Source code for bac_py.network.layer

"""Network layer manager wiring transport to application per Clause 6.

Provides :class:`NetworkLayer`, the non-router network layer manager that
bridges a single transport (any :class:`~bac_py.transport.port.TransportPort`
implementation) with the application layer by handling NPDU
wrapping/unwrapping, router cache management, and network-number learning.
"""

from __future__ import annotations

import logging
import time
from dataclasses import dataclass
from typing import TYPE_CHECKING

from bac_py.network.address import BACnetAddress
from bac_py.network.messages import (
    IAmRouterToNetwork,
    NetworkNumberIs,
    WhoIsRouterToNetwork,
    decode_network_message,
    encode_network_message,
)
from bac_py.network.npdu import NPDU, decode_npdu, encode_npdu
from bac_py.types.enums import NetworkMessageType, NetworkPriority

if TYPE_CHECKING:
    from collections.abc import Callable

    from bac_py.transport.port import TransportPort

logger = logging.getLogger(__name__)
_DEBUG = logging.DEBUG


[docs] @dataclass(slots=True) class RouterCacheEntry: """Cached router address for a remote network. Non-router devices maintain a cache mapping remote DNETs to the local MAC address of a router that can reach that network. """ network: int """The remote DNET this entry provides a route to.""" router_mac: bytes """6-byte MAC of the local router serving this DNET.""" last_seen: float """``time.monotonic()`` timestamp of last I-Am-Router-To-Network update."""
# Default cache TTL: 5 minutes. Per Clause 6.6.3.3, stale routes # should eventually be re-discovered via Who-Is-Router queries. _DEFAULT_CACHE_TTL: float = 300.0 # Maximum number of entries in the router cache. A misbehaving network # could otherwise grow this unboundedly via I-Am-Router-To-Network floods. _MAX_ROUTER_CACHE: int = 1024
[docs] class NetworkLayer: """Network layer manager (non-router mode). Bridges the transport layer and the application layer. Accepts any transport implementing :class:`~bac_py.transport.port.TransportPort` (BACnet/IP, BACnet/IPv6, Ethernet, etc.). Handles NPDU wrapping/unwrapping for application-layer APDUs. Supports optional network number assignment and maintains a router cache for addressing remote networks via known routers. """ def __init__( self, transport: TransportPort, network_number: int | None = None, *, network_number_configured: bool = False, cache_ttl: float = _DEFAULT_CACHE_TTL, ) -> None: """Initialise the network layer. :param transport: The transport used for sending and receiving. Must satisfy the :class:`~bac_py.transport.port.TransportPort` protocol. :param network_number: Local network number, or ``None`` if unknown. :param network_number_configured: ``True`` if the network number was explicitly configured (prevents learning via Network-Number-Is messages). :param cache_ttl: Time-to-live in seconds for router cache entries. """ self._transport = transport self._network_number = network_number self._network_number_configured = network_number_configured self._router_cache: dict[int, RouterCacheEntry] = {} self._cache_ttl = cache_ttl self._receive_callback: Callable[[bytes, BACnetAddress], None] | None = None self._network_message_listeners: dict[int, list[Callable[..., None]]] = {} transport.on_receive(self._on_npdu_received) @property def network_number(self) -> int | None: """The local network number, or ``None`` if unknown.""" return self._network_number
[docs] def on_receive(self, callback: Callable[[bytes, BACnetAddress], None]) -> None: """Register a callback for received application-layer APDUs. :param callback: Called with ``(apdu_bytes, source_address)`` for each received NPDU containing an application-layer APDU. """ self._receive_callback = callback
[docs] def register_network_message_handler( self, message_type: int, handler: Callable[..., None], ) -> None: """Register a handler for incoming network-layer messages. Multiple handlers may be registered for the same message type; they are invoked in registration order. :param message_type: Network message type code to listen for. :param handler: Called with ``(decoded_message, source_mac)`` when a matching network message is received. """ self._network_message_listeners.setdefault(message_type, []).append(handler)
[docs] def unregister_network_message_handler( self, message_type: int, handler: Callable[..., None], ) -> None: """Remove a previously registered network-layer message handler. :param message_type: Network message type code. :param handler: The handler to remove. """ listeners = self._network_message_listeners.get(message_type, []) if handler in listeners: listeners.remove(handler)
