object gets a full 16-level priority array, Relinquish_Default, Current_Command_Priority, and value source tracking. When commandable=False (the default), writes go directly to Present_Value without priority handling.

COV Subscriptions (Server Side)

The server’s COV manager (COVManager) handles incoming SubscribeCOV, SubscribeCOVProperty, and SubscribeCOVPropertyMultiple requests automatically when DefaultServerHandlers is registered.

How it works

  1. A remote client sends a SubscribeCOV request for an object

  2. The server registers the subscription with a lifetime timer

  3. An initial notification is sent immediately (Clause 13.1.2)

  4. On each property write, the server checks if the value change exceeds the COV threshold and sends notifications to all matching subscribers

Notification thresholds:

  • Analog objects: Notify when |new - last| >= COV_Increment, or on any change if no increment is set

  • Binary/multistate objects: Notify on any change in Present_Value

  • All objects: Notify on any change in Status_Flags

Subscription types:

  • Object-level (SubscribeCOV): Monitors Present_Value and Status_Flags

  • Property-level (SubscribeCOVProperty): Monitors a specific property with optional per-subscription COV increment override

  • Property-multiple (SubscribeCOVPropertyMultiple): Multiple property-level subscriptions in a single request

Lifetime management:

  • Subscriptions with a lifetime (in seconds) expire automatically

  • Subscriptions without a lifetime persist indefinitely

  • Clients can cancel subscriptions or re-subscribe to refresh the lifetime

The COV manager is created automatically during application startup and shut down during application stop. No additional configuration is needed beyond registering DefaultServerHandlers.

Inspecting active subscriptions

# List all active subscriptions
subs = app.cov_manager.get_active_subscriptions()

# Filter by object
subs = app.cov_manager.get_active_subscriptions(
    ObjectIdentifier(ObjectType.ANALOG_INPUT, 1)
)

for sub in subs:
    print(f"Subscriber: {sub.subscriber}, Object: {sub.monitored_object}, "
          f"Confirmed: {sub.confirmed}, Lifetime: {sub.lifetime}")

Custom Service Handlers

The ServiceRegistry dispatches incoming requests to registered handler functions. DefaultServerHandlers registers handlers for all standard services, but you can replace or extend them.

Handler signature

Confirmed service handlers receive the raw request bytes and return response bytes (for ComplexACK) or None (for SimpleACK):

async def my_handler(
    service_choice: int,
    request_data: bytes,
    source: BACnetAddress,
) -> bytes | None:
    # Decode request_data, process, return response or None
    ...

Unconfirmed service handlers process the request without returning a response:

async def my_unconfirmed_handler(
    service_choice: int,
    request_data: bytes,
    source: BACnetAddress,
) -> None:
    # Decode and process, no response needed
    ...

Registering custom handlers

from bac_py.types.enums import ConfirmedServiceChoice, UnconfirmedServiceChoice

# Override a standard handler
app.service_registry.register_confirmed(
    ConfirmedServiceChoice.CONFIRMED_PRIVATE_TRANSFER,
    my_private_transfer_handler,
)

# Register an unconfirmed handler
app.service_registry.register_unconfirmed(
    UnconfirmedServiceChoice.UNCONFIRMED_PRIVATE_TRANSFER,
    my_unconfirmed_handler,
)

Custom validation example

Add a write-access filter that restricts writes to a whitelist of source addresses:

from bac_py.services.errors import BACnetError
from bac_py.services.property_access import WritePropertyRequest
from bac_py.types.enums import ErrorClass, ErrorCode

ALLOWED_WRITERS = {"192.168.1.10", "192.168.1.20"}

async def restricted_write_handler(service_choice, data, source):
    if str(source) not in ALLOWED_WRITERS:
        raise BACnetError(ErrorClass.SECURITY, ErrorCode.WRITE_ACCESS_DENIED)
    # Fall through to default handling
    return await default_handlers.handle_write_property(service_choice, data, source)

app.service_registry.register_confirmed(
    ConfirmedServiceChoice.WRITE_PROPERTY,
    restricted_write_handler,
)

Error responses

Handlers signal errors by raising exceptions:

from bac_py.services.errors import (
    BACnetError,         # -> Error-PDU (error_class, error_code)
    BACnetRejectError,   # -> Reject-PDU (reason)
    BACnetAbortError,    # -> Abort-PDU (reason)
)

# Property not found
raise BACnetError(ErrorClass.PROPERTY, ErrorCode.UNKNOWN_PROPERTY)

# Malformed request
raise BACnetRejectError(RejectReason.MISSING_REQUIRED_PARAMETER)

If no handler is registered for a confirmed service, the application automatically sends a Reject-PDU with UNRECOGNIZED_SERVICE. Unregistered unconfirmed services are silently ignored per Clause 5.4.2.

