VFD Fault Rules
Variable frequency drive fault detection rules (VFD-*). Source
grounding: HVAC FDD Reference v1.0 ch.15, PNNL VFD O&M guidance, NIST’s
generic faulty-regulation work, and verified library hunting precedents (see
each card’s Deviations section). Application-agnostic: the same five rules serve
fan, pump, and other process drives, with the process-variable pair bound per
application.
Point dictionary: points/vfd.points.json.
Index
| ID | Name | Sev | Method | Status |
|---|---|---|---|---|
| VFD-0001 | Command vs feedback deviation | 2 | rule | verified |
| VFD-0002 | At minimum speed with load unsatisfied | 3 | rule | verified |
| VFD-0003 | At maximum speed with load unsatisfied | 3 | rule | verified |
| VFD-0004 | VFD process-loop hunting | 3 | rule | verified |
| VFD-0005 | VFD not in remote automatic control | 2 | rule | verified |
VFD-0001/0002 severity and method follow the reference’s ch.15 cards. The three library-authored expansion rules classify their adopted thresholds and source adaptations on-card.
Relationships
- All five rules share the
vfd-pump-faultsplaybook. - VFD-0001 suppresses the speed-limit and hunting rules when speed feedback is not trustworthy. VFD-0005 suppresses those same-drive automatic-loop rules while remote automatic authority is absent.
- No drive-control cluster is declared: mode, tracking, capacity, and tuning findings are peer symptoms without one causal trigger whose correction should clear the rest.