[docs] def send_network_message( self, message_type: int, data: bytes, destination: BACnetAddress | None = None, ) -> None: """Send a network-layer message (non-APDU). :param message_type: Network message type code. :param data: Encoded message payload. :param destination: Target address. If ``None``, broadcasts locally. A local-network address (no DNET) sends a unicast without NPDU destination routing. """ # Local unicast: destination on the same network (no DNET set). # Send directly without NPDU destination header to avoid the # "Destination network must be set" requirement in the NPDU encoder. is_local_unicast = ( destination is not None and not destination.is_broadcast and not destination.is_global_broadcast and destination.network is None ) npdu_dest = None if is_local_unicast else destination npdu = NPDU( is_network_message=True, message_type=message_type, network_message_data=data, destination=npdu_dest, hop_count=255 if npdu_dest is not None else 0, ) npdu_bytes = encode_npdu(npdu) if destination is None or destination.is_broadcast or destination.is_global_broadcast: self._transport.send_broadcast(npdu_bytes) else: self._transport.send_unicast(npdu_bytes, destination.mac_address)
[docs] def send( self, apdu: bytes, destination: BACnetAddress, *, expecting_reply: bool = True, priority: NetworkPriority = NetworkPriority.NORMAL, ) -> None: """Send an APDU to a destination address. Wraps the APDU in an :class:`~bac_py.network.npdu.NPDU` and sends via the transport layer. For remote destinations (DNET set), uses the router cache to send via a known router, or broadcasts if no router is cached. :param apdu: Application-layer PDU bytes. :param destination: Target :class:`~bac_py.network.address.BACnetAddress`. :param expecting_reply: Whether a reply is expected (affects routing). :param priority: Network priority level. """ npdu = NPDU( is_network_message=False, expecting_reply=expecting_reply, priority=priority, destination=destination if not destination.is_local else None, hop_count=255, apdu=apdu, ) npdu_bytes = encode_npdu(npdu) if destination.is_global_broadcast: self._transport.send_broadcast(npdu_bytes) elif destination.is_local and destination.is_broadcast: # Local broadcast (no network, no MAC) self._transport.send_broadcast(npdu_bytes) elif destination.is_local: self._transport.send_unicast(npdu_bytes, destination.mac_address) else: # Remote destination (DNET is set, not global broadcast) self._send_remote(npdu_bytes, destination)
@property def local_address(self) -> object: """The local address of the underlying transport. Returns the transport-specific address type (e.g. :class:`~bac_py.network.address.BIPAddress` for BACnet/IP, :class:`~bac_py.network.address.BIP6Address` for BACnet/IPv6). """ return self._transport.local_address # type: ignore[attr-defined]
[docs] def add_route(self, network: int, router_mac: bytes) -> None: """Pre-populate the router cache for a remote network. Allows sending to a remote network without broadcast-based router discovery. Useful in environments (e.g. Docker bridge networks) where broadcast-based discovery is unreliable. :param network: The remote network number. :param router_mac: 6-byte MAC address of the router that reaches the target network. """ self._ensure_cache_capacity() self._router_cache[network] = RouterCacheEntry( network=network, router_mac=router_mac, last_seen=time.monotonic(), ) logger.debug("Route added: network %d via %s", network, router_mac.hex())
[docs] def get_router_for_network(self, dnet: int) -> bytes | None: """Look up the cached router MAC for a remote network. Evicts the entry if it has exceeded the cache TTL. :param dnet: The destination network number to look up. :returns: The 6-byte router MAC if cached and fresh, or ``None`` if unknown or stale. """ entry = self._router_cache.get(dnet) if entry is None: return None if time.monotonic() - entry.last_seen > self._cache_ttl: logger.debug("Router cache entry for network %d expired, evicting", dnet) del self._router_cache[dnet] return None return entry.router_mac
