VAV Fault Rules

VAV terminal unit fault detection rules (VAV-*). Source grounding: HVAC FDD Reference v1.0 ch.10 (adapted authority — see each card’s Deviations section). The chapter’s economics are multiplicative: a building has dozens or hundreds of boxes, so a small per-box inefficiency — an oversized minimum, a leaking reheat valve — compounds into the “74% problem” class of building-wide waste. Excess minimum flow (VAV-0001) is PNNL’s top-performing office EEM.

Point dictionary: points/vav.points.json.

Index

IDNameSevMethodStatus
VAV-0001Minimum airflow setpoint too high3ruleverified
VAV-0002Rogue zone driving AHU reset3ruleverified
VAV-0003Reheat valve open with zone satisfied3ruleverified
VAV-0004Airflow tracking error3ruleverified
VAV-0005Damper hunting / oscillation3ruleverified
VAV-0006Reheat waste during cooling season3ruleverified
VAV-0010Zone temperature sensor drift (neighbor-median)3statisticalverified
VAV-0007VAV airflow tracking CUSUM3statisticalverified
VAV-0008Zone temperature CUSUM3statisticalverified
VAV-0009Reheat coil leakage CUSUM3statisticalverified

Severity and method per the reference’s ch.10 cards (its §5.8.2 index carries no severity column). VAV-0010 is the neighbor-median drift rule the CUSUM batch reserved: it adjudicates zone_temp (verdict: invalid_while_active), deciding whether the VPACC cards’ input can be believed.

VAV-0007/VAV-0008/VAV-0009 are the VPACC trio (NIST/CEC PIER Project 2.3 §5.1): two-sided CUSUM charts over the three per-box error signals, the library’s first feedback-loop topology (Discrete.UnitDelay accumulators with in-graph occupancy reset). A box without a discharge-air sensor runs 101/102 as the source’s reduced two-channel VPACC; 103 is the one channel that needs vav_dat. Parameter defaults are calibrated by the committed harness method (tools/simharness vavcal) plus the source’s Iowa Energy Center campaign, and remain per-box commissioning values on every card.

Relationships

  • VAV-0001 / 052 / 055 are the zone-level reheat-waste family — the terminal-unit end of CLU-02’s “74% problem” (AHU-0019/AHU-0023 see the same defect from the air handler’s side via zone_reheat_fraction).
  • VAV-0002 is the zone-side cause of the reset failures AHU-0023/AHU-0024 detect at the AHU: one rogue zone holds the reset down for everyone.
  • VAV-0004/VAV-0005 are the box-mechanics pair (tracking and stability); VAV-0005 is AHU-0022’s zone-level sibling and reuses its detector patterns.