Event Engine

The EventEngine evaluates all 18 standard BACnet event algorithms and generates event notifications routed through NotificationClass recipient lists.

Starting the event engine

from bac_py.app.event_engine import EventEngine
from bac_py.objects.analog import AnalogInputObject
from bac_py.objects.notification import NotificationClassObject
from bac_py.types.enums import EngineeringUnits, EventType, NotifyType

async def serve_with_events():
    config = DeviceConfig(instance_number=100, name="My-Device",
                          vendor_name="ACME", vendor_id=999)

    async with BACnetApplication(config) as app:
        # ... add device object and register handlers ...

        # Notification class for routing alarm notifications
        app.object_db.add(NotificationClassObject(
            instance_number=1,
            object_name="Critical-Alarms",
            notification_class=1,
            priority=[3, 3, 3],  # [to_offnormal, to_fault, to_normal]
        ))

        # Analog input with intrinsic out-of-range reporting
        app.object_db.add(AnalogInputObject(
            instance_number=1,
            object_name="Zone-Temp",
            units=EngineeringUnits.DEGREES_CELSIUS,
            present_value=22.5,
            high_limit=30.0,
            low_limit=15.0,
            deadband=1.0,
            notification_class=1,
            event_enable=[True, True, True],
            notify_type=NotifyType.ALARM,
        ))

        engine = EventEngine(app, scan_interval=1.0)
        await engine.start()

        try:
            await app.run()
        finally:
            await engine.stop()

Supported algorithms

The engine evaluates these event types automatically based on object configuration:

  • CHANGE_OF_BITSTRING

  • CHANGE_OF_STATE

  • CHANGE_OF_VALUE

  • COMMAND_FAILURE

  • FLOATING_LIMIT

  • OUT_OF_RANGE

  • CHANGE_OF_LIFE_SAFETY

  • EXTENDED

  • BUFFER_READY

  • UNSIGNED_RANGE

  • ACCESS_EVENT

  • DOUBLE_OUT_OF_RANGE

  • SIGNED_OUT_OF_RANGE

  • UNSIGNED_OUT_OF_RANGE

  • CHANGE_OF_CHARACTERSTRING

  • CHANGE_OF_STATUS_FLAGS

  • CHANGE_OF_RELIABILITY

  • CHANGE_OF_DISCRETE_VALUE

Intrinsic reporting

Objects that define INTRINSIC_EVENT_ALGORITHM (AnalogInput, BinaryInput, AnalogValue, etc.) automatically participate in event evaluation when their Event_Enable property has at least one transition enabled and a valid Notification_Class is assigned.

Algorithmic reporting

For custom event detection, create an EventEnrollmentObject that references the monitored object and specifies the algorithm parameters:

from bac_py.objects.event_enrollment import EventEnrollmentObject
from bac_py.types.enums import EventType, EventState

app.object_db.add(EventEnrollmentObject(
    instance_number=1,
    object_name="Temp-Out-Of-Range",
    event_type=EventType.OUT_OF_RANGE,
    notify_type=NotifyType.ALARM,
    notification_class=1,
    event_enable=[True, True, True],
))

The engine routes notifications through NotificationClassObject recipient lists with day/time filtering and per-recipient confirmed/unconfirmed delivery. See Event Notifications for client-side event handling.

Audit Logging (Server Side)

The AuditManager instruments server handlers to automatically record write, create, and delete operations as audit log entries (new in ASHRAE 135-2020).

