FPB Fault Rules

Fan-powered terminal rules (FPB-*) cover series and parallel fan-powered VAV terminal units, also called fan-powered boxes, fan-powered terminal units, or FPUs. Ordinary VAV boxes remain in vav; fan coils remain in fcu.

Point dictionary: points/fpb.points.json. Brick 1.4.4 provides only generic Terminal_Unit; ASHRAE 223 PPR2.1 provides exact FanPoweredTerminal. Series/parallel identity is deployment topology.

ConcernSeries FPBParallel FPB
Fan locationIn the primary/discharge path, generally continuous when occupiedParallel plenum-air branch, often heating/low-flow operation
Primary airflowThrough primary damperThrough primary damper
Reheat coilTypically downstream of fanIn fan/reheat branch before mixing, per actual unit topology
Fan proof ruleApplicable when commandedApplicable when commanded
Airflow trackingPrimary airflow onlyPrimary airflow only; does not prove fan-branch airflow
Reheat delta-T bindingDirect coil inlet/outletMust remain branch-local or use a validated derived point

Excluded: ordinary single-duct VAV boxes without terminal fans, FCUs, induction units without commanded fans, dual-duct boxes without explicit compatibility, and electric-reheat-only units for the hydronic valve rule.

Index

IDNameSevMethodStatus
FPB-0001Terminal fan proof-of-operation failure2ruleverified
FPB-0002Primary airflow tracking failure3ruleverified
FPB-0003Reheat valve closed with unintended temperature rise3ruleverified
FPB-0004Terminal fan airflow degradation3statisticalverified
FPB-0005Primary airflow sensor disagreement3metaverified
FPB-0006Reheat-coil heat-transfer degradation3statisticalverified

Minimum telemetry tiers

TierPointsSupported rules
Basicfan command/status, primary flow/setpointFPB-0001..0002
Reheat+ valve and coil inlet/outlet temperatures+ FPB-0003
Performance+ fan airflow/expected airflow and expected coil delta-T+ FPB-0004, FPB-0006
Sensor redundancy+ independent primary airflow reference+ FPB-0005

Expected/reference points are host-derived contracts, not guesses. Each deployment records known-good fit data, model/version, inputs, accuracy, same-path scope, freshness, domain checks, and update/freeze policy. A model using the point it is supposed to check is circular and invalid.

Source and validation posture

The LBNL simulated FPU dataset (DOI 10.25984/1881324) documents PFPU/SFPU topology and publishes HVACSIM+ cases spanning 365 days at one-minute resolution, 109 points, fault-free cases, and ten fault categories. It is a future validation source, not evidence for the library-authored thresholds in this slice; the adapter is deferred to PR11.

Relationships

  • FPB-0001 supplies direction-sensitive fan-proof context; no whole-rule suppression is safe for FPB-0002/0003.
  • FPB-0002 is the primary-stream sibling of VAV-0004 and relates upstream AHU static/reset signatures without claiming their causes.
  • FPB-0003 is the coil-local leakage sibling of FCU-0005/VAV-0009; FPB-0006 asks the opposite full-command performance question. Neither joins CLU-01.
  • FPB-0004 separates proven operation from delivered fan-path airflow. FPB-0001 remains direction-sensitive context, not a whole-rule suppressor.
  • FPB-0005’s ambiguous adjudication reports disagreement without automatically choosing the physical sensor or host reference as the failed member.