Point Dictionary: ZONE
Zone point dictionary. These records describe the occupied space independently of the equipment serving it.
| Point | Kind | Unit | Brick | Derived | Provisional |
|---|---|---|---|---|---|
zone_temp | real | °C | Zone_Air_Temperature_Sensor | ||
zone_temp_sp_htg | real | °C | Zone_Air_Heating_Temperature_Setpoint | ||
zone_temp_sp_clg | real | °C | Zone_Air_Cooling_Temperature_Setpoint | ||
occ_sensor | bool | bool | Occupancy_Sensor |
zone_temp
Zone air temperature
- 223P: Sensor observes QuantifiableObservableProperty on the Zone (DomainSpace) via hasProperty
- QUDT unit:
DEG_C
brick:Zone_Air_Temperature_Sensor grep-verified in Brick 1.4.4. 223P attachment is to the zone DomainSpace rather than the VAV box; no reference-model instance checked for the zone-side pattern, but the property class and quantitykind (Temperature, DEG_C) follow the AHU temperature points.
zone_temp_sp_htg
Zone heating temperature setpoint
- 223P: QuantifiableActuatableProperty (setpoint) on the Zone via hasProperty
- QUDT unit:
DEG_C
brick:Zone_Air_Heating_Temperature_Setpoint grep-verified in Brick 1.4.4. Bind the ACTIVE (occupied-mode) heating setpoint the loop is controlling to, not a schedule default — same active-setpoint convention as the AHU dictionary’s sat_sp.
zone_temp_sp_clg
Zone cooling temperature setpoint
- 223P: QuantifiableActuatableProperty (setpoint) on the Zone via hasProperty
- QUDT unit:
DEG_C
brick:Zone_Air_Cooling_Temperature_Setpoint grep-verified in Brick 1.4.4. Active-setpoint convention as zone_temp_sp_htg.
occ_sensor
Occupancy sensor state (TRUE = occupied detected)
- 223P: EnumeratedObservableProperty on the occupancy Sensor via hasProperty