Setting up audit logging

from bac_py.app.audit import AuditManager
from bac_py.objects.audit_reporter import AuditReporterObject
from bac_py.objects.audit_log import AuditLogObject

# Create an audit reporter that monitors all objects
app.object_db.add(AuditReporterObject(
    instance_number=1,
    object_name="System-Auditor",
))

# Create an audit log buffer
app.object_db.add(AuditLogObject(
    instance_number=1,
    object_name="System-Audit-Log",
    buffer_size=1000,
))

# The AuditManager is created in BACnetApplication and
# is invoked automatically by DefaultServerHandlers
# on write_property, create_object, and delete_object.

Key AuditReporter properties:

  • monitored_objects: List of ObjectIdentifiers to audit (empty = all)

  • audit_level: Filtering level (NONE, DEFAULT, AUDIT_CONFIG)

  • auditable_operations: BitString filter for operation types

Key AuditLog properties:

  • buffer_size: Maximum records before circular overwrite (default 100)

  • stop_when_full: If True, stop logging when buffer is full

  • log_enable: Enable/disable logging

  • record_count: Current records in buffer

  • total_record_count: Monotonically increasing sequence number

See Audit Logging for client-side audit queries.

Error Handling

Server handlers use a consistent error hierarchy:

from bac_py.services.errors import (
    BACnetError,        # Error-PDU (error_class, error_code)
    BACnetRejectError,  # Reject-PDU (reason)
    BACnetAbortError,   # Abort-PDU (reason)
)

Common server-side error responses:

Situation

Exception

Clause

Unknown object

BACnetError(OBJECT, UNKNOWN_OBJECT)

12.1

Unknown property

BACnetError(PROPERTY, UNKNOWN_PROPERTY)

12.1

Write to read-only property

BACnetError(PROPERTY, WRITE_ACCESS_DENIED)

15.9

Wrong password

BACnetError(SECURITY, PASSWORD_FAILURE)

16.1

DCC disabled

BACnetRejectError(OTHER)

16.1

Missing parameter

BACnetRejectError(MISSING_REQUIRED_PARAMETER)

5.4

Value out of range

BACnetError(PROPERTY, VALUE_OUT_OF_RANGE)

15.9

Password validation

When DeviceConfig.password is set, the DeviceCommunicationControl and ReinitializeDevice handlers validate the password using constant-time comparison (hmac.compare_digest()). Requests with a missing or incorrect password receive a PASSWORD_FAILURE error.

DeviceCommunicationControl states

The DCC handler supports three states:

  • ENABLE: Normal operation (default)

  • DISABLE: Only DeviceCommunicationControl and ReinitializeDevice requests are processed; all other confirmed services are rejected

  • DISABLE_INITIATION: The server suppresses outbound unsolicited messages but still responds to incoming requests

An optional time_duration (minutes) automatically re-enables the device after the specified period.

Application Lifecycle

BACnetApplication manages the full lifecycle of transport, network layer, TSM, COV manager, and engines.

Manual lifecycle

app = BACnetApplication(config)
await app.start()  # Bind socket, start transport/network
try:
    handlers = DefaultServerHandlers(app, app.object_db, device)
    handlers.register()
    await app.run()
finally:
    await app.stop()  # Idempotent, safe to call multiple times

Combined client and server

A single application can act as both client and server simultaneously:

from bac_py.app.client import BACnetClient

async with BACnetApplication(config) as app:
    device = DeviceObject(instance_number=100, object_name="My-Device",
                          vendor_name="ACME", vendor_identifier=999)
    app.object_db.add(device)

    # Server side
    handlers = DefaultServerHandlers(app, app.object_db, device)
    handlers.register()

    # Client side
    bc = BACnetClient(app)
    value = await bc.read("192.168.1.200", "ai,1", "pv")

    await app.run()

Auto-computed properties

When DefaultServerHandlers.register() is called, it automatically computes and sets:

  • Protocol_Services_Supported: BitString reflecting all registered service handlers

  • Protocol_Object_Types_Supported: BitString for all object types supported by the library

Scheduling

Create a Schedule object with weekly time-value pairs and run the ScheduleEngine to evaluate it:

import asyncio
from bac_py.app.application import BACnetApplication, DeviceConfig
from bac_py.app.schedule_engine import ScheduleEngine
from bac_py.objects.schedule import ScheduleObject
from bac_py.types.constructed import BACnetTimeValue
from bac_py.types.primitives import BACnetTime

async def serve_with_schedule():
    config = DeviceConfig(instance_number=100, name="My-Device",
                          vendor_name="ACME", vendor_id=999)

    async with BACnetApplication(config) as app:
        # ... add device and other objects ...