# ------------------------------------------------------------------ # Receive path # ------------------------------------------------------------------ def _on_npdu_received(self, data: bytes, source_mac: bytes) -> None: """Process incoming NPDU from transport. Decodes the NPDU, delegates network-layer messages to :meth:`_handle_network_message`, and delivers application- layer APDUs to the registered receive callback. The source address is reconstructed from the NPDU source field (if present, for routed messages) or from the raw transport MAC. :param data: Raw NPDU bytes received from the transport. :param source_mac: MAC address of the sender on the local network. """ try: npdu = decode_npdu(memoryview(data)) except (ValueError, IndexError): logger.warning("Dropped malformed NPDU") return if npdu.is_network_message: self._handle_network_message(npdu, source_mac) return # Convert source MAC to BACnetAddress, preserving source # network from the NPDU if present (for routed messages). if npdu.source is not None: src_addr = npdu.source # Learn that source_mac is a router for this remote network. # This enables efficient unicast routing for subsequent requests # to devices on that network (e.g. MS/TP devices behind a router). if src_addr.network is not None and src_addr.network != 0xFFFF: self._learn_router_from_source(src_addr.network, source_mac) else: src_addr = BACnetAddress( mac_address=source_mac, ) if self._receive_callback: if __debug__ and logger.isEnabledFor(_DEBUG): logger.debug( "Dispatching APDU (%d bytes) to application from %s", len(npdu.apdu), src_addr, ) try: self._receive_callback(npdu.apdu, src_addr) except Exception: logger.warning("Error in receive callback", exc_info=True) # ------------------------------------------------------------------ # Network message handling (non-router) # ------------------------------------------------------------------ def _handle_network_message(self, npdu: NPDU, source_mac: bytes) -> None: """Process network layer messages relevant to non-router devices. Handles I-Am-Router-To-Network, What-Is-Network-Number, and Network-Number-Is internally, and dispatches all decoded messages to registered listeners. :param npdu: The decoded :class:`NPDU` containing the network message. :param source_mac: MAC address of the sender on the local network. """ try: if npdu.message_type is None: logger.warning("Dropped network message with no message type") return msg = decode_network_message(npdu.message_type, npdu.network_message_data) except (ValueError, IndexError): logger.warning( "Dropped malformed network message type %s", npdu.message_type, ) return logger.debug("Handling network message type %s: %s", npdu.message_type, type(msg).__name__) if isinstance(msg, IAmRouterToNetwork): self._handle_i_am_router(msg, source_mac) elif isinstance(msg, WhoIsRouterToNetwork): # Non-routers do not respond to Who-Is-Router per spec. logger.debug("Ignoring Who-Is-Router-To-Network (non-router)") elif isinstance(msg, NetworkNumberIs): self._handle_network_number_is(msg, npdu) elif npdu.message_type == NetworkMessageType.WHAT_IS_NETWORK_NUMBER: self._handle_what_is_network_number(npdu) else: logger.debug( "Ignoring network message type %s (non-router)", npdu.message_type, ) # Dispatch to registered listeners listeners = self._network_message_listeners.get(npdu.message_type, []) for listener in listeners: try: listener(msg, source_mac) except Exception: logger.warning("Error in network message listener", exc_info=True) def _evict_stale_cache_entries(self) -> None: """Remove expired entries from the router cache. Called before inserting new entries when the cache is at capacity. """ now = time.monotonic() stale = [k for k, v in self._router_cache.items() if now - v.last_seen > self._cache_ttl] for k in stale: del self._router_cache[k] def _ensure_cache_capacity(self) -> None: """Ensure the router cache has room for at least one new entry. Evicts stale entries first. If still at capacity, evicts the oldest entry by ``last_seen`` timestamp. """ if len(self._router_cache) < _MAX_ROUTER_CACHE: return self._evict_stale_cache_entries() if len(self._router_cache) >= _MAX_ROUTER_CACHE: oldest_key = min(self._router_cache, key=lambda k: self._router_cache[k].last_seen) del self._router_cache[oldest_key] def _handle_i_am_router( self, msg: IAmRouterToNetwork, source_mac: bytes, ) -> None: """Populate the router cache from an I-Am-Router-To-Network message. Creates or updates a :class:`RouterCacheEntry` for each advertised DNET, recording the source MAC and current timestamp. :param msg: The decoded :class:`IAmRouterToNetwork` message. :param source_mac: MAC address of the advertising router. """ now = time.monotonic() for dnet in msg.networks: if dnet not in self._router_cache: self._ensure_cache_capacity() self._router_cache[dnet] = RouterCacheEntry( network=dnet, router_mac=source_mac, last_seen=now, ) logger.debug( "Router cache updated: %s via %s", msg.networks, source_mac.hex(), ) def _learn_router_from_source(self, snet: int, source_mac: bytes) -> None: """Learn a router path from a routed APDU's SNET/SADR fields. When an APDU arrives with SNET set, the transport-level sender (source_mac) is a router that can reach that remote network. Cache this path so subsequent requests to devices on that network can be sent as unicast to the router rather than broadcast. Only creates an entry if one doesn't already exist or the existing entry has expired, to avoid overwriting explicit I-Am-Router-To-Network entries. :param snet: The source network number from the NPDU. :param source_mac: Transport-level MAC of the router that forwarded the message. """ existing = self._router_cache.get(snet) if existing is not None: now = time.monotonic() if now - existing.last_seen <= self._cache_ttl: # Fresh entry exists — just refresh the timestamp existing.last_seen = now return # No entry or stale — learn from source if snet not in self._router_cache: self._ensure_cache_capacity() self._router_cache[snet] = RouterCacheEntry( network=snet, router_mac=source_mac, last_seen=time.monotonic(), ) logger.debug( "Learned router for network %d from routed APDU via %s", snet, source_mac.hex(), ) def _handle_what_is_network_number(self, npdu: NPDU) -> None: """Respond to What-Is-Network-Number if configured. Per Clause 6.4.19, this message must not be routed (ignore if SNET/SADR or DNET/DADR present). :param npdu: The decoded :class:`NPDU` used to check routing fields. """ if npdu.source is not None or npdu.destination is not None: return if self._network_number is not None and self._network_number_configured: self._send_network_number_is() def _handle_network_number_is(self, msg: NetworkNumberIs, npdu: NPDU) -> None: """Learn network number from a Network-Number-Is message. Per Clause 6.4.20, this message must not be routed (ignore if SNET/SADR or DNET/DADR present). Only learn if our number is not configured and the source is configured (authoritative). :param msg: The decoded :class:`NetworkNumberIs` message. :param npdu: The decoded :class:`NPDU` used to check routing fields. """ if npdu.source is not None or npdu.destination is not None: return if not msg.configured: return if self._network_number_configured: return self._network_number = msg.network logger.info("Learned network number %d from Network-Number-Is", msg.network) # ------------------------------------------------------------------ # Remote send helpers # ------------------------------------------------------------------ def _send_remote(self, npdu_bytes: bytes, destination: BACnetAddress) -> None: """Send an NPDU to a remote destination using the router cache. If a router is cached for the destination network, unicasts to it. Otherwise broadcasts the NPDU and issues a Who-Is-Router query to populate the cache for future sends. :param npdu_bytes: The encoded NPDU bytes to send. :param destination: Remote :class:`~bac_py.network.address.BACnetAddress` (must have a network number set). :raises ValueError: If *destination* has no network number. """ if destination.network is None: msg = "Cannot send to remote destination without network number" raise ValueError(msg) router_mac = self.get_router_for_network(destination.network) if router_mac is not None: if __debug__ and logger.isEnabledFor(_DEBUG): logger.debug( "Sending to network %d via cached router %s", destination.network, router_mac.hex(), ) self._transport.send_unicast(npdu_bytes, router_mac) else: # Cache miss: broadcast NPDU (a router will pick it up) logger.warning( "No cached router for network %d, broadcasting NPDU", destination.network ) self._transport.send_broadcast(npdu_bytes) # Also issue Who-Is-Router-To-Network to populate cache self._send_who_is_router(destination.network) def _send_who_is_router(self, dnet: int) -> None: """Broadcast a Who-Is-Router-To-Network query. :param dnet: The remote network number to query for. """ msg = WhoIsRouterToNetwork(network=dnet) npdu = NPDU( is_network_message=True, message_type=NetworkMessageType.WHO_IS_ROUTER_TO_NETWORK, network_message_data=encode_network_message(msg), ) self._transport.send_broadcast(encode_npdu(npdu)) def _send_network_number_is(self) -> None: """Broadcast a Network-Number-Is message.""" if self._network_number is None: return msg = NetworkNumberIs( network=self._network_number, configured=self._network_number_configured, ) npdu = NPDU( is_network_message=True, message_type=NetworkMessageType.NETWORK_NUMBER_IS, network_message_data=encode_network_message(msg), ) self._transport.send_broadcast(encode_npdu(npdu))