        # Occupied/unoccupied schedule (Mon-Fri 8am-6pm = 1, else = 0)
        weekday_entries = [
            BACnetTimeValue(time=BACnetTime(8, 0, 0, 0), value=1),
            BACnetTimeValue(time=BACnetTime(18, 0, 0, 0), value=0),
        ]
        app.object_db.add(ScheduleObject(
            instance_number=1,
            object_name="Occupancy-Schedule",
            weekly_schedule=[
                weekday_entries,  # Monday
                weekday_entries,  # Tuesday
                weekday_entries,  # Wednesday
                weekday_entries,  # Thursday
                weekday_entries,  # Friday
                [],               # Saturday
                [],               # Sunday
            ],
            schedule_default=0,
        ))

        # Start the schedule engine
        engine = ScheduleEngine(app, scan_interval=10.0)
        await engine.start()

        try:
            await app.run()
        finally:
            await engine.stop()

asyncio.run(serve_with_schedule())

Trend Logging

Create a TrendLog object that records AnalogInput present-value readings using the TrendLogEngine:

import asyncio
from bac_py.app.application import BACnetApplication, DeviceConfig
from bac_py.app.trendlog_engine import TrendLogEngine
from bac_py.objects.trendlog import TrendLogObject
from bac_py.types.enums import LoggingType, ObjectType, PropertyIdentifier
from bac_py.types.primitives import ObjectIdentifier

async def serve_with_trendlog():
    config = DeviceConfig(instance_number=100, name="My-Device",
                          vendor_name="ACME", vendor_id=999)

    async with BACnetApplication(config) as app:
        # ... add device and AnalogInput objects ...

        # Log ai,1 present-value every 60 seconds (polled mode)
        app.object_db.add(TrendLogObject(
            instance_number=1,
            object_name="Zone-Temp-Log",
            log_device_object_property=ObjectIdentifier(
                ObjectType.ANALOG_INPUT, 1),
            logging_type=LoggingType.POLLED,
            log_interval=60,  # seconds
            buffer_size=1000,
        ))

        engine = TrendLogEngine(app, scan_interval=1.0)
        await engine.start()

        try:
            await app.run()
        finally:
            await engine.stop()

asyncio.run(serve_with_trendlog())

COV-based trend logging

For change-of-value recording (Clause 12.25.13), set logging_type to LoggingType.COV. The engine registers a change callback on the monitored local object and records a log entry whenever the value is written:

# Log ai,1 present-value on every change (COV mode)
app.object_db.add(TrendLogObject(
    instance_number=2,
    object_name="Zone-Temp-COV-Log",
    log_device_object_property=ObjectIdentifier(
        ObjectType.ANALOG_INPUT, 1),
    logging_type=LoggingType.COV,
    buffer_size=1000,
))

COV-mode trend logs do not poll. They only record when the monitored property is actually written, which can be more efficient for slowly changing values.

Registered Services

DefaultServerHandlers.register() installs handlers for the following services:

Confirmed services:

  • ReadProperty, WriteProperty

  • ReadPropertyMultiple, WritePropertyMultiple

  • ReadRange

  • SubscribeCOV, SubscribeCOVProperty, SubscribeCOVPropertyMultiple

  • ConfirmedCOVNotificationMultiple

  • DeviceCommunicationControl, ReinitializeDevice

  • AtomicReadFile, AtomicWriteFile

  • CreateObject, DeleteObject

  • AddListElement, RemoveListElement

  • AcknowledgeAlarm, ConfirmedEventNotification

  • GetAlarmSummary, GetEnrollmentSummary, GetEventInformation

  • ConfirmedTextMessage

  • VT-Open, VT-Close, VT-Data

  • AuditLogQuery, ConfirmedAuditNotification

  • ConfirmedPrivateTransfer

Unconfirmed services:

  • Who-Is, Who-Has

  • TimeSynchronization, UTCTimeSynchronization

  • UnconfirmedCOVNotificationMultiple

  • UnconfirmedEventNotification

  • UnconfirmedTextMessage

  • WriteGroup

  • Who-Am-I, You-Are

  • UnconfirmedAuditNotification